Honeywell CLOUDLINK 4G M1 Скачать руководство пользователя страница 3

4

5

6

7

Installing CloudLink 4G M1 Modem in MiWireless as example (pivot panel)

1

2

3

EXT

-PWR

COMMON

EXT

-PWR

COMMON

4

Position the mounting tabs onto the slots of the 
bracket and torque the captive screw

Connect the CloudLink 4G M1Modem antenna using

a wrench with torque 4-6 IN-LB

Connect the serial cable (RS232) from the CloudLink
Modem to terminal block of MiWwireless* (Do not 
connect into RS485 slot)

Connect the power supply cables from the terminal 

block as shown in the figure. Red wire to EXT-PWR

pin and Common to any one of the pins

* When there is a Protocol Translator board connect the serial cable (RS232) from the PT board to the CloudLink Modem.

Note : For information on retrofit kit details, please refer the document# 22-3015 & 22-3170.

Install the 4G antenna on the MiWireless 
device by tightening the nut

Screw the mounting bracket onto the 
Pivot/Sub panel to hold the Modem 

Remove the existing 3G antenna

Содержание CLOUDLINK 4G M1

Страница 1: ...orrectors and data loggers No additional software is required In addition MasterLink is now available as an application that can be installed on iOS and Android devices This handout is meant to be a quick reference on getting started with the Cloud Link 4G M1 Modem device Regulation Standards Figure Cloud Link 4G M1 Modem Easy to configure and retrofit Simple to use through BLE serial interfaces Des...

Страница 2: ...tic Reed Switch Battery Connector Configuration Port External Power Input Mounting tabs Default Switch A B C D E E X T P W R C O M M O N Open the SIM cover and insert the SIM card into SIM card holder Connect the antenna Connect to battery power or external power supply Fold along the dashed line Configure port with 9600 Baud Rate RS232 for serial connection Connect the serial port cables ...

Страница 3: ... block of MiWwireless Do not connect into RS485 slot Connect the power supply cables from the terminal block as shown in the figure Red wire to EXT PWR pin and Common to any one of the pins When there is a Protocol Translator board connect the serial cable RS232 from the PT board to the CloudLink Modem Note For information on retrofit kit details please refer the document 22 3015 22 3170 Install the...

Страница 4: ...ww honeywellprocess com or contact your Honeywell Process Solutions representative Honeywell Process Solutions 1280 Kemper Meadow Drive Cincinnati OH 45240 www honeywellprocess com Phone 1 513 272 1111 MI TAC Support Honeywell com Configuring CloudLink 4G M1 Modem using MasterLink desktop App Connect the Modem with USB to serial cable and login to the app with registered credentials Navigate to the...

Отзывы: