Honeywell CHRONOTHERM IV DELUXE T8624D Скачать руководство пользователя страница 20

T8624D CHRONOTHERM

®

 IV DELUXE PROGRAMMABLE THERMOSTAT

68-0166—1

20

Honeywell Europe S.A.
3 Avenue du Bourget
1140 Brussels
Belgium

Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7

Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325

Helping You Control Your World

®

68-0166—1   J.H.   Rev.  10-97

Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.

WIRING DIAGRAM (FIG. 14)

Fig. 14. Typical hookup of T8624D in multistage system.

W2

L1
(HOT)

L2

M11309

FAN
RELAY

Y1

G

C

THERMOSTAT

RC

HEAT
RELAY 
1

R

W1

L1
(HOT)

L2

COMPRESSOR
CONTACTOR 1

Y2

COMPRESSOR
CONTACTOR 2

HEATING 
TRANSFORMER

COOLING
TRANSFORMER

HEAT
RELAY 
2

OT

OT

B

HEAT
DAMPER

OUTDOOR
SENSOR

COOL
DAMPER

O

2

2

3

3

3

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
ONE TRANSFORMER SYSTEM.

CAN BE USED FOR CHANGEOVER VALVE ON HEAT 
PUMP SYSTEMS.

1

1

www.honeywell.com/yourhome

Содержание CHRONOTHERM IV DELUXE T8624D

Страница 1: ... with outdoor temperature sensor capability for homeowner convenience The sensor is also more accurate than a thermometer Configurable features allows one model to be used to replace many different models less inventory no longer need to carry separate models to get these features F or C temperature display automatic or manual changeover electric or conventional heat fan operation adjustable heati...

Страница 2: ...ide features listed in Table 1 Table 1 Thermostat Features Temperature Ratings Operating Ambient 40 F to 110 F 4 C to 43 C Shipping 30 F to 150 F 34 C to 65 C Display Accuracy 1 F 0 5 C Setpoint Range Heating 40 F to 90 F 7 C to 31 C Cooling 48 F to 99 F 9 C to 37 C Differential 3 F 1 5 C Default Settings see Table 3 Table 3 Default Setpoints Changeover System Selection Fan Selection Comments Auto...

Страница 3: ...te horizontally on the wall or on a 2 in x 4 in wiring box 1 Position and level the wallplate for appearance only The thermostat will function properly even when not level 2 Use a pencil to mark the mounting holes See Fig 3 3 Remove the wallplate from the wall and drill two 3 16 inch holes in the wall if drywall as marked For firmer material such as plaster drill two 7 32 inch holes Gently tap anc...

Страница 4: ...near each terminal for identification Refer to Table 4 for terminal designations CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 4 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole ...

Страница 5: ...er or changeover valve Output 24V powered contact C Ba C X1 X2 Common Input G F Fan relay Output 24V powered contact O R Cool damper or changeover valve Output 24V powered contact OT OT Outdoor temperature sensor C7089B Input R V 24V system or heating transformer Input RC 24V cooling transformer Input W1 H1 R3 Stage 1 heating relay Output 24V powered contact W2 H2 R4 W3 Y Stage 2 heating relay Out...

Страница 6: ... as follows On Fan operates continuously Auto Fan operates with equipment Fig 7 T8624D System and Fan key locations Fig 6 T8624D key locations and descriptions M15042 Hold Temp Run Program Copy Daylight Time Set Current Day Time System Fan Time Set Program Day System Fan Wake Leave Return Sleep Heat Cool Settings M10405A Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake L...

Страница 7: ...Setup feature To enter the Installer Setup press and hold the Information i key with the increase and decrease keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 8 and 9 To advance to the next Installer Setup press the Time key Period Time Heat Setpoint Cool Setpoint Fan Setting Wake 6 00 AM 70 F 21 C 78 F 25 ...

Страница 8: ...erature is displayed in F 1 Temperature is displayed in C Not used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not used 17 and 18 Extended fan operation in heating 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in cooling 20 0 No extended fan operation after the call for coo...

Страница 9: ...elect change Display Description Display Description Setting Not used 31 and 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Temperature range stops in heating 34 90 Highest setpoint heating can be set to 40 to 89 Temperature range 1 F increments heating ...

Страница 10: ...uto System Fan Wake Room AM DST Tue Heat INSTALLER SYSTEM TEST Use the Installer System Test to check the thermostat operation Refer to Table 7 for a list of the available system tests To start the system test CAUTION The minimum off time for compressors is bypassed during the Installer System Test Equipment damage can occur if the compressor is cycled too quickly Press and hold the increase and d...

Страница 11: ...em fan turn off Cooling Equipment System Test Time 30 Change from heating to cooling equipment system test 31 Stage one cool and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Stage two cool turns off 30 Stage one cool and system fan turn off Fan Equipment SystemTest Time 40 Change from cooling to fan equipment system test 41 Fan comes on 40 Fan turns off ...

Страница 12: ...g Monday Wake 6 00 AM 70 F 21 C 78 F 25 5 C Auto Leave 8 00 AM 62 F 16 5 C 85 F 29 5 C Auto Return 6 00 PM 70 F 21 C 78 F 25 5 C Auto Sleep 10 00 PM 62 F 16 5 C 82 F 28 C Auto Tuesday Wake 6 00 AM 70 F 21 C 78 F 25 5 C Auto Leave 8 00 AM 62 F 16 5 C 85 F 29 5 C Auto Return 6 00 PM 70 F 21 C 78 F 25 5 C Auto Sleep 10 00 PM 62 F 16 5 C 82 F 28 C Auto Wednesday Wake 6 00 AM 70 F 21 C 78 F 25 5 C Auto...

Страница 13: ... Heat Cool Settings Daylight Time Daylight Time Copy AM DST Tue Set Day Time 4 Press Run Program M10316 Time Set Program System Fan Run Program Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Auto System Fan Wake Room AM DST Tue Heat M10317 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Wake Leave Return Slee...

Страница 14: ...m the day displayed M10325 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Day Heat Cool Settings Daylight Time Copy Heat Auto System Fan Wake Mon AM Set Program Start Time Setting Heat M10326 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Copy Mon 4 Press Da...

Страница 15: ...hange between heat and cool settings M10336 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Cool Setting 4 Press increase or decrease key to adjust temperature settings M10336 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Cop...

Страница 16: ...ad changes This is a phenomenon that most people in the industry know and accept Many factors contribute to offset including switch differential thermal lag overshoot cycle rates and system load The thermostat microprocessor simultaneously gathers compares and computes data Using this data it controls a wide variety of functions The special proprietary algorithm program in the thermostat eliminate...

Страница 17: ...at is turned on a startup and initialization program begins The startup occurs only on initial powerup After total loss of power for an extended period the current time and day may need to be set but the user program is held See Table 11 for the default values NOTE Immediately following initialization the user can enter new setpoints to be used in place of the default values Period Time Heat Setpo...

Страница 18: ...0 to 90 F 7 to 31 C Cooling limits are 48 to 99 F 9 to 37 C or the cooling lower The setpoint temperature range stops were configured Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops Heating or cooling come on momentarily and shut off Heat or cool circuit is opening up or becoming high impedance Add resistor in parallel with load or install interface relay System on indic...

Страница 19: ...over to auto in Installer Setup 12 T8624D1063 Trane Premier White color T8624D2004 Wiring differences old new B C jumper R to Rc taupe color Symptom Possible Cause Action Cooling will not come on No power to the thermostat Check for 24 Vac between R and C If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if ...

Страница 20: ...rol Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers WIRING DIAGRAM FIG 14 Fig 14 Typical hookup of T8624D in multistage system W2 L1 HOT L2 M11309 FAN RELAY Y1 G C THERMOSTAT RC HEAT RELAY 1 R W1 L1 HOT L2 COMPRESSOR CONTACTOR 1 Y2 COMPRESSOR CONTACTOR 2 HEATING TRANSFORMER COOLING TRANSFORMER ...

Отзывы: