Honeywell CHRONOTHERM III T8611M Скачать руководство пользователя страница 27

27

68-0076—1

Press and release to return to normal
operation.

CHECKING THE PROGRAM
TIMES AND TEMPERATURES

If desired, check all the stored settings

without affecting the permanent program.

Press and hold until the desired period shows
on the display. The start time and tempera-
ture setting will appear on the display.

Press and release to display the next day
time and temperature for that period.

Press and release to return to normal opera-

tion.

CHECKING THE CURRENT
TEMPERATURE SETTING

Press a single key to compare actual
room temperature to the setting at any

time.

Press and release. The display will show
the current temperature setting for several
seconds, then revert to the room tempera-
ture.

During recovery from energy savings, the
setting displayed will not match the pro-
grammed setting. This is because the ther-
mostat gradually changes the temperature
setting during recovery to provide maxi-
mum comfort combined with most effi-
cient use of the heating or cooling equip-
ment.

 Operation

The T8611M Thermostat provides automatic control of

multistage heat pump systems with up to three stages of
heat and up to two stages of cool. The first heat stage is the
heat pump and the last stage is electric, gas, or oil auxiliary
heat. T8611M provides automatic changeover from heat
to cool or cool to heat.

ADAPTIVE INTELLIGENT RECOVERY™
OPERATION

Adaptive Intelligent Recovery™ is the Honeywell trade-

mark for the way the T8611 controls the heating and
cooling equipment during recovery from an energy sav-
ings setting to a comfort setting. During recovery, the
control point changes gradually rather than jumping from
the energy savings setting to the comfort setting all at once.
This provides additional energy savings.

When Adaptive Intelligent Recovery™ is used in the

heating mode, the control point raises gradually, maximiz-
ing the use of the more economical heat pump to bring the
sensed temperature to the desired comfort setpoint. This
minimizes the use of the typically more expensive auxil-
iary heat.

In both heating and cooling, the thermostat monitors

recovery each day and adjusts the next day recovery start
time. This ensures that the building is at the desired
temperature at the programmed time, regardless of the
outdoor temperature. Recovery time varies depending on

the weather conditions and the building heating/cooling
system.

The advantages are:

• The comfort setting is achieved at the programmed

time and maintained regardless of weather condi-
tions; occupants come home and wake up to com-
fort.

• Drafts from low temperature discharge air are mini-

mized during occupied periods.

• The thermostat automatically uses the more eco-

nomical heat pump as the primary heat source dur-
ing heat mode recovery, avoiding the use of the
expensive auxiliary heat.

• Comfort and energy savings can be achieved in both

heating and cooling.

• Reduces heat pump compressor cycling, extending

equipment life.

Use of Outdoor Thermostats

Because Adaptive Intelligent Recovery™ calls for aux-

iliary heat only when it is truly needed, it eliminates the
need for outdoor thermostat(s). If an outdoor thermostat is
used with T8611 and it is set close to the balance point, the
recovery time from energy savings will be prolonged
because the outdoor thermostat will prevent operation of

PERIOD

DAY

RUN

PROGRAM

M2751

SET
PT

    HEAT

M2748

SET
PT

PM

FRI

NIGHT

    HEAT

M2749

SET
PT

PM

SAT

NIGHT

    HEAT

M2750

SET
PT

PM

FRI

EVENING

T8611M

OPERATING THE THERMOSTAT • OPERATION

PRESENT

SETTING

Содержание CHRONOTHERM III T8611M

Страница 1: ...ous time of day day of week cur rent period and room temperature AdaptiveIntelligentRecovery bringsroomtem perature to programmed temperature at program med time maximizing comfort and energy sav ings Temperature control program maintains tempera ture within 1 F of setpoint Temporaryprogramoverrideavailablebyusing WARMER and COOLER keys SKIP next period key CHANGE to last period key HOLDTEMPkeypro...

Страница 2: ...tat heating and cooling ON cycles EM HT LED red on subbase lights when system switch is in EM HT On some systems light may indicate need to switch to EM HT because of heat pump problem AUX HT LED green on subbase lights when ther mostat is calling for operation of auxiliary heat CHECK LED yellow on subbase lights when an equipment or system problem needs to be checked Consult heat pump literature ...

Страница 3: ...ting dimensions in in mm 4 121 3 4 3 83 5 16 7 179 1 46 13 16 5 135 5 16 M5181A 4 3 32 104 1 31 32 50 Fig 2 202905AA Remote Sensor dimensions in in mm 4 3 32 104 FRONT 1 31 32 50 SIDE M5244 2 51 1 31 32 50 41 64 16 3 8 1 19 64 9 64 1 2 8 4 DIA 13 35 1 25 BACK ...

Страница 4: ...STEM RUN PROGRAM PERIOD TIME TEMPERATURE PRESENT SETTING SKIP NEXT PERIOD CHANGE TO LAST PERIOD SET PRESENT DAY TIME HOLD TEMP DAY SET HEAT COOL CANCEL PERIOD COPY FROM AHEAD WARMER BACK COOLER M5360 WED MIDDAY AM HEAT ON HEAT OFF COOL ON AUTO FAN ROOM COPY TO ...

Страница 5: ...ate equipment and thermostat IMPORTANT The T8611 requires a conductor to trans former common to provide continuous 24V power for thermostat operation This feature is commonly specified and provided by equipment manufacturer IF RETROFIT REPLACEMENT APPLICATION CONSIDER equipment requirements systemswitching manual EM HT HEAT OFF COOL automatic EM HT HEAT OFF AUTO COOL unique heat pump functions of ...

Страница 6: ... Y2 If applying T8611M to 1 stage cooling system leave Y2 Stage 2 cool unconnected Second Stage Heat W2 If applying T8611M to 2 stage heat systems in which the Auxiliary Resistive second stage is compressorized connect stage 2 to W2 Third Stage Heat W3 leave W3 unconnected If 2 stage heat system in which the second stage is auxillary electric resistive connect auxiliary stage to W3 leave W2 unconn...

Страница 7: ...rich a na na na na Changeover on heat check LED optional Bard a N1024 F1261 N1036 F1299 Changeover on heat typical R1129 L1181 R1146 L1185 checkLEDoptional equipment terminal W1 to thermostat B Bryant Day Night Payne b a b b G1451 F1113b G1166 F1125 Check LED optional F X1 a G1261 F1253 jump X2 to C Note P terminal a J1010 L1371 G1174 available on manual changeover a R1335 L1405 T8611R models only...

Страница 8: ...lay isolation Crispaire Marvair G1089 F1162 G1208 F1166 F1204 F1323 R1111 L1215 R1156 L1094 Fedders Airtemp Climatrol a C1398 L1090 C1509 L1102 Separate first stage heat cool a C1406 C1517 terminals required check LED a C1414 C1541 optional equipment terminal K to thermostat E Florida Heat Pump a na na na na Optional check LED X X1 jump X2 to C Heatwave Southwest Mfg G1105 F1170 G1232 F1224 Heil Q...

Страница 9: ...t R1004 B1042 R1008 B1046 Y W1 to B K to E B1109 R1057 L1037 R1152 L1207 R1198 L1227 R1285 L1157 R1350 L1181 Janitrol Tappan G1147 F1139 G1109 F1117 Equipment terminal C to thermostat C Lennox NOTE Rewire for single 75 VA transformer if two transformer system G1014 F1113 G1026 F1067 G1022 E1148 G1125 E1019 C G1162 G1091 DoD specs use guard G1154 F1105 G1323 L1201 R1024 B1160 R1040 B1202 R1178 L135...

Страница 10: ...PB series separate first stage heat cool a na na na na Late PE series optional check LED X1 X1 jump X2 to R Rheem Ruud G1097 F1238 G1133 F1158 G1238 G1141 L1157 R1081 L1045 G1220 R1107 L1136 R1079 R1095 Square D Sun Dial a C1224 F1071 C1525 F1182 Separate first stage heat cool required optional check LED X X1 jump X2 to R Trane General Electric a G1204 J1043 G1059 J1039 Optional check LED F X1 jum...

Страница 11: ...ransformer G1281 Westinghouse G1048 F1121 G1034 F1141 F1246 F1091 F1279 F1257 J1019 J1013 J1050 J1062 R1103 L1108 R1149 L1110 L1173 L1128 L1151 na na na na Separate first stage heat cool ter minals required D1108 L1223 G1356 L1219 2 speed heat pump optional check LED L X1 jump X2 to C White Rodgers na na na na 1F58 910 S28 series Williamson R1236 L1348 na na N1008 F1196 na na Changeover on heat W1...

Страница 12: ...spots behind doors in corners or under cabinets hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas behind the sensor such as an outside wall IF REPLACING AN EXISTING THERMOSTAT Turn thermostat power off at furnace or heat pump This thermostat requires a single transformer A two transformer system may require turning off two switches ...

Страница 13: ...crews Fig 6 Mounting remote sensor base on wall WIRING All wiring must comply with local electrical codes and ordinances Disconnect power before wiring to prevent electrical shock or equipment damage The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections Either method is acceptable Push excess wire back into the hole and plug hole with nonhard...

Страница 14: ...STEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW FAULT DETECTION SWITCH SWITCH TO C COMMON SIDE OF SYSTEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW SWITCHING DEVICE SWITCH IN SECONDARY OF SEPARATE TRANSFORMER L1 HOT L2 24 Vac 1 MONITOR AUXILIARY HEAT RELAY HEAT 2 L1 HOT L2 HEAT OFF AUTO SYSTEM SWITCH COOL 1 COOL 2 AUTO ON FAN SWITCH 7 1 R C L W3 W2 E G O B Y Y2 X2 STAGE 2 HEAT RELAY EMERGENCY ...

Страница 15: ...LOW FAULT DETECTION SWITCH SWITCH TO R POWER SIDE OF SYSTEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW FAULT DETECTION SWITCH SWITCH TO C COMMON SIDE OF SYSTEM TRANSFORMER TO R TO C X2 X1 CHECK LED YELLOW SWITCHING DEVICE SWITCH IN SECONDARY OF SEPARATE TRANSFORMER L1 HOT L2 24 Vac 1 M1018D HEAT 2 L1 HOT L2 HEAT OFF AUTO SYSTEM SWITCH COOL 1 COOL 2 AUTO ON FAN SWITCH 4 1 R C L W3 W2 E G O B Y Y2...

Страница 16: ...T RELAY L1 HOT L2 HEAT OFF AUTO SYSTEM SWITCH COOL 1 AUTO ON FAN SWITCH 4 1 R C L W3 W2 E G O B Y Y2 X2 EMERGENCY HEAT RELAY FAN RELAY CHANGEOVER RELAY HEAT STAGE 1 COMPRESSOR CONTACTOR 3 C O EM HT COOL X1 CHANGEOVER RELAY COOL AUX HEAT LED GRN HEAT 3 EM HEAT LED RED HIGH LIMIT C O HEAT 1 HIGH LIMIT CHECK LED YELLOW 2 S1 S2 S3 S1 S2 S3 AA AA A A AA AA AA AA 202905 REMOTE SENSOR 5 X2 X1 CHECK LED Y...

Страница 17: ...he display will flash REPL BAT Homeowner will have 20 30 seconds to install new batteriesafterremovingoldbatteriesfrombackofthermo stat After 20 30 seconds it will be necessary to repro gram REPL BAT indication will disappear within 5 10 minutes when thermostat is remounted on the powered subbase IMPORTANT Forproperthermostatoperation always replace dead batteries with new alkaline batteries If ba...

Страница 18: ...hould shut off followed by the fan NOTE On an AUTO changeover thermostat the cooling temperature must be set at least 3 F 2 C above the heating temperature or display will flash COOLING CAUTION Do not operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s recommendations NOTE When cooling setting is changed thermostat will wait up to five minutes before turning on the co...

Страница 19: ...enter self test 3 Press each key as listed below and look for re sponses listed as key is held down and released Keys may be pressed in any order except RUN PROGRAM should be pressed last because it ends self test M 525A AM SUN MORNING REPL BAT SET PT ROOM PM OUTDOOR TUE WED THU FRI SAT TEMPORARY MON MIDDAY EVENING NIGHT COOL ON HEAT ON CHANGE TO LAST PERIOD SKIP NEXT PERIOD PRESENT SETTING PRESEN...

Страница 20: ...ows 1 00 PM Mon Press and hold until the current day ap pears in the display Press and hold until the current time ap pears in the display Be sure AM or PM appears as desired This completes setting the current day and time Go on to Step 2 STEP 2 SETTING THE PROGRAM TIMES AND TEMPERATURES FOR ONE DAY Chooseadaytoprogramfirst Monday is used in the examples Start by pro gramming the MORNING time and ...

Страница 21: ...to start the energy saving period Press and hold until the display shows the desired temperature NOTE It is possible to cancel any period showing on the display ex cept MORNING by pushing the CANCEL PERIOD key To move to the next period while program ming simply press the PERIOD key again Program the EVENING time and tem perature if desired Press and release The display shows EVENING but no time o...

Страница 22: ...s 72 F the minimum cooling setting is 75 F To set the cooling temperature lower first lower the heating setting Press and release The display shows the preprogrammed cooling temperature and theprogrammedstarttimeforMORNING Press and hold until the display shows the desired cooling temperature for MORN ING Press and release The display shows the preprogrammed cooling temperature and the programmed ...

Страница 23: ...til all days are shown not flashing press COPY TO key once more Press and release to copy the program into all the days selected STEP 4 SETTING THE SCHEDULES AND TEMPERATURES FOR THE REMAINING DAYS Use the procedures described in Steps 2 and 3 and summarized in this step to program the remaining days Press and release to enter the programming mode Press and hold until the day desired to program sh...

Страница 24: ...air cleaning FAN AUTO Normal setting for most homes and businesses The fan starts and stops with the compressor in heat pump systems when the system switch is set to HEAT AUTO or COOL When system switch is set to EM HT the fan operates withtheauxiliaryheat onsomemodels EM HT The thermostat controls only the backup heat The heat pump is off HEAT Thethermostatcontrolstheheat ing system OFF Both the ...

Страница 25: ...OOL AUTO M2756 IMPORTANT The CHANGE feature will be operable the day after the thermostat has been programmed and operating The thermostat requires this time to learn the programmed schedule To temporarily raise or lower the tem perature for the current period only To change back T8611M PROGRAMMING THE THERMOSTAT OPERATING THE THERMOSTAT M2736 SET PT PM TUE MIDDAY EVENING M2737 MORNING SET PT PM T...

Страница 26: ...ing After a few seconds the display will show the current temperature Press and release to check the temperature setting Pressandreleasetocancelmanualcon trol CANCELING PROGRAM SETTINGS The thermostat requires time and tem peraturesettingsintheMORNINGtime period for each day but any of the others can be canceled Each time period for each day must be canceled separately Press and hold until the des...

Страница 27: ...ysavingssettingtothecomfortsettingallatonce This provides additional energy savings When Adaptive Intelligent Recovery is used in the heatingmode thecontrolpointraisesgradually maximiz ing the use of the more economical heat pump to bring the sensed temperature to the desired comfort setpoint This minimizes the use of the typically more expensive auxil iary heat In both heating and cooling the the...

Страница 28: ...imes will shorten as the control point approaches the comfort setpoint During the comfort period theheatpumpisoncontinuouslyandauxiliaryheat cycles until the next energy savings period When energy saving begins the heat pump cycles off until the sensed temperature falls below the control point Although the heat pump comes on when the sensed temperature falls below the control point the sensed temp...

Страница 29: ... TO BE ADJUSTED ON A REGULAR BASIS WARMER COOLER KEYS BEING USED TO ADJUST TEMPERATURE REPROGRAM THERMOSTAT TO MAKE PERMANENT CHANGE IN PROGRAM WARMER COOLER KEYS ARE TEMPORARY UNLESS PERIOD KEY IS PRESSED FIRST PROGRAM IS LOST DUE TO POWER OUTAGE OR DISPLAY GOES BLANK WHEN POWER IS TURNED OFF BATTERIES ARE INCORRECTLY INSTALLED REMOVE AND REPLACE PER MARKINGS ON THERMOSTAT BATTERIES ARE DEAD REPL...

Страница 30: ...period when the owner can set back heating or set up cooling the temperature for energy savings because family members are asleep or the building is unoccupied Often a NIGHT energy savingstemperatureissetonlyfortheheatingseasonso family members can sleep cool in summer Glossary AUX HT light green This light glows whenever the thermostat is calling for operation of the backup heater Backup auxiliar...

Страница 31: ...etting the Program Times and Temperatures for One Day 20 Copying the Program to the Desired Days 23 Setting the Schedules and Temperatures For the Remaining Days 23 Setting the System and Fan Switches on the Subbase 24 Operating The Thermostat 25 Temporarily Changing the Program 25 Reprogramming the Thermostat 26 Holding a Temperature for Extended Absence 26 Canceling Program Settings 26 Checking ...

Страница 32: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Отзывы: