INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat oper-
ation. Refer to Table 4 for a list of the available self-tests. 

CAUTION

Equipment Damage Hazard.  
Minimum compressor off-time is bypassed 
during Installer System Test.

Avoid cycling compressor quickly.

To start the self-test:
Press and hold the increase 

!

 and decrease 

"

 keys at 

the same time until 10 appears. All segments of the 
display are displayed before the 10 appears. See Fig. 12 
and 13.

Fig. 12. Display of all LCD segments.

Fig. 13. Display of test number.

Refer to Table 5 for the directions and results of the 
specific tests.

NOTE: Press Time 

  to advance to the next test and 

Time 

 to go back to the previous test. Press 

Run Program to exit the self-test.

NOTE: Press any key and the displayed numbers 

change. Press Time 

∇ 

to go to the previous test 

and Time 

 to go to the next test. The Run    

Program key does not exit this test. Press   
Time 

or Time 

 and then the Run Program key 

to exit.

Table 4. Tests Available In The Installer Self-Test.

Test 

Number

System Test Description

10-19

Heating equipment can be turned on and off

30-39

Cooling equipment can be turned on and off

40-49

Fan equipment can be turned on and off

60 0 to 

60 19

Keyboard keys test

70-79

Thermostat information including date code 
and software versions are displayed

M14559

Aux Ht

Set Day/Time

Set Program

Mon
Wake Leave Return

Sleep

Outdoor

Room

Filter

Wait

FFan

Em Heat

O

n

Auto

O

ff

Cool

Auto

AM

PM

Hold for

Heat Cool

Repl Batt

Recovery

DST

Tue Wed Thu Fri Sat Sun

Days

Temporary Setting

Em Ht

M14612

Table 5. Installer Self-Test Options.

Key to 

Press

Test 

Number

Description

Heating Equipment System Test

Time 

10

Enter heating equipment system test

 

!

11

Heat comes on. When Installer Setup 
number 2 is 1, the system fan is also 
energized

"

10

Heat and system fan turn off

Cooling Equipment System Test

Time 

30

Change from heating to cooling 
equipment system test

 

!

31

Cool and system fan come on

"

30

Cool and system fan turn off

Fan Equipment System Test

Time 

40

Change from cooling to fan 
equipment system test

 

!

41

Fan comes on

"

40

Fan turns off

Key Equipment System Test

Time 

60

Change from fan to key operation 
system test

Содержание Chronotherm Deluxe T8601D

Страница 1: ...fully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat...

Страница 2: ...ed holes until flush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening 5 Loosely insert the mounting screws into the holes 6 Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 through 5 for typical hookups A letter code is located near each terminal for identification CAUTION Electrical Hazard...

Страница 3: ... CAN BE USED FOR CHANGEOVER VALVE ON SINGLE STAGE HEAT PUMP SYSTEMS AVAILABLE ON SELECT MODELS OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE 2 2 2 1 3 OT OT OUTDOOR TEMPERATURE SENSOR 3 L1 HOT L2 M10354 FAN RELAY Y G THERMOSTAT RC HEAT RELAY R W L1 HOT L2 COMPRESSOR CONTACTOR HEATING TRANSFORMER COOLING TRANSFORMER B C HEAT DAMPER COOL DAMPER O 2 1 POWER SUPPLY PROVIDE DISCONNECT M...

Страница 4: ...nuously Auto Fan operates with equipment Fig 9 Thermostat System and Fan key locations NOTE Always press the keys with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard M14624 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy INCREASE TEMPERATURE SETTING OR...

Страница 5: ... To advance to the next Installer Setup press the Time key To change a setting use the increase or decrease key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Setup press Run Program Fig 10 Display of all LCD segments Fig 11 Display of Installer Setup number and setting CAUTION Electric Heat System Configuration Hazard Can cause equipment damage Configure e...

Страница 6: ...system starts recovery at programmed time Degree temperature display 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not used 17 and 18 Extended fan operation in heatinga 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended...

Страница 7: ...splayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actu...

Страница 8: ...ber of days remaining at any time by pressing the i key three or four times If more than one timer is active all active timers show sequentially when pressing the i key several times M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System F...

Страница 9: ... exit Table 4 Tests Available In The Installer Self Test Test Number System Test Description 10 19 Heating equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment can be turned on and off 60 0 to 60 19 Keyboard keys test 70 79 Thermostat information including date code and software versions are displayed M14559 Aux Ht Set Day Time Set Program Mon Wak...

Страница 10: ...software identification code Example 02 software ID code 2 4 Press the increase key again to display the software revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the self test The self test times out after four minutes without any key presses CHECKOUT Outdoor Tempera...

Страница 11: ...perature settings do not change Example Cannot set the heating higher or the cooling lower The upper or lower temperature limits were reached Check the temperature setpoints Heating limits are 40 to 90 F 4 5 to 32 C Cooling limits are 48 to 99 F 7 to 35 C The setpoint temperature range stops were configured Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops Heating does com...

Страница 12: ...t to Cool Set system selection to Cool Cool setpoint is above room temperature Check cooling setpoint Set cooling setpoint to desired temperature System on indicator flame heat snowflake cool is displayed but no warm or cool air is coming from the registers Fan operation set for 0 conventional heat when it should be set for 1 electric heat Enter Installer Setup number 2 and reconfigure the fan ope...

Отзывы: