CLCM1H,6H,6T DIGITAL WALL MODULES 

– INSTALLATION INSTRUCTIONS 

Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

 

 
CentraLine 
Honeywell GmbH 
Böblinger Strasse 17 
71101 Schönaich, Germany 
Phone  +49 (0) 7031 637 845 
Fax 

+49 (0) 7031 637 740 

[email protected]

 

www.centraline.com 

 

 
 
 
 
 
 
Subject to change without notice 
MU1Z-0902GE51 R0416C 

 

 

 

 

 

Explanation:

 The goal of this action is to reset those overrides which 

a room user has enacted at the wall module. Thus, in, e.g., hotels 
and office buildings, a typical requirement is to remotely reset the 
wall module setpoint override to zero, and to remotely reset the wall 
module fan speed override to “Auto”. 

NOTE:

 

If the wall module has been set to OFF by the room 
user, it cannot be reset to auto. 

In the case of PANTHER controllers

, this reset can be 

done by sending 6 Volt (= “unoccupied”) to the LED input of 
the wall module: 

As long as 6V is being sent to the LED input 
•  the wall module will be in “unoccupied” 
•  the local setpoint and/or fan speed setting will be reset 

and disabled. 

As long as 10V is being sent to the LED input 
•  the wall module will be in “occupied” 
•  the local setpoint and/or fan speed setting will be 

enabled. 

In the case of SERVAL controllers

, this reset can be done 

by switching from 

“occupied” to “unoccupied”. This will send a 

specially coded SERVAL signal to the LED input of the wall 
module. 

"Unoccupied"

 means: 

 

Effective Unoccupied (moon on continuously) or 

 

Override Unoccupied (moon flashing). 

"Occupied"

 means: 

 

Effective Occupied (sun on continuously), or 

 

Override Occupied (sun flashing). 

P9  Limit setpoint 

 - 

 

Limits setpoint to ±

0 … 5 Celsius (if set to °C) or to 

±

0 … 9 °F (if set to °F). 

Default (if set to °C): 

P9:5

 

Default (if set to °F): 

P9:9

 

Example

 (units set to °C): A setting of 

means that the 

set point offset is limited to -3 to +3 °C. 

Example

 (units set to °F): A setting of 

means that the 

set point offset is limited to -8 to +8 °F. 

PA  Limit for humidity low limit output value 

 - 

 

Limits 

the output value to 10 … 20% relative humidity in 

steps of 5%. This affects the output voltage on pin 7, only, 
and has no effect upon values appearing in the display. 

 = 10%, 

 = 15%, 

 = 20% (default), 

 = not used. 

 

Resetting to Factory Defaults 

Pressing the left, middle, and right button simultaneously 
while powering the wall module will reset the wall module 
settings to the factory defaults values. 
When the reset has been completed, the display will show 

.

 

 

Preferred DWM Configurations 

Depending upon how you configured (using ARENA/COACH) 
the SERVAL application software (as either HYD, CHC, or 
FCU), the DWM hardwired to it should be configured as 
indicated in Table 4. 

Table 4. Preferred DWM configurations in dependence 

upon configuration of SERVAL application software 

 

configuration of SERVAL application 

HYD 

CHC 

FCU 

p

refe

rr

e

DWM

 

c

on

fig

ura

tio

n

 

P1:3 

P1:3 

P1:3 

P2:2 

P2:2 

P2:2 

P3:1 

P3:1 

P3:2, P3:3, or P3:4 

P4:1 

P4:1 

P4:1 

P5:2 

P5:2 

P5:2 

P6:1 

P6:1 

P6:1 

P7:50 

P7:50 

P7:50 

P8:4 

P8:4 

P8:4 

 

Depending upon the given application software (either HE01, 
HT02, or AH03) which you have chosen to download into 
your PANTHER, the DWM hardwired to it should be 
configured as indicated in Table 5. 

Table 5. Preferred DWM configurations in dependence 

upon PANTHER application software 

 

PANTHER application 

HE01 

HT02 

AH03 

pre

fe

rr

e

DWM

 

c

on

fig

ura

tio

n

 

P1:3 

P1:3 

P1:3 

P2:2 

P2:2 

P2:2 

P3:1 

P3:1 

P3:1 or P3:2 

P4:1 

P4:1 

P4:1 

don't care 

don't care 

don't care 

P6:1 

P6:1 

P6:1 

P7:50 

P7:50 

P7:50 

P8:4 

P8:4 

P8:4 

 

How to Check the Software Version 

Simultaneously press the left (FAN OVERRIDE) and right 
(BYPASS) buttons for approx. 5 sec: An LCD display test will 
then be performed, after which the DWM's current software 
version (e.g.: 2.11) is shown in the LCD display. 

Содержание CENTRALINE CLCM1H112

Страница 1: ... making connections to or removing connections from the DWM s terminals Do not reconnect the power supply until you have com pleted the installation If the DWM is powered via terminal 8 and connected to earth ground then the cable must be shielded Observe precautions for handling electrostatic sensitive devices Cover Disassembly Assembly The DWM comes packed with a sub base that mounts separately ...

Страница 2: ...rmer When hardwired with the PANTHER the DWM can be powered either with 24 Vac dc from PANTHER terminal 2 via DWM terminal 8 use min 1 0 1 5 mm2 wire or with 18 27 Vac dc from PANTHER terminal 32 via DWM terminal 8 Wiring with SERVAL CLCM6T21N only LON 3 2 1 4 5 6 2324 7 8 GND 9 LED 10 FAN 11 DI2 12 DI1 SET SENS GND T7460 T7560 5 3 4 2 1 triac 0 5 A F2 5H 3A 10A 131415 18 17 16 III II I L N 230 V ...

Страница 3: ... type setting Scale type setting Fahrenheit relative Fahrenheit absolute Celsius relative default Celsius absolute P2 Room temperature display Do not display room temperature setpoint only Display room temperature default Display room temperature and humidity alternating every 5 seconds CLCM6H212 only P3 Bargraph use setting No Fan Auto OFF ON Auto OFF 2 Speeds Auto OFF 3 Speeds default P4 Control...

Страница 4: ...ault if set to F P9 9 Example units set to C A setting of means that the set point offset is limited to 3 to 3 C Example units set to F A setting of means that the set point offset is limited to 8 to 8 F PA Limit for humidity low limit output value Limits the output value to 10 20 relative humidity in steps of 5 This affects the output voltage on pin 7 only and has no effect upon values appearing ...

Страница 5: ...tromversorgung abschalten Die Stromversorgung erst nach Abschluß der Installation wieder einschalten Wenn die Stromversorgung des DWM über Klemme 8 erfolgt und ein Erdungsanschluß vorhanden ist muß das Kabel geschirmt sein Elektrostatisch gefährdete Baugruppen EGB müssen mit Vorsicht behandelt werden Abnehmen und Anbringen der Abdeckung Das DWM wird mit einer Sockeleinheit geliefert die zur einfac...

Страница 6: ...ie Stromversorgung des DWM zwei Möglichkeiten 24 VAC DC von der PANTHER Klemme 2 über DWM Klemme 8 Leiterquerschnitt min 1 0 bis 1 5 mm2 oder 18 bis 27 VAC DC von der PANTHER Klemme 32 über DWM Klemme 8 Verdrahtung mit SERVAL nur CLCM6T21N LON 3 2 1 4 5 6 2324 7 8 GND 9 LED 10 FAN 11 DI2 12 DI1 SET SENS GND T7460 T7560 5 3 4 2 1 triac 0 5 A F2 5H 3A 10A 131415 18 17 16 III II I L N 230 V fan 19202...

Страница 7: ...chritte 4 bis 6 wiederholen oder den Konfigurationsmodus mit BYPASS verlassen HINWEIS Nach ca 10 s ohne Bedienvorgang kehrt das DWM automatisch in den Normalmodus zurück P1 Sollwerteinstellung Skaleneinstellung Fahrenheit relativ Fahrenheit absolut Celsius relativ Standard Celsius absolut P2 Raumtemperaturanzeige Raumtemperatur nicht anzeigen nur Sollwert Raumtemperaturanzeige Standard Raumtempera...

Страница 8: ...esendet Nicht genutzt bedeutet Modus für ungenutzten Raum aktiv Mondsymbol dauernd ein oder Modus für ungenutzten Raum übersteuert Mondsymbol blinkt Genutzt bedeutet Modus für genutzten Raum aktiv Sonnensymbol dauernd ein oder Modus für genutzten Raum übersteuert Sonnensymbol blinkt P9 Sollwertgrenze Der Sollwert wird auf 0 bis 5 Celsius bei Einstellung auf C oder auf 0 bis 9 F bei Einstellung auf...

Страница 9: ...fectuer les connexions aux bornes du DWM ou de les retirer Ne rebranchez pas l alimentation électrique avant d avoir terminé l installation Si le DWM est alimenté via la borne 8 et connecté à la terre le câble doit être blindé Respectez les précautions relatives à la manipulation des composants sensibles à l électricité statique Désassemblage assemblage du capot Le DWM est livré avec une sous base...

Страница 10: ... aucun besoin d un transformateur dédié Lorsqu il est câblé à PANTHER le DWM peut être alimenté en 24 Vca cc depuis la borne 2 de PANTHER via la borne 8 du DWM Utilisez un câble de 1 0 1 5 mm2 min ou en 18 27 Vca cc depuis la borne 32 de PANTHER via la borne 8 du DWM Câblage avec SERVAL CLCM6T21N uniquement LON 3 2 1 4 5 6 2324 7 8 GND 9 LED 10 FAN 11 DI2 12 DI1 SET SENS GND T7460 T7560 5 3 4 2 1 ...

Страница 11: ...ée pendant environ 10 sec le DWM retourne automatiquement au mode normal P1 Paramètre du type de point de consigne paramètre du type d échelle Fahrenheit relatif Fahrenheit absolu Celsius relatif par défaut Celsius absolu P2 Affichage de la température de la pièce Ne pas afficher la température de la pièce point de consigne uniquement Affichage de la température de la pièce par défaut Affichage de...

Страница 12: ... entrée LED du module mural Unoccupied signifie Inoccupation effective lune affichée en continu ou Modification d inoccupation lune clignotante Occupied signifie Occupation effective soleil affiché en continu ou Modification d occupation soleil clignotant P9 Point de consigne limite Limite le point de consigne à 0 5 Celsius si défini en C ou à 0 9 F si défini en F Valeur par défaut si défini en C ...

Страница 13: ... voordat u draden aansluit op of loskoppelt van de aansluitingen op de DWM Sluit de voeding pas weer aan als u de installatie hebt voltooid Als de DWM stroom krijgt via aansluiting 8 en is ver bonden met de aarde moet de kabel zijn afgeschermd Tref de nodige voorzorgsmaatregelen voor het werken met apparaten die gevoelig zijn voor statische elektriciteit De kap loshalen en terugplaatsen De DWM wor...

Страница 14: ...ls de DWM permanent is aangesloten op de PANTHER kan de DWM worden gevoed met 24 Vac dc vanaf PANTHER aansluiting 2 via DWM aansluiting 8 gebruik een draad van min 1 0 1 5 mm2 of met 18 27 Vac dc vanaf PANTHER aansluiting 32 via DWM aansluiting 8 Bedrading met de SERVAL alleen CLCM6T21N LON 3 2 1 4 5 6 2324 7 8 GND 9 LED 10 FAN 11 DI2 12 DI1 SET SENS GND T7460 T7560 5 3 4 2 1 triac 0 5 A F2 5H 3A ...

Страница 15: ...te sluiten OPMERKING na ongeveer 10 seconden zonder verdere actie keert de DWM automatisch terug naar de normale modus P1 Instelling type richtwaarde instelling type schaal Fahrenheit relatief Fahrenheit absoluut Celsius relatief standaardinstelling Celsius absoluut P2 Weergave kamertemperatuur De ruimtetemperatuur niet weergeven alleen richtwaarde De ruimtetemperatuur weergeven standaard instelli...

Страница 16: ...zet maan wordt continu weergegeven of Onbezet door overschrijven maan knippert Bezet betekent Werkelijk bezet zon wordt continu weergegeven of Bezet door overschrijven zon knippert P9 Limiet richtwaarde Beperkt de richtwaarde tot 0 5 Celsius indien ingesteld op C of tot 0 9 F indien ingesteld op F Standaardinstelling indien ingesteld op C P9 5 Standaardinstelling indien ingesteld op F P9 9 Voorbee...

Отзывы: