SPECIAL INSTRUCTION FOR USE
•
The equipment shall only be used in an area of not more than pollution degree 2,
as defined in IEC/EN 60664-1.
•
The equipment shall be installed in an enclosure that provides a degree of
protection not less than IP 54 in accordance with IEC/EN 60079-15.
•
Transient protection shall be provided that is set at a level not exceeding 140 %
of the peak rated voltage value at the supply terminals to the equipment.
•
Install the HMI device according to the accompanying installation instructions.
•
Ground the HMI device according to the accompanying installation instructions.
•
Only qualified personnel may install the HMI device or repair it.
•
Ensure that the aeration holes are not covered.
•
Care shall be taken not to allow layers of dust to form on the graphic panel in a
way that might cause the accumulation of static charges. Keep the faceplate of
the HMI device clean: the equipment must be cleaned only with a soft cloth and
neutral soap product. Do not use solvents.
•
This device should not be used for purposes and methods other than indicated in
this document and in the documentation accompanying the product.