background image

C7961E,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

65-0267-09

10

Removing Detector from Sight Pipe 

(Refer to Fig. 8)

Loosen the three screws holding the mounting flange; rotate 

the detector slightly so the screws clear the slots in the back 

section of the flange; separate the flange; and pull off the back 

section (with the UV sensor).

NOTE: The detector is free when the collar is unscrewed; 

do not drop it.

Procedure for Zero Meter Reading

1.

Replace the plug-in amplifier. Then recheck the flame 

signal.

2.

Replace the coil and shutter assembly (see Installation 

Instructions 66-1169). Then recheck the flame signal.

3.

If you cannot yet obtain a meter reading, replace the 

detector.

IMPORTANT

At the completion of Troubleshooting, be sure to per-

form the Adjustments and Checkout procedures.

SERVICE

WARNING

Electrical shock hazard.

Can cause serious injury or death.

Open the master switch to disconnect power before 

removing or installing the detector or its cover. More 

than one disconnect can be involved.

Periodic Maintenance

1.

Clean the viewing window (or focusing lens) when nec-

essary. Remove the detector (see Troubleshooting sec-

tion) and use a clean cloth over the eraser end of a 

pencil. Do not remove the window (or lens) to clean it. If it 

is broken or damaged or it is coated with a substance 

that cannot be removed, replace it (see Fig. 13).

2.

Keep the flame detection system adjusted for the 

smoothest, most reliable operation as recommended by 

the burner manufacturer.

3.

Replace viewing window only when necessary to obtain 

proper operation.

Removing Detector Cover (All 

Models): 

1.

Open the Master Switch.

2.

Unscrew the four captive cover screws (Fig. 7) and care-

fully slide off the cover.

NOTE: These bolts are removable. Put them in a safe 

place to avoid losing them.

Fig. 12. Replacing quartz viewing 

window or focusing lens.

Replacing Quartz Viewing Window 

(or Focusing Lens) 

C7961E (Fig. 12)

IMPORTANT

Use quartz window or lens. Ordinary glass absorbs or 

filters out ultraviolet radiation.

1.

Open the master switch; remove the detector from the 

sight pipe and remove the detector cover. (See appropri-

ate sections.)

2.

Loosen the three screws holding the back section of the 

mounting flange to the faceplate. Carefully remove and 

keep together the three screws, the gray 

fiber-neoprene gasket, the red rubber washer, and the 

back section of the mounting flange.

NOTE: If the viewing window (with its rubber mounting 

gaskets) is stuck to the mounting flange, skip 

step 3.

IMPORTANT

Be very careful not to kink or otherwise damage the 

flexible shutter.

3.

Using the eraser end of a pencil, push out the viewing 

window (with its rubber mounting gaskets) from the 

inside of the faceplate.

4.

Insert one rubber mounting gasket into the window aper-

ture in the faceplate.

5.

Insert the new quartz viewing window (or focusing lens) 

into the window aperture with either side toward the 

flame.

6.

Insert two rubber mounting gaskets (only one gasket 

when replacing a focusing lens) into the aperture.

7.

Put the back section of the mounting flange, red rubber 

washer, and fiber-neoprene gasket in place on the face-

plate, and securely tighten the three mounting screws.

1

3

1

2

2

3

FACEPLATE

PENCIL

114372 (20 PSI) OR 122748 (50 PSI)

QUARTZ VIEWING WINDOW (OR 124204

QUARTZ FOCUSING LENS, 20 PSI)

114638 RED RUBBER 

WASHER (BETWEEN 

GASKET AND

FLANGE)

MOUNTING

SCREWS (3)

WINDOW

APERTURE

114465 RIBBER

MOUNTING

GASKETS (3)

BACK SECTION OF

MOUNTING FLANGE

VIEWING WINDOW CAN BE REPLACED WITH EITHER SIDE TOWARD 

THE FLAME.

ONLY ONE GASKET ON EACH SIDE OF THE FOCUSING LENS.

REMOVE THE THREE MOUNTING SCREWS AND MOVE THE COIL

AND SHUTTER ASSEMBLY OUT OF THE WAY TO PUSH OUT THE

VIEWING WINDOW.

M10130B

120739 FIBER-NEOPRENE GASKET

Содержание C7961E

Страница 1: ...Models available with Molex Woodhead 1R5006A20A120 Formerly Brad Harrison 41310 connector A swivel mount is available to facilitate flame sighting 40 F 40 C rated ultraviolet sensing tube Incorporates UV sensor tube checking feature used with R7851C Dynamic Self check Amplifiers High pressure 50 psi 345 kPa quartz viewing window magnifying lens and antivibration mount are available as accessories ...

Страница 2: ...ets NEMA 4 enclosure requirements indoor outdoor pro tection rain tight dust tight hose directed water protec tion C7961F Explosion proof two piece violet cast aluminum Pressure Rating of Quartz Viewing Window C7961E 20 psi 138 kPa see Replacement Parts C7961F 100 psi 690 kPa Pressure Rating of Quartz Focusing Lens 20 psi 138 kPa see Accessories Mounting C7961E Mounting flange with 3 4 in NPT or 1...

Страница 3: ...lues marked on the detector 4 Sight the detector so it does not respond to ignition spark 5 On multiburner installations each detector must respond only to the flame of the burner it is supervis ing Proper flame detector installation is the basis of a safe and reliable flame safeguard installation Refer also to the burner manufacturer instructions Carefully follow all instructions for the best pos...

Страница 4: ...ge of the detector field of view If the temperature of the hot refractory causes the flame relay in the flame safeguard control to pull in re aim the sight pipe so the detector views a cooler area of the refractory Ignition spark is an intense source of ultraviolet radiation When installing the detector make sure it does not respond to ignition spark Single Burner Requirements The detector must ha...

Страница 5: ...an installation locate each flame detector so that it has the best possible view of the first 30 percent closest to the burner nozzle the flame root it is supervising and the worst possible view of all other flames Fig 4 illustrates a critical detector application problem that requires flame discrimination Flame discrimination is accomplished for Detector A by repositioning it until the flame rela...

Страница 6: ...the sight pipe and into the chamber The air pressure must be greater than the chamber pressure Swivel Mount To facilitate proper flame sighting use 118367A Swivel Mount ordered separately The swivel mount requires a reducer of the proper size to mount it onto the sight pipe It also requires a one inch close nipple for mounting to a C7961 with a one inch connector For 118367A Swivel Mount mounting ...

Страница 7: ...ectrical ignition source in the event of a seal leakage 1 All wiring must comply with applicable local electrical codes ordinances and regulations Use NEC Class 1 wiring 2 Keep the flame signal leadwires as short as possible from the flame detector to the terminal strip or wiring subbase Capacitance increases with leadwire length reducing the signal strength The maximum permissible leadwire length...

Страница 8: ...e when using direct spark ignition Also measure the flame signal at low and high firing rates and while modulating in between as applicable With the detector in its final position all required flame signals must be steady or stable and as specified in Table 1 If you cannot obtain the proper signal refer to the Troubleshooting section Pilot Turndown Test When the detector is used to prove a pilot f...

Страница 9: ...satisfactorily completed TROUBLESHOOTING WARNING Electrical shock hazard Can cause serious injury or death Open the master switch to disconnect power before removing or installing the detector or its cover More than one disconnect may be involved Equipment Required A volt ohm meter with a minimum sensitivity of one megohm volt and a zero to five or ten Vdc scale is suggested When the Keyboard Disp...

Страница 10: ... place to avoid losing them Fig 12 Replacing quartz viewing window or focusing lens Replacing Quartz Viewing Window or Focusing Lens C7961E Fig 12 IMPORTANT Use quartz window or lens Ordinary glass absorbs or filters out ultraviolet radiation 1 Open the master switch remove the detector from the sight pipe and remove the detector cover See appropri ate sections 2 Loosen the three screws holding th...

Страница 11: ... to the faceplate and remove the flange Put the bolts in a safe place 3 Unscrew the retaining ring with its rubber O ring seal from the seal off flange 4 Tip the flange and let the viewing window fall into your hand 5 Insert either side of the new 122037 Quartz Viewing Window into the window aperture 6 Screw the retaining ring with O ring seal into the seal off flange and tighten securely 7 Clean ...

Страница 12: ...DETECTOR Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0267 09 JPG Rev 01 13 Printed in United States ...