C7355A ROOM IAQ MONITOR
31-00434—01
10
Measurements Adjustment via MODBUS:
1.
Temperature
2.
Humidity
3.
CO
2
4.
TVOC coefficient
5.
Particle coefficient
Use MODBUS PC software to operate according to the following table:
Table 4. Measurement Adjustment via MODBUS.
Temperature
value adjustment
RH value
adjustment
CO
2
value
adjustment
TVOC coefficient
adjustment
Particle total
environmental
coefficient
adjustment
Function code
3(Read)/16(Write)
3(Read)/16(Write)
3(Read)/16(Write)
3(Read)/16(Write)
3(Read)/16(Write)
Starting point
(Base 0)
4 6 14
12
1224
Data
length
2 2 1 2 2
Data type
32 Bit Float
Big-endian
32 Bit Float
Big-endian
INT16
32 Bit Float
Big-endian
32 Bit Float
Big-endian
Setting value
Standard reading -
C7355A local
temperature
measured value
Standard reading -
C7355A local
humidity measured
value
Standard reading -
C7355A local CO
2
measured value
Standard
reading/TVOC
local measured
value
Standard reading X
C7355A local
PM2.5 average
measured value
Setting range
-9.00–+9.00 °F(--
5.00–+5.00 °C)
-10.00–
+10.00%RH
-300–+300 ppm
0.001–65.000
times
0.001–10.000
times