C7110C1040 AND C7110C1080 WALL MODULES – PRODUCT DATA 

EN0B-0775GE51 R0619 

 

Zero Calibration ("CAL0") 

 

Fig. 6. Jumper set to CAL0 

When the configuration jumper is set to position "CAL0" (see 
Fig. 6), Zero Calibration will be carried out. This is done while 
testing the wall module with CO

2

-free air (e.g., a pure nitrogen 

atmosphere or air purged of CO

2

 using Milk of Lime). 

 

Fast Background Calibration ("CAL400") 

 

Fig. 7. Jumper set to CAL400 

When the configuration jumper is set to position "CAL400" 
(see Fig. 7), Fast Background Calibration will be carried out. 
The current level is then set to 400 ppm (= normal expected 
actual fresh air level) in a single step. 

NOTE:

  Before starting Fast Background Calibration, 

ventilate the room with fresh outdoor air. 

 

Behavior of Service LED during Quick Calibration 

During Zero Calibration or Fast Background Calibration, the 
Service LED will indicate that the given calibration process is 
in progress by flashing once per second for 90 sec (sensor 
warm-up) and then twice per second for 10 sec (sensor cali-
bration). Once the calibration process has been completed, 
however, the Service LED will then stop flashing and return to 
normal operational behavior. 

NOTE:

  One possible reason for a failed calibration is if CO

2

 

levels fluctuate too wildly during calibration; in this 
event, you should remove and then restore power to 
the device and perform the calibration again. 

 

ABC 

During 

ABC

 (

A

utomatic 

B

aseline 

C

orrection) – which is 

ON

 

by default – any initial (due, e.g., to rough handling during 
shipping) or subsequent long-term drift will be gradually 
corrected (i.e., by a max. of 50 ppm per week). This is done 
by comparing the lowest measured value (over the last 7.5 
days) with the expected fresh air level (400 ppm). 

When the configuration jumper is set to the factory default 
position of "2000" ppm or to "3000" ppm, the wall module will 
operate normally and perform ABC. 

 

Fig. 8. Default setting (ABC 

ON

 = adjacent LED flashes 

GREEN for first 10 s after power restoration) 

NOTE:

  In buildings featuring plastered walls / ceilings or 

other constructional materials containing quicklime – 
especially when fresh – unusually low levels of CO

2

 

(i.e., far below 400 ppm) may prevail, especially in 
new, poorly ventilated areas. To prevent sensor mal-
functions in such situations, it is recommended that 
ABC be switched 

OFF

 

Switching ABC OFF and ON 

IMPORTANT 

Do not change the position of the configuration 
jumper before first removing power. 

ABC

OFF

ABC

ON

 

Fig. 9. Switching ABC 

OFF

 (left) or 

ON

 (right) 

ABC can be switched 

OFF

 by repositioning the jumper as 

indicated in the left-hand side of Fig. 9. The adjacent LED will 
then flash YELLOW briefly and then remain lit YELLOW. This 
indicates that ABC has finished switching 

OFF

NOTE:

  If ABC is switched 

OFF

, we recommend that you 

then calibrate the sensor using Zero Calibration or 
Background Calibration at least once per year to 
ensure that the CO

2

 level readings remain within 

specifications. 

ABC can be switched 

ON

 by repositioning the jumper as 

indicated in the right-hand side of Fig. 9. The adjacent LED 
will then flash GREEN for the first 10 sec and then remain lit 
GREEN. This indicates that ABC has finished switching 

ON

NOTE:

  Only after ABC has finished switching 

ON

 or 

OFF

 

should you again remove power, return the jumper to 
the desired range setting (i.e., "2000" or "3000"), and 
finally restore power. The given ABC setting (

ON

 or 

OFF

) will then remain in effect even if power is 

subsequently removed or restored. 

 

Содержание C7110C1040

Страница 1: ...esired air quality while during low occupancy periods the unnecessary conditioning of air can be avoided or reduced FEATURES Fully compatible with the Honeywell controllers CO2 sensor employing state of the art Non Dispersion Infrared NDIR technology Selectable CO2 measurement range of 400 2000 3000 ppm Self calibrating automatic drift correction ABC algorithm based on long term evaluation Interna...

Страница 2: ...gree of protection provided by enclosures IP20 CO2 Measurement Range 400 2000 3000 ppm Output terminals 1 2 0 10 VDC for max 2 mA Accuracy factory calibration 50 ppm or 5 of measurement range Pressure dependence 1 6 per kPa deviation from normal pressure of 100 kPa Response time 90 penetration within 2 min MOUNTING WARNING Risk of electric shock or equipment damage Do not touch any live parts Disc...

Страница 3: ...irst removing power In a normal environment the unit is maintenance free Accurate measurement is guaranteed by the built in ABC self calibration feature see below Setting Range to 2000 ppm or 3000 ppm 2000 ppm When the configuration jumper is set to the factory default position of 2000 ppm see Fig 8 or to any other position except 3000 ppm see Fig 5 the CO2 measuring range is 400 2000 ppm 3000 ppm...

Страница 4: ...aring the lowest measured value over the last 7 5 days with the expected fresh air level 400 ppm When the configuration jumper is set to the factory default position of 2000 ppm or to 3000 ppm the wall module will operate normally and perform ABC Fig 8 Default setting ABC ON adjacent LED flashes GREEN for first 10 s after power restoration NOTE In buildings featuring plastered walls ceilings or ot...

Страница 5: ... Threshold Level ppm SERVICE LED MAX OFF SERVICE LED IS LIT SERVICE LED FLASHES MIN SERVICE LED IS DARK 50 1000 ppm ACTUAL CO2 CONCENTRATION EXAMPLE Fig 11 Configuration potentiometer e g set to 50 1000 ppm The CO2 output can operate in two modes To select the Sensor Output mode analog set the configuration potentiometer to OFF default setting see Fig 11 See also Fig 12 To select the Relay Output ...

Страница 6: ...o 400 ppm given measured concen trations below 400 ppm the output signal will gradually rise to 2 V The Relay Output Mode In the Relay Output mode digital the Service LED see Fig 11 will either flash or be lit continuously thus indicating the actual Threshold Level setting 10 V 500 ppm 1000 ppm 0 V HYSTERESIS 100 ppm CO2 LEVEL 2000 3000 ppm MIN MAX SERVICE LED IS OUTPUT OF TERMINAL 2 Fig 13 Relay ...

Страница 7: ... Dark S O Calibration successful Lit continuously S O Calibration failed Dark S O CO2 1000 ppm Dark S O CO2 1000 ppm Flashing R O CO2 threshold Lit continuously R O CO2 threshold S O R O ABC ON S O R O ABC OFF OCC BYPASS BUTTON C7110C1080 ONLY AND CALIBRATION LED The functionality of the occupancy bypass button C7110C1080 only and the corresponding behavior of the calibration LED are dependent upo...

Страница 8: ... 0 7031 637 01 Fax 49 0 7031 637 740 http ecc emea honeywell com EN0B 0775GE51 R0619 Subject to change without notice ACCESSORIES order no description T7460LONJACK Module for access to external buses 5 pc set T7460 LONJACK The T7460 LONJACK ordered separately is a small board with a 3 5 mm jack When mounted to the Printed Circuit Board see Fig 14 it provides easy access to external buses Order qua...

Отзывы: