background image

60-0348—2

2

C554A CADMIUM SULFIDE FLAME DETECTOR

AIR TUBE

IGNITION
ELECTRODE

IGNITION
TRANSFORMER

CAD CELL

NOZZLE

M7857

Fig. 2. Cad cell location.

The orifice (available on some models) reduces the
amount of light available to the photocell minimizing the
chance that the cell will respond to the glow from the hot
refractory. See Fig. 3 for a cutaway view of the orifice.

ORIFICE

WALL

CADMIUM SULFIDE CELL

M7863

Fig. 3. Cutaway view of orifice.

Mounting

Mount the C554A at the rear of the burner. The mounting
bracket can be bent to fit, if necessary.

Wiring

Disconnect power supply before beginning wiring to
prevent electrical shock or equipment damage.

All wiring must comply with local electrical codes and
ordinances. See Fig. 4 for a typical C554A hookup to the
oil burner primary control.

T

T

F

F

THERMOSTAT
(24V)

C554A
CADMIUM SULFIDE
FLAME DETECTOR

OIL BURNER RELAY

M7858

Fig. 4. Typical hookup for C554A to oil burner

primary control.

CHECKOUT

To check cad cell operation, use the following procedure:

Disconnect cad cell leadwires; then start the
burner. Shortly after the burner starts, place a
temporary jumper between terminals F-F. Connect
an ohmmeter across the cad cell leadwires;
resistance should be less than 1600 ohms.

Stop burner and remove temporary jumper.

With the burner off, check the dark cell resistance
across the cad cell leadwires. Resistance should
be greater than 20,000 ohms.

NOTE:

If cell resistances are different than
specified, recheck the wiring and the
location of the cell. If necessary, replace
plug-in portion of cell, Honeywell part no.
130367 Replacement Cad Cell.

Reconnect cad cell leadwires. Check the
Protectorelay

®

 (burner sequencing relay) control

according to the instructions packed with the
control.

SERVICE AND REPLACEMENT

Under normal operating conditions, the C554A does not
require cleaning. If a badly adjusted burner causes
heavy accumulation of dirt and soot on the cell surface,
carefully wipe the cell surface to restore full view of the
oil flame.

If the C554A is damaged, replace the plug-in portion of
the cell.  Order Honeywell part no. 130367 Replacement
Cad Cell.

60-0348—2  J.S.  Rev. 2-96

Automation and Control Solutions

Honeywell International Inc.

Honeywell Limited—Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Scarborough, Ontario   M1V 4Z9

Отзывы: