BACNET® FIXED FUNCTION THERMOSTAT
31-00099—01
24
LIST OF MAIN DEVICE OBJECTS
Not accessed via the touchscreen. These are set up with default values.
Fan Control
Zone Control
Device Object Label
Device Object Label
AV-39
Fan Speed Demand (Analog) %
AV-103
Outside Air Temp
AV-5
Fan Stop Delay (Sec)
AV-104
Space Temp from (BMS)
AV-82
Fan Runtime
AV-12
Supply Air Temp
AV-85
Medium Speed Fan Start SP
AV-123
Schedule Module
AV-86
Filter Runtime
AV-36
Space Temp used for PI Calc
AV-89
High Speed Fan Start SP
BV-124
System Auto Selected
BV-16 Filter
Alarm
BV-133
Enable Internal Schedule
BV-5
Fan Status
BV-32
Enable Remote Sensor (AI-2)
BV-59
Fan Auto - On
BV-4
In Standby Mode
BV-72
Fan 3 speed - Low
BV-40
Occupied Command
BV-73
Fan 3 speed - Medium
BV-47
Enable Remote Sensor (AI-0)
BV-74
Fan 3 speed - High
BV-56
Enable BMS Scheduling
BV-80
Enable Fan Speed Control
Heating and Cooling Signals
Compressor Control
AV-0 Heating
Signal
AV-21
Compressor 1 Starts
AV-1
Cooling Signal
AV-22
Compressor 2 Starts
AV-105
Sensed Humidity
AV-40
AC HP Mode Control
AV-13
Heating Valve Demand
AV-68
AC HP Compr Start Demand %
AV-18
AC-HP Compr. Min Off (mins)
AV-69
AC HP Compr Stop Demand %
AV-27
AC-HP Compr. Min On (mins)
AV-81
Runtime HP Comressor (App 10)
AV-41
Heat Signal Proportional Gain
AV-87
Runtime Cooling Stage 1
AV-42
Heating Signal Integral Gain
AV-88
Runtime Cooling Stage 2
AV-43
Cool Signal Proportional Gain
BV-21
Reverse Valve Action, 1 = cool
AV-44
Cooling Signal Integral Gain
BV-22
1 = Cooling Locked Out
AV-57
Calc. Compr. Off time (sec)
BV-27
1 = Heating Locked Out
AV-58
Calc. Compr. Cycle time (sec)
BV-6
HP Fun Request
AV-59
Calc. Compr. Mins on (sec)
BV-7
Fan Request (AC Cooling)
AV-8
Cooling Valve Demand
BV-31
WS HP Water Loop OK
AV-83
Runtime Heat Stage 1
Economizer Control
AV-84
Runtime Heat Stage 2
AV-10
Economizer Position
BV-1
1 = In Heating Mode
AV-63
Econ. Damper Stroke Time
BV-12
1 = Dehum Mode is On
AV-60
Supply Air Low temp Limit
BV-52
RH Fan Circ Cycle time (mins)
AV-66
Econ. Min. Position
BV-27
Heating Lockout
AV-11
Float Point Econ. Position
BV-28
Cooling Lockout
BV-20
Supply Air Low Limit Alarm
BV-24
Supply Temperature Valid
Occupancy/Standby
Residential Mode
BV-4
In Standby Mode
AV-129
Sets the number of occupancy periods,
2 = wake and sleep,
4 = wake, leave, return and sleep.
BV-63
Door Open
BV-62
No Motion Since Door Closed
NOTE:
This is a selection of some of the device objects.
For the full list refer to the BACnet FF Thermostat
System Engineering Guide, 31-00098.
BV-149
Wireless Installed
BV-67
Occupied
BV-60
Window/Door Open (Wireless)
BV-61
No Motion Since Dr Clsd (Wireless)
AV-20
Standby Delay (Sec)
BV-81
Hotel Mode