9.2.2.1 Measuring
resistance values
►
Disconnect the corresponding temperature sensor from the
controller.
►
Measure the resistance value. The typical resistance values,
depending on the temperature, are listed in the following table.
Please note that small deviations are permissible.
Temperature sensor resistance values
Temperature [°C]
–30
–20
–10
0
10
20
Resistance [
Ω
]
882 922 961 1000 1039
1078
Temperature [°C]
30
40
50
60
70
80
Resistance [
Ω
]
1117 1155 1194 1232 1271 1309
Temperature [°C]
90
100
110
120
130
140
Resistance [
Ω
]
1347 1385 1423 1461 1498 1536
Temperature [°C]
150
160
170
180
Resistance [
Ω
]
1573 1611 1648 1685
10 Dismantling
and
disposal
DANGER
Risk of death by electrocution!
►
Remove the controller from the power supply before
dismantling the controller.
►
To dismantle the controller, follow the assembly instructions in
the reverse order.
►
Dispose of the controller in accordance with the regional
regulations.