INSTALLATION INSTRUCTIONS

60-0915-5

L4006A,B,E,H 

Aquastat® Controllers

APPLICATION

These boiler-mounted, immersion type controllers 
operate in response to temperature changes in hydronic 
heating systems.

L4006A breaks the circuit on a temperature rise to the 
control setting. It is used for high limit or low limit control. 
When used as a controller or as a low limit, a separate 
high limit must be used.

L4006B makes the circuit on a temperature rise. It is 
used as a circulator controller, delaying circulator 
operation when boiler water temperature is below the 
control setting.

L4006E,H includes a trip-free manual reset switch. 
These models are designed to break the control circuit 
whenever the temperature of the controlled medium 
reaches the high limit setting. A reset button on the front 
of the case must be pressed to re-establish the control 
circuit. L4006H also includes bracket and clamp for 
surface mounting on pipe or tank.

A plastic bag of heat-conductive compound is included 
with the L4006A,B,E Aquastat® Controllers for use when 
the sensing bulb is inserted into a well designed for a 
large bulb than the one used on the L4006A,B,E. A 
124904 Well Adapter, for use on old wells that do not fit 
the L4006A,B,E immersion well clamp, can be ordered; 
see form 68-0040, Wells and Fittings for Temperature 
Controllers. A setting stop is included to prevent setting 
above a desired temperature on limit.

If a well adapter or other accessories are needed, refer to 
form 68-0040, Wells and Fittings for Temperature 
Controllers, for part numbers and ordering information.

INSTALLATION

When Installing This Product…

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Electrical Shock Hazard.
Can cause serious injury, death or equipment 
damage.

Disconnect the power supply before beginning 
installation to prevent electrical shock or 
equipment damage.

Installing Immersion Well Models 

(L4006A,B,E)

IMPORTANT

Obtain the best thermal response with a well 
that snugly fits the sensing bulb. The bulb 
should be inserted until it rests against the 
bottom of the well. Use a well of correct length 
and bend the tubing, if necessary, to provide 
enough force to hold the bulb against the 
bottom of the well. Do not make a sharp bend in 
the tubing. A sharp bend can produce a break in 
the tubing and cause a loss of fill. This condition 
will cause the high and low limit controls to be 
made continuously.

If the well is not a snug fit on the bulb, use the 
heat-conductive compound as follows. Fold the 
plastic bag of compound lengthwise and twist 
gently. Snip the end of the bag and insert into 
the well. Slowly pull out the bag while squeezing 
firmly to distribute the compound evenly in the 
well. Insert the bulb into the well. Bend the 
tubing, if necessary, to provide force to hold the 
bulb against the bottom of the well and to hold 
the out end of the bulb in firm contact with the 
side of the well. Wipe off any excess compound.

NOTE: Some models have an adjustable capillary 

tubing length to 3 inches (76 mm). In these 
models, pull out extra tubing from inside the 
case, if needed. 

Follow the boiler manufacturer instructions, if available; 
otherwise, proceed as follows.

60-0915-5.fm  Page 1  Wednesday, June 20, 2007  9:16 AM

Содержание Aquastat L4006A

Страница 1: ...uld damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING Electrical Shock Hazard Can cause serious injury death or e...

Страница 2: ... Fig 2 Bulb in immersion well and use of adapter If the Old Well Is Unsuitable 1 Drain the system and remove the well 2 Select a new well from form 68 0040 order well separately 3 Install the new well refill the system and check for leaks 4 Loosen but do not remove the two adapter clamp screws Fig 1 5 Insert the sensing bulb into the well until it bottoms as show in Fig 2 Add heat conductive compo...

Страница 3: ...th local codes and ordinances regarding wire size insulation enclosure etc See Fig 4 and 5 for typical diagrams of Aquastat Controllers used in heating systems Use these Aquastat Controllers with copper wire only Fig 4 Typical hookup for gas fired system with domestic hot water Fig 5 Hookup for oil fired summer winter hydronic system with domestic hot water This is typical where control for domest...

Страница 4: ...ust the control point to correspond with the boiler manufacturer recommendations To adjust insert a screwdriver in the slotted screw type head located beneath the window in the cover Turn the scale to the desired control point Manual Reset When the device includes manual reset L4006E and H be sure to press the red reset button on the front of the case to make sure that the controller is not locked...

Страница 5: ...ection 4 First Aid Measures Eye Contact Flush eyes with water for 15 minutes Remove any contact lenses and continue to flush Obtain medical attention if irritation develops and persists Skin Contact Remove excess with cloth or paper Wash thoroughly with mild soap and water Obtain medical attention if irritation develops and persists Ingestion Contact physician or local poison control center immedi...

Страница 6: ...tibilities Strong oxidizing agents and halogens Hazardous Decomposition Products Carbon dioxide carbon monoxide Section 11 Toxicology Information No data available Section 12 Ecological Information Chemical Fate Information Hydrocarbon components will biodegrade in soil relatively persistent in water Section 13 Disposal Consideration Dispose of as solid waste in accordance with local state and fed...

Страница 7: ...7 60 0915 5 60 0915 5 fm Page 7 Wednesday June 20 2007 9 16 AM ...

Страница 8: ...l Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 60 0915 5 C H Rev 08 05 60 0915 5 fm Page 8 Wednesday June 20 2007 9 16 AM ...

Отзывы: