AQ250 SERIES HYDRONIC CONTROL PANELS
69-1982
12
Table 3. AQ1554P2 Zoning Module (Pump Zoning Module) DIP switch arrangement
* The AQ1500B0 Boiler Control Module DIP switch #5 must be set to “GROUP” position and DIP switch #6 must be set to “MAIN” position.
Table 4. AQ1574V4 Zoning Module (Valve Zoning Module) DIP switch arrangement
* The AQ1500B0 Boiler Control Module DIP switch #5 must be set to “GROUP” position and DIP switch #6 must be set to “MAIN” position.
8 Test and Check Out the Installation
Startup
Apply power to the AQ250 Control Panel ONLY AFTER all of
the AQ2000 SERIES components (Control Panel,
thermostats, sensors, Zoning Modules / Panels) have been
wired to the other components in the hydronic heating system
(boiler, zone valves or pumps, DHW AQUASTAT, etc.).
Once powered, the AQ250 Control Panel will begin its start-up
routine, establishing communication with all other AQ2000
SERIES components on the AQUATROL network.
Test
A) AUTO TEST—AQ1500B0 CONTROL MODULE
Auto Test operation enables the installer to test the system
installation by sequentially activating all of the Control
Module's outputs for 15 seconds each. Each step of the Auto
Test routine may be paused or skipped by pressing the Test
button.
STATUS LEDS
Every status light (ZR, BOILER pump, AUXiliary pump, DHW
pump) will be turned on for 15 seconds when its
corresponding output is energized during Auto Test.
DIP #
Switch Description
Label and Factory Settings
1
Zone Address
For each group of 4 zones, there can be only one DIP switch in the right hand position. The
first Zoning Module connected to each Control Module must have the first of these DIP
switches (“1-4”) set to the right hand position with the other 3 switches set to the left. The
second Zoning Module’s “5-8” switch must be in the right hand position; the third Zoning
Module’s “9-12” switch must be in the right hand position, etc.
2
3
4
5
Zoning with valves or pumps
6
Are zone valves normally closed (N.C.) or normally open (N.O.)
7
If set to “YES”, AUX Pump contacts (on Control Module) are switched when any of
the zones on this Zoning Module are active*
8
Not used at this time
DIP #
Switch Description
Label and Factory Settings
1
Zone Address
For each group of 4 zones, there can be only one DIP switch in the right hand position. The
first Zoning Module connected to each Control Module must have the first of these DIP
switches (“1-4”) set to the right hand position with the other 3 switches set to the left. The
second Zoning Module’s “5-8” switch must be in the right hand position; the third Zoning
Module’s “9-12” switch must be in the right hand position, etc.
2
3
4
5
Not used at this time
6
Are zone valves normally closed (N.C.) or normally open (N.O.)
7
If set to “YES”, AUX Pump contacts (on Control Module) are switched when any of
the zones on this Zoning Module are active*
8
Not used at this time
M23720
Diagnostic
Test
Diagnostic
Test
M23714
M23716
Diagnostic
Test
Diagnostic
Test
M23714