Internet Communication Module 7845i-GSM Installation and Setup Guide
3-12
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY OPTIONS
DESCRIPTION
22
Notify Panel Of_
(Neither Fault)_
✔
✔
[Neither
fault]
[Both IP
and GSM
Faults]
If "Both IP and GSM Fault" is selected, the device
will only notify the control panel if both
communication paths fail, but will always send
notification of either failure to the central station.
NOTE:
The fault relay output (if programmed) will
be triggered only if "Both IP and GSM Faults" is
selected.
Press the [space] key to scroll through choices.
23
Flt Rel ON Y/N
(N)_
✔
✔
[Y], [N]
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module radio fault.
Use if fail-safe mode is desired.
See
Wiring for
Module Radio Faults
in Section 2.
UL NOTE:
Must be set to "Y".
24
Pwr Loss Rpt Y/N
(Y)_
✔
✔
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after power
is restored.
25
Low Bat Rpt Y/N
(Y)_
✔
✔
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery condition
clears.
NOTE:
Must be set to "N" for use with LynxR-I
controls.
26
Tamper Rpt Y/N
(Y)_
✔
✔
[Y], [N]
Sends a tamper report when the module detects a
tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
27
Lynx Panic Y/N
(N)_
✔
[Y], [N]
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the
module's zone terminal.
Reports a Panic alarm on zone 3 when the module
detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
Important Information Regarding Zone Input Options
If desired,
4204 mode
supports two optional hardwire zone input triggers by making connections to the module’s zone
6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE:
These triggers are not available when using 2-4204 mode.
Zone Trigger Mode
provides six hardwire zone input triggers by making connections to the module’s zone terminals
and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a
reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2):
The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell
output to the 7845i-GSM zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The
7845i-GSM reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when it
detects a steady signal.
Telco Zone and Open/Close Zone:
Dedicated zones can be assigned as the telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a telco line fault or open/close report respectively, in
ADEMCO High-Speed format. Connect the appropriate trigger from the control to the selected zone input for each of
these
options.
Input Trigger Types:
Triggering of each zone input can be programmed to cause an alarm under one of the following
conditions:
•
(V+), where a positive voltage causes an alarm for normally low connections