Technical description
Part no.:
Battery:
Battery Protection:
Overcharge protection / deep discharge protection
o
5 to 40 C
Up to 95%
23 hours
Produced in accordance with:
Ambient Temperature Range:
Maximum Power Consumption:
Operation Voltage:
Relative Humidity:
Charging Time:
Technical lifetime (light source):
> 100000 hours
AgoraLED NM LED 230V 2X6W 138
11.4W / 11.8VA
220-240V AC, 50-60 Hz
138172
138173
12V / 7Ah Pb
IP42
IP65
1h / 3h / 8h manually selected (default 1h)
Degress of cover protection:
Emergency Mode Duration:
EN 60598-1, EN 60598-2-22, EN 55015
EN 61547, EN 61000-3-2, EN 61000-3-3
Lumen output, emergency:
1h: 3200lm / 3h: 1600lm / 8h: 800lm
Weight:
Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function
4150 gr
42000 gr
4 years
GB
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
http://www.hls-nordic.com
Indicator LEDs
LED Status explanation
Description
GREEN
RED
Battery charged
Battery Charging
Emergency
Battery not connected
Low Battery Capacity
Lamp fault
Off
On
Blink
Any
Fast Blink
The AgoraLED is a self-contained non-maintained emergency luminaire with selftest function.
Fault Reset:
Fault reset is performed by pressing the TEST button for more than 5 seconds.
Manual Test (Test Button):
Manual testing is only possible when both mains power supply and battery are connected. Test the lamps by pressing
the TEST button briefly (<1 sec.).
Selftest Functions:
Lamp Test - This is performed when luminaire is in emergency mode.
Emergency Circuit Test (every 15 days) - Luminaire is switched to battery mode; lamps are lit for 3 seconds.
- Luminaire is switched to battery mode; lamps are lit for the stated duration.
Check of lamp and battery conditions
General:
During emergency mode the TEST button can be pressed repeatedly to select the light output to 100%, 50%, 33% or
off (e.g. in order to conserve the battery energy is power failure happens during daytime).
This function is not available if the luminaire is set to 8h autonomy duration.
This selection is cancelled out when the mains power supply is restored.
A 2A mains fuse (non-replaceable) is mounted on the PCB. A 8AF glass fuse on the PCB is for protection against
excessive lamp current and reverse battery connections.
Important notice when installing luminaires within the same area!!!
To avoid that luminaires perform their battery test at the same day, connect the battery packs with more than 1.5
minutes in between.
Note:
Disconnect the battery if luminaire is not supplied from mains for a longer period of time (>2 months).
Note:
The light source is non replaceable.
Note:
If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person in order to
avoid hazard.
At the end of their useful life the packaging,
product and batteries should be disposed of via a
suitable recycling centre.
Do not dispose of with your normal household
waste.
Do not burn.