Technical description

Part no.:

Battery:

Battery Protection:

Overcharge protection / deep discharge protection

o

5 to 40  C

Up to 95%

23 hours

Produced in accordance with:

Ambient Temperature Range:

Maximum Power Consumption:

Operation Voltage:

Relative Humidity:

Charging Time:

Technical lifetime (light source):

> 100000 hours

AgoraLED NM LED 230V 2X6W 138

11.4W / 11.8VA

220-240V AC, 50-60 Hz

138172

138173

12V / 7Ah Pb

IP42

IP65

1h / 3h / 8h manually selected (default 1h)

Degress of cover protection:

Emergency Mode Duration:

EN 60598-1, EN 60598-2-22, EN 55015 
EN 61547, EN 61000-3-2, EN 61000-3-3

Lumen output, emergency:

1h: 3200lm / 3h: 1600lm / 8h: 800lm

Weight:

Expected Battery Lifetime:

Controlgear classification in accordance with IEC 62034: with automatic test function

4150 gr

42000 gr

4 years

GB

Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway 

 http://www.hls-nordic.com 

Indicator LEDs

LED Status explanation

Description

GREEN

RED

Battery charged

Battery Charging

Emergency

Battery not connected

Low Battery Capacity

Lamp fault

Off

On

Blink

Any

Fast Blink

The AgoraLED is a self-contained non-maintained emergency luminaire with selftest function.

Fault Reset:

Fault reset is performed by pressing the TEST button for more than 5 seconds.

Manual Test (Test Button):

Manual testing is only possible when both mains power supply and battery are connected. Test the lamps by pressing 
the TEST button briefly (<1 sec.).

Selftest Functions:

Lamp Test                                                                 - This is performed when luminaire is in emergency mode.
Emergency Circuit Test (every 15 days)        - Luminaire is switched to battery mode; lamps are lit for 3 seconds.
                                                                                      - Luminaire is switched to battery mode; lamps are lit for the stated duration.
                                                                                         Check of lamp and battery conditions

General:

During emergency mode the TEST button can be pressed repeatedly to select the light output to 100%, 50%, 33% or 
off (e.g. in order to conserve the battery energy is power failure happens during daytime).
This function is not available if the luminaire is set to 8h autonomy duration.
This selection is cancelled out when the mains power supply is restored.
A 2A mains fuse (non-replaceable) is mounted on the PCB. A 8AF glass fuse on the PCB is for protection against 
excessive lamp current and reverse battery connections.

Important notice when installing luminaires within the same area!!!

To avoid that luminaires perform their battery test at the same day, connect the battery packs with more than 1.5 
minutes in between.

Note:

 Disconnect the battery if luminaire is not supplied from mains for a longer period of time (>2 months).

Note:

 The light source is non replaceable.

Note:

 If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person in order to 

avoid hazard.

At  the  end  of  their  useful  life  the  packaging, 
product and batteries should be disposed of via a 
suitable recycling centre. 
Do  not  dispose  of  with  your  normal  household 
waste.  
Do not burn.