AgoraLED IP42
AgoraLED IP65
Test
Test
LAMP FAULT
BATT FAULT
POWER
CHARGE
EMERGENCY
LIGHTING
AGORALED
307mm
100mm
333mm
210mm
234mm
Dimensional Drawings:
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
http://www.hls-nordic.com
Installation:
(Wall Mounting Only)
2
Cover
retaining
screws
Mounting Holes
Test
Test
LAMP FAULT
BATT FAULT
POWER
CHARGE
EMERGENCY
LIGHTING
AGORALED
3
4
5
Step 1:
Hold the device on the wall and mark the holes with a marker. The distance between the mounting holes is
234mm. Drill the holes. Use the supplied mounting accessories to mount the device. Remove the four cover
retaining screws.
Step 2:
Install the cable grommet and pass the round cable. Connect the cables to the respective positions in the
terminal block L for phase and N for neutral.
Always use in any case round mains cable, with external diameter
2
of 6-9mm (H05RN-F type 2x1mm or any other type, at least equal to it’s mechanical and electrical
properties). ATTENTION!! The cable must not be deformed In any way.
Step 3:
Install the battery cable connectors to the batteries taking care of the polarity, black cable (-) and red cable (+).
Step 4:
In case you use a module connect it on the PCB.
Step 5:
The user can select one of the 3 available minimum durations: 1 hour, 3 hours and 8 hours. The selection must
be done while the luminaire is disconnected from AC and battery supplies. The selection is achieved through
Switches 2 & 3 of DS1. Switch 1 and 4 are not used. Two additional labels are included in the package, one for 3
hours duration (180) and one for 8 hours duration (480). Depending on the selected duration, the installer must
replace the default 1 hour (60) label with one that has the required duration.
Please take notice of the
orientation of the label.
Step 6:
There is a terminal block for connection to the (optional) communication modules (elBus, DALI and pot. free), in
the lower left corner of the PCB. The terminals are marked C1 and C2.
Step 7
: Make a hole in the right side of the luminaire, install the rubber gasket and make a hole in the center by using a
small screwdriver. Pass the round cables through the gasket and connect it on the terminals.
Step 8:
Close the front cover and fasten it with the removed screws. (Tightening torque 1 N*m)
6
C1C2
AgoraLED IP65
N
L
2
6
7
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
1h
(default position)
3h
8h
Dip Switch Positions
1