Installation Instructions
4-4
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*44
Part. 1 Secondary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press
∗
44
∗
.
*45
Part. 2 Primary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press
∗
45
∗
.
*46
Part. 2 Secondary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press
∗
46
∗
.
*47
Phone System Select
If Central Station Receiver
is
not
on satellite
link: 0 = Decadic Pulse Dial;
1 = Multifrequency Tone Dial
If Central Station Receiver
is
on satellite link:
2 = Decadic Pulse Dial;
3 = Multifrequency Tone Dial
Select the type of telephone service.
*48
Report Format
(Primary/Secondary)
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
5 = CID* using 10-digit account number
6 = 4+2 ADEMCO EXPRESS
7 = CID* using 4-digit account number
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
10 = ROBOFON 8 (6-digit account number)
11 = ROBOFON Contact ID
Select report format for primary and secondary phone numbers.
* ADEMCO Contact ID format
NOTE:
To enable the audio “beeps” format (Follow-Me feature), refer
to the System Features section later in this manual, and the User
Guide.
*49
Split/Dual Reporting
0 = disable (standard/backup report only).
1 - 5 (see table to right)
To Primary No.
To Secondary No.
1 = alarms, restore, cancel
others
2 = all except open/close, test
open/close, test
3 = alarms, restore, cancel
all
4 = all except open/close, test
all
5 = all
all
*50
Burglary Dialer Delay
0 = no dial delay (
UL: must be “0”)
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
Provides delay of “BURGLARY ALARM” report to the central station,
which allows time for the subscriber to avoid a false alarm
transmission. This delay does not apply to zone type 24 alarms (silent
burglary) or to 24-hour zone types 6, 7, and 8 (silent panic, audible
alarm, auxiliary alarm), which are always sent as soon as they occur.
*51
Part. 3 Primary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48.
*52
Part. 3 Secondary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48.
*53
SESCOA/Radionics Select
0 = Radionics (0-9, B-F reporting)
1 = SESCOA (0-9 only reporting)
Select SESCOA or Radionics format.
Select 0 for all other formats.
*54
Dynamic Signaling Delay
0 = disabled (both signals sent)
1–15 = entry times a 15-second delay.
e.g., 1 = 15 seconds, 2 = 30 seconds, etc.
Intended for use with ECP Contact ID Output reporting via ACM.
This field lets you select the time the panel should wait for
acknowledgment from the first reporting destination (see
∗
55) before
it attempts to send a message to the second destination. Delays can
be selected from 0 to 225 seconds, in 15-second increments. This delay
is per message. If ”0” is entered in this field, the control panel will
send redundant reports to both Primary Dialer and ECP output.
Содержание Ademco Vista-48LA
Страница 1: ...ADEMCO VISTA 48LA Security System Installation and Set Up Guide K0749 6EN 5 05 Rev A ...
Страница 2: ...ii ...
Страница 28: ...Installation Instructions 3 8 ...
Страница 42: ...Installation Instructions 4 14 ...
Страница 62: ...Installation Instructions 5 20 ...
Страница 76: ...Installation Instructions 8 6 NOTES ...