background image

 

- 2 -

 

4208U-SOC-V0

1    2   3   4     5

(EACH LOOP’S MAX
RESISTANCE:
300 ohms + 10k EOLR)

7

8

ON

1

DIP Switches

4208U

TB1

REED (TAMPER) SWITCH

1

9

8

7

6

5

4

3

2

10k 10k

10k

10k

10k

10k

10k 10k

LOOPS: A

B

C

D

E

F

G

H

12

11

10

(  )

(+)

1

2

3

4

TB2

TO POLLING LOOP
(USE TWISTED PAIR)

(  ) GND

(+) 12V

OPTIONAL AUX.
POWER INPUT.
SEE NOTE 1.

NOTES:

IF USING AUXILIARY POWER ON COMMECRICAL
FIRE/BURG COMBINATION SYSTEMS
(e.g. VISTA-128FBP), DO NOT CONNECT THE
POLLING LOOP GROUND ON TERMINAL 2.
AUXILIARY POWER CAN ONLY BE USED IN
BURGLARY APPLICATIONS.

FOR CE INSTALLATIONS A N6363 EMI
SUPPRESSION BEAD IS REQUIRED.

1.

2.

 

Figure 2.  Summary of Connections 

1    2   3   4     5

6

7

ON

ON

OFF

SIDE VIEW

POSITIONS 2-5:  SELECT THE 8 SENSOR 

DEVICE GROUP ADDRESS
(SHOWN ON, ON, ON,
OFF = 2nd GROUP SELECTION).

POSITION 6:

DEVICE TYPE (SHOWN
ON = “SERIAL NUMBER MODE”).

POSITION 7:

NORMALLY SET TO "OFF"

8

ON

1

POSITION 1:

SELECT RESPONSE TIME 
FOR LOOPS A and B 
(SHOWN ON = SLOW).

POSITION 8:  

SELECT TAMPER PROTECTION
SETTING (SHOWN
“OFF” = TAMPER ENABLED).

}

4208U-001-V2

 

Figure 3.  DIP Switch Settings 

 

Table 1.  4208U Zone Assignments

 

For “Zone Assignment” mode, DIP Switch position 6 must be off. 

When using this mode, program each zone’s “Input Type” as “DIP Switch Polling Loop Device” (DP), where applicable.   

THIS SWITCH SETTING PRESETS THE LOOPS TO THESE ZONE NUMBERS 

 

Z

o

n

e

 

N

u

m
b

e

r

 

DIP Switch Position 

(“-” Means “off”) 

Loop Designations 

 

On 

On 

On 

On 

** 

On 

On 

On 

10 

11 

12 

13 

14 

15 

16 

 

On 

On 

On 

17 

18 

19 

20 

21 

22 

23 

24 

 

On 

On 

25 

26 

27 

28 

29 

30 

31 

32 

 

On 

On 

On 

33 

34 

35 

36 

37 

38 

39 

40 

 

On 

On 

41 

42 

43 

44 

45 

46 

47 

48 

 

On 

On 

49 

50 

51 

52 

53 

54 

55 

56 

 

On 

57 

58 

59 

60 

61 

62 

63 

64 

 

On 

On 

On 

65 

66 

67 

68 

69 

70 

71 

72 

 

On 

On 

73 

74 

75 

76 

77 

78 

79 

80 

 

On 

On 

81 

82 

83 

84 

85 

86 

87 

88 

 

On 

89 

90 

91 

92 

93 

94 

95 

96 

 

On 

On 

97 

98 

99 

100 

101 

102 

103 

104 

 

On 

105 

106 

107 

108 

109 

110 

111 

112 

 

On 

113 

114 

115 

116 

117 

118 

119 

120 

*** 

121 

122 

123 

124 

125 

126 

127 

N/A 

 

 

*Do not select 1 – 8 for VISTA controls. 

 

**If 9 – 16 is selected for controls that have 9 hardwire zones. Loop A (Zone 9) will be inactive.   
***Accommodates option “ONE 4208 IN USE” if referred to in control programming. 

NOTE:  Consult the Control Panel Instructions to determine the valid zone numbers for that control panel.  

Table 2.  4208U Serial Number Assignments

  

THIS SWITCH SETTING PRESETS THE LOOP TO THESE SERIAL NUMBERS 

DIP Switch Position   (“-” Means “off”) 

Loop Designation 

LOOP A 

LOOP B 

LOOP C 

LOOP D 

LOOP E 

LOOP F 

LOOP G 

LOOP H 

ON 

ON 

ON 

ON 

ON 

000-4116 

000-4117 

000-4118 

000-4119 

000-4124 

000-4125 

000-4126 

000-4127 

ON 

ON 

ON 

ON 

006-9908 

006-9909 

006-9910 

006-9911 

006-9916 

006-9917 

006-9918 

006-9919 

ON 

ON 

ON 

ON 

013-9812 

013-9813 

013-9814 

013-9815 

013-9820 

013-9821 

013-9822 

013-9823 

ON 

ON 

ON 

020-9716 

020-9717 

020-9718 

020-9719 

020-9724 

020-9725 

020-9726 

020-9727 

ON 

ON 

ON 

ON 

027-9620 

027-9621 

027-9622 

027-9623 

027-9628 

027-9629 

027-9630 

027-9631 

ON 

ON 

ON 

034-9524 

034-9525 

034-9526 

034-9527 

034-9532 

034-9533 

034-9534 

034-9535 

ON 

ON 

ON 

041-9428 

041-9429 

041-9430 

041-9431 

041-9436 

041-9437 

041-9438 

041-9439 

ON 

ON 

048-9332 

048-9333 

048-9334 

048-9335 

048-9340 

048-9341 

048-9342 

048-9343 

ON 

ON 

ON 

ON 

055-9236 

055-9237 

055-9238 

055-9239 

055-9244 

055-9245 

055-9246 

055-9247 

ON 

ON 

ON 

062-9140 

062-9141 

062-9142 

062-9143 

062-9148 

062-9149 

062-9150 

062-9151 

ON 

ON 

ON 

069-9044 

069-9045 

069-9046 

069-9047 

069-9052 

069-9053 

069-9054 

069-9055 

ON 

ON 

076-8948 

076-8949 

076-8950 

076-8951 

076-8956 

076-8957 

076-8958 

076-8959 

ON 

ON 

ON 

083-8852 

083-8853 

083-8854 

083-8855 

083-8860 

083-8861 

083-8862 

083-8863 

ON 

ON 

090-8756 

090-8757 

090-8758 

090-8759 

090-8764 

090-8765 

090-8766 

090-8767 

ON 

ON 

097-8660 

097-8661 

097-8662 

097-8663 

097-8668 

097-8669 

097-8670 

097-8671 

ON 

104-8564 

104-8565 

104-8566 

104-8567 

104-8572 

104-8573 

104-8574 

104-8575 

 

Note:

 For Commercial and Residential Fire installations, no   

more than one (1) wire per terminal may be connected. 

Содержание ADEMCO 4208U

Страница 1: ...into the raised metal tabs leaving the heads app 1 8 exposed and then hang the 4208U using the two slots on the back WIRING CE For CE installations ADEMCO N6361 EMI suppression bead is required Refer to the N6361 Installation Instructions for wire routing instructions Polling loop and protection loop wires can be brought in either through the back or front of the unit by removing the knockouts Use...

Страница 2: ...4 115 116 117 118 119 120 121 122 123 124 125 126 127 N A Do not select 1 8 for VISTA controls If 9 16 is selected for controls that have 9 hardwire zones Loop A Zone 9 will be inactive Accommodates option ONE 4208 IN USE if referred to in control programming NOTE Consult the Control Panel Instructions to determine the valid zone numbers for that control panel Table 2 4208U Serial Number Assignmen...

Страница 3: ... entering a serial number Duplicate of Zone XX Duplicate of Zone XX is displayed another device with that same serial number is already in the system In that case use a different serial number group setting on the 4208U If learning a serial number by faulting its associated loop make sure that other V Plex devices are not activated as they may interfere with the device being learned VERIFICATION O...

Страница 4: ...eiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits Consult the dealer or an experienced radio TV technician for help INDUSTRY CANADA CLASS B STATEMENT This Class B digital apparatus complies with Canadian ICES 003 Cet appareil numériqu...