Honeywell ADEMCO 4100SM Скачать руководство пользователя страница 2

 

-2 - 

1

2

3

4

5

6

7

8

9

J2
CONNECTOR

VIOLET

GREY

YELLO

W

WHITE

RED

GREEN

BR

O

W

N

BLUE

BLA

CK

4142TR CABLE

(SUPPLIED

WITH 4100SM)

6

5

4

3

2

1

4100SM SERIAL

MODULE

+ PWR

- (GND)

RXD

not used

not used

TXD

not used

DTR

BLUE WHITE

To TB11 Aux. Power (+)

(25mA current draw)

To TB12 Aux. Power (-)

RED

4100SM-014-V1

8

7

To Serial Port

of Computer

 

 

Figure 2. Direct-Wire Connections for VISTA-FBP, 

FA1670C and FA1700C Control Panels 

Connections to an IP or GSM Type Module 

The 4100SM is required to interface the VISTA-FBP, 
FA1670C or FA1700C control panel to an IP or GSM type 

communicating unit. The 4100SM connects to the control 

panel’s circuit board via the supplied 4142TR voltage trigger 
cable. As shown in Figure 3, terminals 3, 6, 7, and 8 on the 

4100SM are used. The 4100SM DB25 serial port connects to 

the Programmer Port of the GSM communication unit. The 
purchase of the VFBPCOMKIT is required.  

1

2

3

4

5

6

7

8

9

7845GSM /7845i-GSM

7845GSM-025-V0

INPUT 1

GR

OUND

OUT 1

OUT 4 OUT 7 OUT 3 OUT 6

OUT 2

OUT 5

VISTA-128FBP/250FBP

FA1670C /FA1700C

J2 CONNECTOR

VIOLET

GRA

Y

YELLO

W

WHITE

RED

GREEN

BR

O

W

N

BLUE

BLA

CK

6

5

4

3

2

1

+ PWR

- (GND)

RXD

not used

not used

TXD

not used

not used

BLUE WHITE

+ (TO TERM 11)

- (TO TERM 12)

RED

8

7

TO

AUX PWR 1

OUTPUT

TB 1

6
7
8

5

11

10

9

2
3

4

1

PROGRAMMER

PORT

FOR EXTERNAL ANTENNA

50 OHM, MMCX ONLY

GSM

GPPS

WEB

MODE 2

MODE 1 

RSSI

Honeywell

4142 TR CABLE

4100SM

K14394LF 25-PIN TO RJ11 CABLE

PARTS SUPPLIED WITH DOWNLOADER KIT P/N VFBPCOMKIT

 

 

Figure 3. Direct-Wire Connections for an IP or GSM Type 

Communication Units 

Checking Your Downloading Software 

Before using the 4100SM for direct-wire downloading, the 
downloading software must be checked to ensure it is 

configured to enable direct-wire operation.  To check the 

software, proceed as follows: 
1.

 

Enter the SETUP screen on the PC (only the Master 
User can do this). 

2.

 

Click on COMM LINK, near the top of the screen. 

3.

 

Hit the [+] key until the screen displays “DIRECT 
WIRE/TELCO.” 

4.

 

Check that the COMM PORT matches the port you 

intend to use.  Hit the [ESC] key to exit the SETUP 
SCREEN. 

Using the 4100SM for Direct-Wire Downloading 

To use the 4100SM for direct-wire downloading, proceed as 

follows: 
1.

 

Make connections described previously in this 
document. 

 

2.

 

Apply power to the control panel and verify that the 

default message (typically “DISARMED – READY TO 
ARM”) is displayed. 

3.

 

Start up the downloading software on your PC, and 
verify that the main menu is displayed. 

4.

 

Make sure that the downloading software is configured 

to operate using the serial port (COM1 or COM2) that 
you selected earlier. 

If you have an internal modem, the serial port must be 
changed every time you change from modem to direct-wire 

operation. 

NOTE: 

The control panel will not function as an alarm 

system while the direct-wire downloading mode is 

active unless you are using a Commercial Fire 

Alarm system.  

5.

 

At the downloading PC, select the file and control 

account information to be downloaded. 

6.

 

Select the DIRECT-WIRE option from the COMM menu 
and hit [Enter].   
If the selected panel type does not allow direct-wire 
operation, the DIRECT-WIRE option will not be 

displayed. 

7.

 

Select the FIRST COMMUNICATION option, if 
required.  Then press the [Enter] key. 
The “START COMMUNICATION” message will begin 
to blink. 

8.

 

Go to the nearest control keypad and enter the Installer 

Code + [#] + [5]. 
The letters “CC” should appear on the fixed-word 
keypad display (“MODEM COMM” on the alpha keypad 

display) to confirm that the direct-wire downloading 

mode is in effect. 
The control panel will continuously and indefinitely 
monitor the keypad terminals for a handshake signal 

from the downloading PC.  (This mode may be cancelled 

by entering an Installer Code + [OFF] sequence.) 

9.

 

Press the [Enter] key on the PC. 
The PC will display a “REQUESTING SESSION” 
message and commence a direct-wire downloading 

session.  At this point, you may do an upload, download, 

or any other PC operation in the same manner that you 
would if a remote connection via the telephone line were 

used.  The communications will take place at a much 

higher speed, however.  The control will automatically 
return to normal alarm system function when the 

downloading session is completed. 

Serial Printer and Navigator Reporter Connections 

The 4100SM can be used to connect the control panel to a 

serial printer or to a PC using the Honeywell Navigator 
Reporter software to print the Event Log. The 4100SM 

connects to the control panel’s circuit board via the supplied 

4142TR voltage trigger cable. As shown in Figures 4 and 5, 
terminals 1, 6, 7, and 8 on the 4100SM are used. The 

colored jumpers may need to be cut, depending on the serial 

printer being used. See note 3 below for details. The 
connections shown in Figures 4 and 5 are the same for the 

printer and the PC. 
 

Содержание ADEMCO 4100SM

Страница 1: ... a header on the control panel s circuit board via the supplied 4142TR voltage trigger cable As shown in Figures 1 and 2 terminals 3 6 7 and 8 on the 4100SM are used The three colored terminals red blue and white must be left uncut for direct wire downloading applications Most IBM compatible PCs have two RS 232 serial ports COM1 and COM2 You must decide which serial port you want to use and then d...

Страница 2: ...erify that the default message typically DISARMED READY TO ARM is displayed 3 Start up the downloading software on your PC and verify that the main menu is displayed 4 Make sure that the downloading software is configured to operate using the serial port COM1 or COM2 that you selected earlier If you have an internal modem the serial port must be changed every time you change from modem to direct w...

Страница 3: ...not used not used TXD not used DTR BLUE WHITE To TB11 Aux Power 25mA current draw To TB12 Aux Power 3M Cable Supplied with 4100SM SERIAL PRINTER SET FOR 8 DATA BITS EVEN PARITY STOP BIT 300 1200 BAUD 4100SM JUMPERS CUT TO SET RESPECTIVE SIGNAL FLOATING COLOR FUNCTION PIN RED BLUE WHITE CD CTS DSR 8 5 6 RED 4100SM 012 V2 8 7 USE GENDER CHANGER NOT SUPPLIED WITH 4100SM IF PRINTER HAS DB25 MALE CONNE...

Страница 4: ...and the 4100SM 3 Go to the COMM screen after selecting DIRECT WIRE and hit the ENTER key two times until the REQUESTING SESSION message appears At this time the meter reading should jump to approximately 12 volts for few seconds and then return to zero If this does not occur there is a possibility that the transmit and receive pins on the computer are reversed Insert a Null Modem adapter not suppl...

Отзывы: