FireLite SLC Wiring Manual —

 P/N 51309:R3  

7/29/2019

Monitor Modules

MMF-300 Wiring Diagrams

5.3.3  MMF-300 Wiring for Emergency Alarm System Applications

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).

Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to “Setting 
an SLC address for a Single Point Module” on page 33.

The figure below shows typical wiring for a supervised and power-limited Emergency Signaling circuit using an MMF-300 module.

See “Power Considerations” on page 63 for information on supervising 24 VDC power.

See Section 6, “Control Modules” for instructions on using control modules as NACs on an SLC.

Refer to the 

Device Compatibility Document 

#15384 for compatible smoke detectors.

+

+

-

-

47K ELR

(supplied

with module)

SLC

MMF-300 Module

programmed for Tornado, 

Hazard, or Medical operation. 

Refer to the control panel 

installation manual.

IDC

UL-listed Signaling 
appliance such as the 
Fire-Lite FSS-2400E

SLC

-em

e

r.

w

m

f

Figure 5.11  Emergency Signaling Wiring with an MMF-300

Содержание 783008112608

Страница 1: ...Intelligent Control Panel SLC Wiring Manual Document 51309 Rev R3 7 29 2019 ECN 3468 ...

Страница 2: ...aches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used...

Страница 3: ...ng or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This syste...

Страница 4: ...riate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed...

Страница 5: ...2 2 Four Wire SLC Class A and Class X 15 2 3 Shield Wire Termination 16 2 4 Control Panel Terminal Blocks 17 2 4 1 MS 9200 17 2 4 2 MS 9600 MS 9600LS MS 9600UDLS 17 2 4 3 MS 9200UDLS Software Version 3 0 18 2 4 4 MS 9200UD MS 9200UDLS Versions 1 and 2 18 2 4 5 MS 9050UD 18 2 4 6 ES 50X 19 2 4 7 ES 200X 19 Section 3 SLC Circuits without Isolators 20 3 1 Overview 20 3 2 NFPA Class B SLC 20 3 3 NFPA ...

Страница 6: ...2 Setting an SLC address for an CMF 300 6 Module 46 6 4 3 Setting NACs as Class B or Class A 46 6 4 4 Disabling Unused Module Addresses 46 6 4 5 Short Circuit Protection 46 6 4 6 Features Not Supported 46 6 4 7 Circuit Board Information 47 6 5 Wiring a CMF 300 6 Module 48 6 5 1 Wiring a Class B NAC Two Wire 48 6 5 2 Wiring a Class A NAC Four Wire 49 Section 7 Relay Modules 50 7 1 Description 50 7 ...

Страница 7: ...1 1 Resistance and Size 63 A 2 Supervising 24 VDC Power 64 Appendix B Surge Suppression 65 B 1 Introduction 65 B 2 Installation 65 B 2 1 Wiring Diagram for MS 9200 66 B 2 2 Wiring Diagram for MS 9600 MS 9600LS MS 9600UDLS MS 9200UD MS 9200UDLS and MS 9050UD 67 B 2 3 Wiring Diagram for ES 50X and ES 200X 68 Appendix C Terminal Conversion Charts for New Legacy Devices 69 C 1 CRF 300 69 C 2 CMF 300 a...

Страница 8: ...0XC respectively unless otherwise specified CMF 300 Legacy Version Module Vertical Rotary Dial CMF 300 Newer Version Module Horizontal Rotary Dial NOTE Only the MMF 300 MMF 302 CRF 300 CMF 300 and MDF 300 modules are available as newer type modules Both the legacy and newer versions share the same part numbers The newer version modules will be phased in replacing the legacy version This manual con...

Страница 9: ...n Instructions I56 3657 H355R Heat Detector w ROR Installation Instructions I56 3657 H355HT Heat Detector 190 Installation Instructions I56 3657 H365 IV Heat Detector 135 Installation Instructions I56 6525 H365R IV Heat Detector w ROR Installation Instructions I56 6525 H365HT IV Heat Detector 190 Installation Instructions I56 6525 D350P Duct Detector Installation Instructions F300 10 00 D350PL A D...

Страница 10: ...tion in the event of a circuit fault Isolator modules are required to meet the requirements of an NFPA Class X circuit I300 Single fault isolator module ISO 6 Six fault isolator module 1 4 2 Monitor Modules Addressable modules that allow the control panel to monitor entire circuits of conventional alarm initiating devices such as manual pull stations smoke detectors heat detectors waterflow and su...

Страница 11: ...includes an alarm relay D350RPLA for Canada Low Flow refers to the air velocity rating of 100 to 4 000 feet per minute 0 5 to 20 32 m sec D355PL An addressable non relay photoelectric low flow smoke detector Low Flow refers to the air velocity rating of 100 to 4 000 feet per minute 0 5 to 20 32 m sec D365PL An addressable non relay photoelectric low flow smoke detector Low Flow refers to the air v...

Страница 12: ...ully compatible with the MS 9200 MS 9200UD MS 9200UDLS MS 9600 MS 9600LS C E MS 9600UDLS E MS 9050UD ES 50X and ES 200X FACPs The devices must be configured for CLIP Classic Loop Interface Protocol Mode operation The address of 300 series devices cannot be set above 99 Compatible devices include 1 4 10 900 Series Addressable Devices Fire Lite s 900 Series of addressable devices are fully compatibl...

Страница 13: ...on on the various devices on an SLC Type of Fault Class B Class A Class X Single Open Trouble Alarm Trouble Alarm Trouble Single Ground Alarm Trouble ground Alarm Trouble ground Alarm Trouble ground Short Trouble Trouble Alarm Trouble Short and open Trouble Trouble Trouble Short and ground Trouble Trouble Alarm Trouble Open and ground Trouble Alarm Trouble Alarm Trouble Communications loss Trouble...

Страница 14: ...ermitted for 2 wire Class B configurations The total DC resistance from the control panel to each branch end cannot exceed 40 ohms Measure DC resistance as detailed and shown below 1 With power removed short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch Wire Requirements Distance in Feet meters Wire Si...

Страница 15: ...ranch A plus Branch B plus Branch C 2 2 2 Four Wire SLC Class A and Class X Loop Resistance The total DC resistance of the SLC pair cannot exceed 40 ohms Measure DC resistance as detailed and shown below 1 Disconnect the SLC channel B Out and SLC channel A Return at the control panel 2 Short the two leads of SLC channel A Return 3 Measure the resistance across the SLC channel B Out leads SLC meas1...

Страница 16: ...connector Feed the shielded wire through the conduit into the control box The shield drain wire must be connected to the shield terminal on the SLC terminal block B B A A SLC meas4 wmf SLC channel B output loop SLC channel A return loop SLC Terminal Block Figure 2 4 Measuring the Wire Length Four Wire SLC NOTE Use of good wiring practice consistent with local electrical codes is expected CAUTION D...

Страница 17: ...ectors and 99 modules 2 4 2 MS 9600 MS 9600LS MS 9600UDLS TB3 provides two types of 24 VDC power Nonresettable and Resettable TB8 provides connections for the SLC wiring 198 addresses are available per loop 99 detectors and 99 modules while operating in CLIP mode 318 addresses are available per loop 159 detectors and 159 modules while operating in LiteSpeed mode TB6 SHIELD SLC SLC TB4 SLC 9200tb w...

Страница 18: ...le per loop 99 detectors and 99 modules 2 4 5 MS 9050UD 24 VDC power may be supplied by a remote power supply such as the Fire Lite FCPS 24FS6 8 TB2 provides connections for the SLC wiring 50 addresses are available any combination of detectors and modules TB10 SLC TB1 SLC Out Connections for wire shield Resettable Power jumper selectable by JP6 Nonresettable Power jumper selectable by JP4 SLC 920...

Страница 19: ...esettable and Resettable user programmable PWR1 has a user programmable Class A wiring option TB12 provides connections for the SLC wiring 198 addresses are available per loop 99 detectors and 99 modules TB12 SLC RTN RTN 24VDC TB11 SLC Out SLC es50tb wmf SLC Return Figure 2 11 ES 50X Terminal Block Resettable or Nonresettable Power user programmable TB12 SLC RTN RTN PWR1 PWR2 TB11 SLC Out Resettab...

Страница 20: ... circuits that do not require isolation devices NFPA Class B NFPA Class A 3 2 NFPA Class B SLC NFPA Class B requirements can be met by using the diagram below T tapping of the SLC wiring is allowed for Class B configuration SLC style4 wmf Two wire Addressable Detector Addressable Module T tapped Circuits Control Panel SLC B B Figure 3 1 Basic NFPA Class B SLC ...

Страница 21: ...s 3 3 NFPA Class A SLC NFPA Class A requirements can be met by using the diagram below T tapping of the SLC wiring is NOT allowed for Class A configuration Control Panel SLC Two wire Addressable Detector Addressable Module SLC style6 cdrwmf SLC Return SLC Out B B A A Figure 3 2 Basic NFPA Class A SLC ...

Страница 22: ... communication problem with all other addressable devices on the remaining branches labeled Continua tion of the SLC in the figure below During a fault condition the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch Once the fault is removed the module automatically reapplies power to the SLC branch or segment 4 1 2 Wiring an Iso...

Страница 23: ... Circuits with Isolators The figure below shows typical wiring of an ISO 6 Isolator Module ISOLATOR 1 ISOLATOR 2 ISOLATOR 3 ISOLATOR 4 ISOLATOR 5 ISOLATOR 6 iso 6wire wmf SLC in from FACP or previous device Figure 4 2 Wiring an ISO 6 Module SLC out to next device status indicators ...

Страница 24: ...n using an I300 isolator module to protect each branch of the SLC is shown below Refer to Figure 4 1 for I300 wiring and to Section 4 1 for limitations Figure 4 3 NFPA Class B SLC Using an I300 Isolator Module Two wire Addressable Detector Addressable Pull Station SLC style4iso wmf Control Panel SLC B B Isolated Branch Isolator Module Isolator Module Isolator Module Isolated Branch Isolated Branch...

Страница 25: ...e I300 module Refer to Figure 4 2 for ISO 6 wiring and to Section 4 1 for limitations Note that the ISO 6 can not accept two wires at one pin Wire Class B SLC loops as shown in the figure below Figure 4 4 NFPA Class B SLC Using an ISO 6 Isolator Module Two wire Addressable Detector Addressable Pull Station Control Panel SLC ISO 6 ISOLATOR 1 Out Out In In SLC style4ISO 6 wmf ISOLATOR 2 ISOLATOR 3 I...

Страница 26: ...tion A will still operate from power on the SLC Out side and Section C will operate from the SLC Return side A combination of isolator modules and isolator bases may be used T tapping is NOT allowed within the Class A configuration Isolator modules shall be within 20 feet 6 1 meters of device and must be enclosed in metal conduit Figure 4 5 NFPA Class A SLC Using Isolator Modules SLC Out SLC Retur...

Страница 27: ...T allowed within the Class X wiring configuration When a detector base or pull station is used install isolator modules on both sides of the device Connections between isolator modules and the device they isolate must be close nippled conduit within 3 feet 91 44 cm 2 1 3 4 3 4 3 4 1 3 1 3 2 1 2 1 SLC style7iiso wmf SLC Out SLC Return Two Wire Addressable Detector Addressable Pull Station Control P...

Страница 28: ... circuit 5 1 1 Addressable Monitor Modules MMF 300 Monitor Module This is an addressable module that monitors either a Class B or Class A circuit of dry contact input devices This module is capable of participating in degraded mode where supported by the FACP NOTE For more information on the individual module specifications refer to the Installation Instructions that are provided with these device...

Страница 29: ...binet The BB 2 can accommodate up to 2 modules and the BB 6 which requires the CH 6 chassis can accommodate up to 6 modules See the Installation Instructions provided with module for proper installation into a cabinet Disable Address Place shunt in Disable 1 position to disable highest module address Disable 2 position to disable highest two module addresses Class B or Class A Select Remove shunt ...

Страница 30: ...MMF 300 this module is used to monitor a single IDC of UL listed compatible two wire 24 volt conventional smoke detectors Refer to the Device Compatibility Document FZMtpH wmf Rotary Switches SLC SLC 24 VDC 24 VDC IDC Return IDC Return IDC Out IDC Out Areas used to record the device address and SLC number Figure 5 3 MMF 302 Interface Module ...

Страница 31: ...ommodate up to 6 modules See the Installation Instructions provided with module for proper installation into cabinet T6 J1 BASE ADDRESS 0 BASE ADDRESS 1 BASE ADDRESS 2 BASE ADDRESS 3 BASE ADDRESS 4 BASE ADDRESS 5 A B SELECT A B SELECT DISABLE 1 DISABLE 2 T1 T0 T2 T3 T4 T5 SW1 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 10 11 13 14 15 12 0 1 2 3 4 5 6 7 8 9 Disable Address Place shunt in Disable 1 position to...

Страница 32: ...the electrical box of the Class B device being monitored 5 2 Installation When installing any of these modules DO NOT mix the following services that the IDC provides Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervision with normally open contact devices fmmtph wmf Rotary Switches SLC SLC 9 H 8 H 7L 6L Address 1 Base Address Areas...

Страница 33: ...to adjust the rotary switches on the module to the desired address The module below is set at 28 NOTE The MS 9050UD and ES 50X can support addresses 01 50 The MS 9200 MS 9200UD MS 9200UDLS and ES 200X can support module addresses of 01 99 The MS 9600 MS 9600LS and MS 9600UDLS can support module addresses 01 159 The plastic stop located on the Tens switch must be removed to set addresses above 99 T...

Страница 34: ... the SLC Use the rotary switches on the module to set it to the required SLC address Refer to Setting an SLC address for a Single Point Module on page 33 The figure below shows typical wiring for a supervised and power limited NFPA Class B IDC using an MMF 300 module Refer to the Device Compatibility Document for compatible smoke detectors See Power Considerations on page 63 for information on sup...

Страница 35: ... for a Single Point Module on page 33 The figure below shows typical wiring for a supervised and power limited NFPA Class A IDC using an MMF 300 module Refer to the Device Compatibility Document for compatible smoke detectors See Power Considerations on page 63 for information on supervising 24 VDC power SLC idcD1tpH wmf 24 VDC Four wire Detector Base Heat detector SLC MMF 300 IDC 24 VDC Power Fil...

Страница 36: ...l wiring for a supervised and power limited Emergency Signaling circuit using an MMF 300 module See Power Considerations on page 63 for information on supervising 24 VDC power See Section 6 Control Modules for instructions on using control modules as NACs on an SLC Refer to the Device Compatibility Document 15384 for compatible smoke detectors 47K ELR supplied with module SLC MMF 300 Module progra...

Страница 37: ...automatically assigned to the next nine higher addresses Refer to Setting an SLC address for a Multi Point Module on page 33 DO NOT set the lowest address above 150 41 for the MS 9050UD or ES 50X 90 for the MS 9200 MS 9200UD MS 9200UDLS or ES 200X as the other module points will be assigned to nonexistent addresses The figure below shows typical wiring for a supervised and power limited NFPA Class...

Страница 38: ...nt Module on page 33 DO NOT set the lowest address above 150 41 for the MS 9050UD or ES 50X 90 for the MS 9200 MS 9200UD MS 9200UDLS or ES 200X as the other module points will be assigned to nonexistent addresses The figure below shows typical wiring for a supervised and power limited NFPA Class A IDC using an MMF 300 10 module Refer to the Device Compatibility Document for compatible smoke detect...

Страница 39: ...cally respond to the next higher address which will be an odd number Use caution to avoid duplicate addressing of modules on the system Refer to Setting an SLC address for a Single Point Module on page 33 Each IDC H L is power limited to 230 microamperes 24 VDC The figure below shows typical wiring for a supervised and power limited NFPA Class B IDC using an MDF 300 10 module Refer to the Device C...

Страница 40: ...ddress for a Single Point Module on page 33 The IDC is supervised and power limited to 230 microamperes 24 VDC The figure below shows typical wiring for a supervised and power limited NFPA Class B IDC using an MMF 302 module Refer to the Device Compatibility Document for compatible smoke detectors 24 VDC power must be provided from a UL listed power supply for fire protection use This power is inh...

Страница 41: ...gure below shows typical wiring for a supervised and power limited NFPA Class A IDC using an MMF 302 module Refer to the Device Compatibility Document for compatible smoke detectors 24 VDC power must be provided from a UL listed power supply for fire protection use This power is inherently supervised by the module See Power Considerations on page 63 for information on 24 VDC power SLC Two wire smo...

Страница 42: ...dress for a Multi Point Module on page 33 DO NOT set the lowest address above 150 41 for the MS 9050UD or ES 50X 90 for the MS 9200 MS 9200UD MS 9200UDLS or ES 200X as the other module points will be assigned to nonexistent addresses The figure below shows typical wiring for a supervised and power limited NFPA Class B IDC using an MMF 302 6 module Refer to the Device Compatibility Document for com...

Страница 43: ...the lowest address above 150 41 for the MS 9050UD or ES 50X 90 for the MS 9200 MS 9200UD MS 9200UDLS or ES 200X as the other module points will be assigned to nonexistent addresses The figure below shows typical wiring for a supervised and power limited NFPA Class A IDC using an MMF 302 6 module Refer to the Device Compatibility Document for compatible smoke detectors 24 VDC power must be provided...

Страница 44: ...0 as a Notification Appliance Circuit NAC 6 3 1 Wiring a Class B NAC Two Wire with Addressable Control Modules A supervised and power limited NFPA Class B NAC using a CMF 300 module Polarized alarm notification appliances are shown con nected to the module in a two wire configuration Refer to the Device Compatibility Document for compatible notification appliances and relays See Power Consideratio...

Страница 45: ...mp of inductive load on mechanical bells and horns 24 VDC power must be provided from a UL listed power supply for fire protection use A power supervision relay is required only on the last module of the power run Do not T tap or branch a Class A circuit Do not loop wiring under the screw terminals of any notification appliance To maintain supervision break the wire run at each device CMF 300 NAC ...

Страница 46: ...small shunt from the A B SELECT set of pins See drawing below and Figure 6 4 on page 47 6 4 4 Disabling Unused Module Addresses A shunt is used in conjunction with a pin block to disable a maximum of three 3 unused module addresses If two module addresses are disabled the lowest four addresses will be functional while the high est two will be disabled For example if the shunt is placed on DISABLE ...

Страница 47: ... remove shunts Disable Address Place shunt onto required pins Select Class B or Class A Remove shunt for Class A Short Circuit Protection Remove shunt from the corresponding pins to enable Shunt 1 for first address 2 for second address etc 1 2 3 4 5 6 SLC Address Set rotary switches to address required Status Indicators Green LEDs are controlled by FACP to indicate status of each module address Fi...

Страница 48: ...erations on page 63 for information on monitoring 24 VDC power Each module can control 2 amps of resistive load on electronic devices or 1 amp of inductive load on mechanical bells and horns 24 VDC power must be provided from a UL listed power supply for fire protection use A power supervision relay is required only on the last module of the power run Do not T tap or branch a Class B circuit Termi...

Страница 49: ...p of inductive load on mechanical bells and horns 24 VDC power must be provided from a UL listed power supply for fire protection use A power supervision relay is required only on the last module of the power run Do not T tap or branch a Class A circuit Do not loop wiring under the screw terminals of any notification appliance To maintain supervision break the wire run at each device NOTE Refer to...

Страница 50: ...33 7 2 2 Wiring a CRF 300 Module Form C Relay The figure below shows a CRF 300 module wired to the Control Panel Load Description Application Maximum Voltage Current Rating Resistive Non Coded 30 VDC 3 0 A Resistive Coded 30 VDC 2 0 A Resistive Non Coded 110 VDC 0 9 A Resistive Non Coded 125 VAC 0 9 A Inductive L R 5ms Coded 30 VDC 0 5 A Inductive L R 2ms Coded 30 VDC 1 0 A Inductive PF 0 35 Non C...

Страница 51: ...C N O COMM BASE ADDRESS 0 N C N O COMM BASE ADDRESS 1 N C N O COMM BASE ADDRESS 2 N C N O COMM BASE ADDRESS 4 N C N O COMM BASE ADDRESS 5 Disable Address Place shunt onto required pins SLC Address Set rotary switches to address required Status Indicators Green LEDs are controlled by FACP to indicate status of each module address Figure 7 2 CRF 300 6 Control Relay Module crf 300 6 wmf ...

Страница 52: ... A shunt is provided on the circuit board to disable a maximum of three 3 unused module addresses If two module addresses are disabled the lowest four addresses will be functional while the highest two will be disabled For example if the shunt is placed on TWO and the base address is set to 28 the module addresses will be assigned to 28 29 30 and 31 To disable addresses remove the shunt from its s...

Страница 53: ...o 156 The module will automatically assign the next three addresses as appropriate to monitored input 1 relay output 2 and monitored input 2 8 2 2 Wiring a CDRM 300 Module Form C Relay The figure below shows a CDRM 300 module wired to the Control Panel Load Description Application Maximum Voltage Current Rating Inductive PF 0 35 Non Coded 25 VAC 2 0 A Resistive Non Coded 30 VDC 3 0 A Resistive Cod...

Страница 54: ...nsor s LEDs are latched on If Alarm Verification is OFF disabled the sounder will activate when the sensor s visible LEDs are latched on for approximately 10 seconds The B224RB WH IV Relay Detector Base includes Form C latching relay contacts for the control of an auxiliary function The relay operates 12 seconds nominally after activation of the sensor head remote annunciator output The B224BI WH ...

Страница 55: ...wn connected to an SLC is shown in the figure below An optional RA100Z RA400Z Remote LED Annunciator is shown connected to the detector SLC B5012wire wmf RA100Z RA400Z Remote LED Annunciator Optional To Next Device on SLC From Control Panel SLC Figure 9 1 Wiring a B300 6 B210LP or B501 Detector Base NOTE The B300 6 andd B210LP base wiring is identical to the B501 B501 is the flangeless model ...

Страница 56: ... acceptable and an isolator module must be installed as shown in the figure below 9 5 Wiring a Relay Base Figure 9 3 shows typical wiring of a B224RB plug in relay detector base connected to an SLC SLC Out SLC In Conduit I300 Isolator Module slc 224bi2wire wmf Figure 9 2 Wiring of a B224BI Isolator Base Mounting Plate Note The grid pattern on the redesigned B224BI mounting plate has been removed f...

Страница 57: ...ply Optional Sounder Interconnect NOTE For more detailed wiring on the sounder base refer to the device s installation instructions NOTE The W GATE as part of the wireless network has been tested for compliance with the Federal Communications Commission FCC requirements of the United States Government It has not been evaluated for use outside the USA Use of this system outside the USA is subject t...

Страница 58: ...on the SLC in Class A installations SLC connections are power limited by the panel An interruption in the SLC that causes a loss of power at the W GATE for more than 100ms may result in a trouble condition and loss of fire protection provided by the wireless devices for approximately 15 minutes Use of a regulated external 24VDC power source not SLC power is recommended for installations that requi...

Страница 59: ...l 24VDC Power Source The W GATE provides isolation of short circuits of the SLC in Class A installations SLC connections are power limited by the panel 24VDC must be power limited by the source 2 6 wmf Figure 9 7 W GATE Powered by a Regulated External Source External 24VDC Power SLC in from FACP device SLC out to next device Class B or SLC return to FACP Class A ...

Страница 60: ... to 5 2 1 Setting an SLC address for a Single Point Module on page 33 10 2 2 Wiring a Beam Detector Typical wiring of a BEAM355 beam detector connected to an SLC is illustrated in the figure below NOTE This section provides basic wiring and addressing information For critical information on device installation operation and alignment refer to the Installation Instructions provided with these devic...

Страница 61: ...I FL beam detector connected to an SLC is illustrated in the figure below Heater Power Heater Power Rotary address switches USB port SLC Out SLC In Aux Remote test input Remote trouble output Remote alarm output Not used Not used Heater on off switch RTS151 KEY connections Figure 10 2 OSI RI FL Beam Detector Terminal Block Wiring ...

Страница 62: ...it is factory preset with an address of 00 To set an SLC address refer to Setting an SLC address for a Single Point Module on page 33 11 2 2 Wiring a Manual Pull Station Figure 11 1 shows typical wiring for a BG 12LX Manual Pull Station to an SLC NOTE For more information refer to the Installation Instructions provided with this device US P AT 4440991 SLC To next device on SLC SLC bg12lx2 wmf Figu...

Страница 63: ...of line relay whichever is greater in volts N total number of detectors on the 24 VDC supply circuit Is detector current in standby Na number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia detector current in alarm Ir end of line relay current Nb number of Notification Appliance Devices Ib Notification Appliance current when activated The minimum supply v...

Страница 64: ... open the supervised circuit generating a trouble condition There fore the relay needs to be installed at the end of the supervised circuit so it will not disrupt the operating capability of all the devices on that circuit The relay can be installed in line with any leg or of the supervised NAC circuit either a Class B or a Class A circuit The drawing below illustrates this concept An alternate me...

Страница 65: ...s required by the NEC Add these additional suppressors in series with the SLC wiring at the building entry exit Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below B 2 Installation Mounting of the surge suppressor must be inside the FACP enclosure or in a separate encl...

Страница 66: ...T OUTPUT L1 L2 L3 L4 L1 L2 L3 L4 GRND INPUT OUTPUT L1 L2 L3 L4 L1 L2 L3 L4 GRND SLC plpn1 wmf SLC Loop SLC Terminal Block Optional Four wire Return Loop Class A PLP 42N PLP 42N A B A B A Shield B Shield NOTE Use 12AWG 3 25mm2 to 18AWG 0 75mm2 wire with crimp on connectors to connect the unit s ground terminal to equipment ground Wire length must be minimized to provide best protection SLC slcp1 wm...

Страница 67: ...B A B A A Shield B Shield INPUT OUTPUT L1 L2 L3 L4 L1 L2 L3 L4 GRND INPUT OUTPUT L1 L2 L3 L4 L1 L2 L3 L4 GRND SLC plpn4 wmf SLC Loop SLC Terminal Block Optional 4 wire Return Loop Class A PLP 42N PLP 42N B A B A A Shield B Shield NOTE Use 12AWG 3 25mm2 to 18AWG 0 75mm2 wire with crimp on connectors to connect the unit s ground terminal to equipment ground Wire length must be minimized to provide b...

Страница 68: ... L1 L2 L3 L4 GRND INPUT OUTPUT L1 L2 L3 L4 L1 L2 L3 L4 GRND SLC plpn5 wmf SLC Loop SLC Terminal Block Optional 4 wire Return Loop Class A PLP 42N PLP 42N B A B A Ground stud on inside of backbox Refer to Figure 2 4 in the FACP manual NOTE Use 12AWG 3 25mm2 to 18AWG 0 75mm2 wire with crimp on connectors to connect the unit s ground terminal to equipment ground Wire length must be minimized to provi...

Страница 69: ...en 2 Common 1 Open 1 Legacy Module V Type Common 2 Closed 2 Open 2 Common 1 Closed 1 Open 1 SLC SLC Legacy Module Terminal Number V Type Terminal Function Newer Module Terminal Number H Type 1 SLC 1 2 SLC 2 3 Unused 3 4 Normally Open 1 5 5 Normally Closed 1 6 6 Relay Common 1 7 7 Normally Open 2 8 8 Normally Closed 2 9 9 Relay Common 2 10 N A Unused 4 N A Unused 11 Table C 1 CRF 300Terminal Conver...

Страница 70: ... C 2 CMF 300 and MMF 302 Terminal Conversions Newer Module H Type Class A Supervision Class A Supervision Class A B Supervision SLC SLC SLC SLC Class A Supervision Class A Supervision Class A B Supervision Class A B Supervision Legacy Module V Type Legacy Module Terminal Number V Type Terminal Function Newer Module Terminal Number H Type 1 SLC 1 2 SLC 2 3 Unused 3 4 Unused 4 5 Unused 5 6 Class A B...

Страница 71: ... 7 ONES ONES 0 2 4 6 8 0 2 4 6 8 Newer Module H Type Address 1 H Address 1 H Base Address L Base Address L SLC SLC SLC SLC Address 1 H Address 1 H Base Address L Base Address L Legacy Module V Type Legacy Module Terminal Number V Type Terminal Function Newer Module Terminal Number H Type 1 SLC 1 2 SLC 2 3 Unused 3 4 Unused 4 5 Unused 5 6 Base Address L 6 7 Base Address L 7 8 Address 1 H 8 9 Addres...

Страница 72: ...se 1 2 3 To next device on SLC SLC SLC B501wire wmf RA100Z RA400Z Remote LED Annunciator Optional B501 only For connection of cable shield Use a female disconnect to wire the RA100Z RA400Z to Terminal 1 Figure D 1 Wiring the Legacy B350LP or B501 Detector Base NOTE The B350LP base wiring is identical to the B501 except there is no shield terminal ...

Страница 73: ...es D 2 B224BI Isolator Base D 3 B224RB Relay Base SLC In SLC Out SLC 224BIwire wmf Conduit I300 Isolator Module Figure D 2 Wiring the Legacy B224BI Isolator Base SLC b224rb wmf To next device on SLC For connection of cable shield 3 Relay Common 2 Normally Open 1 Normally Closed Figure D 3 Wiring the Legacy B224RB Relay Base ...

Страница 74: ...tector Base Layouts for Legacy Devices B501BH 2 and B501BHT 2 Sounder Bases D 4 B501BH 2 and B501BHT 2 Sounder Bases slc b501bhwiring wmf Figure D 4 Wiring the Legacy B501BH 2 and B501BHT 2 Sounder Bases SLC SLC UL Listed 24V Power Supply Optional Sounder Interconnect ...

Страница 75: ... indicates black color B501BH B501BHT B501BHA B501BHTA Sounder base includes Sounder base with temporal sounder UL 8th Edition B501BH 2 B501BHT 2 N A Sounder base includes Sounder base with temporal sounder UL 9th Edition B224RB B224RB WH B224RB IV B224RBA B224RBA WH B224RBA IV Low Profile Intelligent relay base B224BI B224BI WH B224BI IV B224BIA B224BIA WH B224BIA IV Low Profile Intelligent isola...

Страница 76: ... the system against wire to wire short circuits on six isolated SLC circuits Functionally the same as six I300 A modules Multi input output modules MMF 300 10 MMF 300 10A Supervises ten Class B addressable Initiating Device Circuits IDC which monitor normally open contact initiating devices MMF 302 6 MMF 302 6A Monitors six zones of conventional two wire detectors CDRM 300 CDRM 300A Dual Class B m...

Страница 77: ...e 11 50 address disabling 52 address setting 52 circuit board 51 wiring 52 D D350P Detector 11 D350RP Detector 11 D355PL detector 11 D365PL detector 11 DC resistance 14 15 detector 54 bases 54 75 beam 60 heat 54 ion 54 multi criteria 54 detector bases wiring of 55 detectors listing 11 75 devices addressable 22 auxiliary 11 maximum number between isolators 22 supervised 64 DNR W Duct Detector Housi...

Страница 78: ...1 SD355 Detector 11 54 SD355CO Detector 12 SD355R Detector 11 SD355T Detector 11 SD365 Detector 11 SD365CO Detector 11 SD365R Detector 11 SD365T Detector 11 sensing circuit thermistor 11 short circuit 22 signaling line circuit 10 single point module 33 SLC address setting of 33 54 SLC connections 17 SLC terminal block 16 SLC wiring 34 35 36 37 38 39 40 41 42 43 SLCP 30 65 smoke detectors 54 sounde...

Страница 79: ...IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the o...

Страница 80: ...One Fire Lite Place Northford CT 06472 1601 USA USA Phone 203 484 7161 Canada Phone 905 856 8733 www firelite com ...

Отзывы: