Honeywell 5193SD Скачать руководство пользователя страница 3

HW-500-003 

I56-3934-002R

Refer to the manufacturer’s published instructions for proper use of the 
canned smoke agent.

C.  Direct Heat Method (5193SDT only) 

 

 Using a 1000-1500 watt hair dryer, direct the heat toward either of the 
thermistors. Hold the heat source about 12 inches from the detector to 
avoid damage to the plastic.

D.     Auto-maintenance  Feature

:  Test  detector  alarm  operation  from  the 

control  panel  if  applicable  (refer  to  control  panel  test  procedure). 

If a detector fails any of the above test methods, its wiring should be checked 
and it should be cleaned as outlined in the 

Maintenance

 section. If the 

detector still fails, it should be replaced.
Notify the proper authorities when the system is back in service.

Maintenance

NOTE:

  Before  performing  maintenance  on  the  detector,  notify  the  proper 

authorities that maintenance is being performed and the system will be tem-
porarily out of service. Disable the zone or system undergoing maintenance 
to prevent any unwanted alarms. 

Power must be removed from the panel 

before performing maintenance of any kind.

1.  Remove the detector cover by turning counterclockwise. 
2.  Vacuum the cover or use canned air to remove any dust or debris.
3.   Remove the top half of the screen/sensing chamber by lifting straight up 

(Figure 6).

4.   Vacuum or use canned air to remove any dust or particles that are pres-

ent on both chamber halves.

5.   Replace the top half of the screen/sensing chamber by aligning the arrow 

on  the  screen/sensing  chamber  with  the  arrow  on  the  housing.  Press 
down firmly until the screen/sensing chamber is fully seated. 

6.   Replace the detector cover by placing it over the screen/sensing chamber 

and turning it clockwise until it snaps into place.

7.  Reinstall the detector and test. (See the 

Testing

 section.)

8.  Notify the proper authorities when the system is back in service.

FIGURE 6: REMOVING/REPLACING SCREEN/SENSING CHAMBER

REMOVABLE
DETECTOR
COVER

SCREEN/SENSING
CHAMBER
(TOP HALF)

DETECTOR
HOUSING

S0136-00

CAUTION

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

Do NOT Install Detectors in the Following Areas:

In  or  near  areas  where  particles  of  combustion  are  normally  present 

s

such as kitchens; in garages (vehicle exhaust); near furnaces, hot water 
heaters, or gas space heaters.

In very cold or very hot areas.

s

In wet or excessively humid areas, or next to bathrooms with showers.

s

In dusty, dirty, or insect-infested areas.

s

Near fresh air inlets or returns or excessively drafty areas. Air condition-

s

ers,  heaters,  fans,  and  fresh  air  intakes  and  returns  can  drive  smoke 
away from the detector.

Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), and/or ap-
plicable codes for specific information regarding the spacing and placement 
of smoke detectors. 

CAUTION

Dust covers are an effective way to limit the entry of dust into the smoke de-
tector sensing chamber. However, they may not completely prevent airborne 
dust particles from entering the detector. Therefore, Honeywell recommends 
the removal of detectors before beginning construction or other dust produc-
ing activity. When returning the system to service, be sure to remove the dust 
covers from any detectors that were left in place during construction.

Please refer to insert for the Limitations of Fire Alarm Systems

FCC STATEMENT

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must 
accept any interference received, including interference that may cause undesired operation.
Note: 

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide 

reasonable  protection against harmful interference in a residential installation. This equipment generates,  uses and can radiate radio frequency energy and, if not installed and used 
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular instal-
lation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to 
try to correct the interference by one or more of the following measures:
 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help. 

For the latest warranty information, please go to: www.security.honeywell.com/hsc/resources/wa