- 5 -
Step-by-Step
Tech Support
Updated 7/27/10
02 Control
Panel
Type
02
Enter 1 for the Vista-10, 10se-Via30p,30pse – 4140xmp
Enter 2 for the Vista-10/15/20p, Vista-20, 20HW, 20SE, 20HWSE & Vista-
15
Enter 4 for the Vista-40, 50p, 128b/bp, 250bp and 128fb/fbp and 250fbp
For Integration of the 4500 Thermostat module complete the following:
03 Units
of
Temperature
0
1 – Temperature in Celsius
0 – Temperature in Fahrenheit
04
Thermostat #1 Enable and Address
00
00 – Thermostat #1 disabled
01 – Thermostat #1 enabled and set to address 1
05 Thermostat
#1
Swing
1,4
Digit #1: Swing above set point
Digit #2: Swing below set point
Above (Digit #1)
Below (Digit #2)
°F
°C °F °C
1 0.0
0.0 1 0.0 0.0
2 +0.50 +0.30 2 -0.50 -0.30
3 +0.75 +0.40 3 -0.75 -0.40
4 +1.00 +0.60 4 -1.00 -0.60
5 +1.50 +0.80 5 -1.50 -0.80
6 +2.00 +1.10 6 -2.00 -1.10
7 +2.50 +1.40 7 -2.50 -1.40
Figure 5: Swing Points
Do Not Select a 1,1
This field defines how many degrees below the set point the heat will turn
on, and how many degrees above the set point the heat will turn off. These
values also define the swing of the air conditioner operation.
06
Announce the Thermostat #1 Temperature
0
0 – Do not announce thermostat #1 Temperature
1 – Announce thermostat #1 temperature as part of the status report.
This is recommended that this field be programmed to enable announcement
of ambient temperature so that premise temperature can be monitored when
user is away.
07
Thermostat #1 Descriptor #1
000
000 – No Announcement
08
Thermostat #1 Descriptor #2
000
000 – No Announcement
09
Thermostat #1 Descriptor #3
000