4232CBM

Connected Building Module

INSTALLATION AND SETUP GUIDE

 

 

About the 4232CBM 

The 4232CBM Connected Building Module is intended 
to provide connection between compatible Honeywell 
control panels and supported third-party software and 
hardware products. It provides an interface between 
the control panel’s ECP bus and external equipment 
with either RS422 or RS232 interfaces. The connection 
and configuration of this device is application-specific. 
Please refer to the documentation for your external 
equipment for information on which connection method 
to use, and how to configure the external device to 
communicate properly with the 4232CBM. 

NOTE:

 The connected building features offered by the 

4232CBM are not evaluated by ETL or UL. 

Compatible Controls 

Control Firmware 

Level 

VISTA-15P, VISTA-15PSIA 
VISTA-20P, VISTA-20PSIA 

V9.1 or higher 

VISTA-21iP, VISTA-21iPSIA  V3.13 or higher 

VISTA-128BPT, 
VISTA-128BPTSIA 

All versions 

 

The 4232CBM module connects to the control panel 
via the panel’s ECP terminals, and connects to the 
external computer or other equipment via either RS422 
or RS232 connections, according to the application. 

The module is powered via the control panel’s ECP 
+12VDC connection. 

 

Wiring the Module 

Refer to the diagram below for connections. 

Mounting the Module  

Mount the module inside the control panel cabinet 
using double-sided tape (supplied). Make sure the 
solder connections on the bottom of the PC board do 
not touch the cabinet. 

 

LED Indications 

Four green LEDs indicate the following conditions:  

LED Condition 

Meaning 

On 

message waiting for the 
external device 

external 
device 

Flashing 

check connection to the

 

external device 

Panel 

On or Blink 

keypad data waiting for the 
external device 

Slow Blink  

power on, normal operation 

Flashing 

power on, not configured 

Power 

Off power 

off 

Data 

Blink  

receiving data from the external 
device 

 

Specifications 

Board Dimensions 

3.75” W x 2.5” L x 0.875” D 

Current Drain 

50mA nominal; 75mA max 

ECP Input Voltage 

8-14VDC 

Wire Run Length 

RS232 Connection: 50 ft max with 

24 AWG twisted pair wire 

RS422 Connection: 1000 ft max 

with 24 AWG twisted pair wire 

ECP Connection: 900 ft max home 

run with 22 AWG unshielded wire 

Temperature  

32°F (0°C) to 140°F (60°C)   

 

 

1. 

4232CBM to External Equipment Connection

: For RS232 applications, connect the three RS232 lines 

(GND, Tx and Rx) to the external equipment. For RS422 applications, connect the four RS422 lines (Tx+/- 
and Rx +/-) to the appropriate points on the external equipment.

 

 

4232CBM-001-V0

CONTROL         4232CBM

CONTROL PANEL

ECP CONNECTION

RS422

CONNECTIONS

9-PIN

CONN.

RS232

CONNECTIONS

4232CBM PC BOARD

DATA (RECEIVING)

(MESSAGE WAITING)

PANEL (KEYPAD DATA)

POWER

LED INDICATORS

STANDARD

9-PIN

SERIAL

CONNECTOR

NOT USED

DATA OUT

GND

DATA IN

12VDC

4-WIRE

HARNESS

TX      
TX      
RX      
RX      

RX (YELLOW)

GND (BLACK)

TX (GREEN)

12VDC (RED)

120

NOTE:

 IF WIRE RUN TO RS422 DEVICE EXCEEDS 100 FT, INSTALL

120 OHM RESISTOR BETWEEN RX      AND RX      TERMINALS ON
THE 4232CBM.

RESISTOR

5(GND)

3(TX)

2(RX)

GND

RX

TX

 

 

NOTES:  

A.  The connections shown above are used for most applications where the external equipment has a male DE-9 

connector (for example, PCs and most home automation equipment). 

B.  For RS422 applications, refer to the documentation for your external equipment. 

 