4219
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4
3
2
1
ZONES A
B
C
D
F
G
H
TAMPER JUMPER POSITION
4219 IN CABINET
(NOT TAMPER)
4219 REMOTE
(TAMPER PROTECTED)
TB1
TB2
4-PIN CONSOLE PLUG
CONNECTIONS SAME
AS TB2
1
2
3
4
DATA OUT
TO CONTROL
DATA IN
FROM CONTROL
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE:
300 OHMS + EOL)
5
8
11
REED (TAMPER) SWITCH
2
E
1
3
4
6
7
9
10
12
DIP SWITCH
FOR SETTING ADDRESS
AND ZONE A RESPONSE
NOTE
FOR CE INSTALLATIONS A
N6361EMI SUPPRESSION
BEAD IS REQUIRED.
4219-SOC-V0
Figure 2. Summary of Connections
4 2 1 9 A D D R E S S S E T T I N G S
SWITCH
NUMBER
("—" means "OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
ON —
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON —
3
ON ON
—
—
ON ON
—
—
ON ON
—
—
ON ON
—
—
4
ON ON ON ON
—
—
—
—
ON ON ON ON
—
—
—
—
5
ON ON ON ON ON ON ON ON
—
—
—
—
—
—
—
—
1
2
345
➞
➞
➞
➞
➞
OFF
ON
DIP SWITCH:
(WHITE AREAS DENOTE SWITCH HANDLES)
4219-001-V0
POSITIONS 2-5:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS.
CONSULT CONTROL'S INSTRUCTIONS FOR ADDRESS USE.
SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES ZONE A's RESPONSE TIME:
ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED).
OFF = FAST (10MS) RESPONSE TO AN OPEN.
Figure 3. DIP Switch Settings
SEE THE CONTROL PANEL’S INSTALLATION AND SETUP GUIDE FOR COMPLETE INFORMATION
REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SYSTEM.