® BUS WIRING GUIDELINES

3

74-2865—04

Table 1. Daisy-chain FTT Network Bus Topology Transmission Specifications (Doubly Terminated).

NOTES:

See Table 2 for singly terminated FTT network bus topology transmission specifications.

See Tables 3 and 4 for a list of Honeywell provided FTT daisy-chain and free topology network wire/cables.

See the generic cable manufacturer information that meets Echelon LonWorks Bus specifications in Table 5.

Table 2. FTT Network Free Topology Transmission Specifications (Singly Terminated).

Table 3. Honeywell Provided Daisy-Chain (Doubly Terminated) FTT Network Wire/Cables.

Table 4. Honeywell Provided Free Topology (Singly Terminated) FTT Network Wire/Cables.

NOTE:

Honeywell Cable, www.honeywellcable.com, is the recommended manufacturer of network wire.

Wire/Cable Type (Unshielded)

Cable Parameters

Maximum FTT Network Bus 

Length for Segment(s)

C nF/km Vprop% of c AWG/Dia. RloopW/km

Honeywell Cable 1125 (stranded non-plenum) 79

67

16/1.5 mm

2

17.9

4600 feet (1400 m)

Belden 85102 (stranded non-plenum)

56

62

16/1.5 mm

2

28

8900 feet (2700 m)

Belden 8471 (stranded non-plenum)

72

55

Level IV Cable Specifications, 22AWG (solid/
stranded twisted pair)

49

67

22/.34 mm

2

106

4600 feet (1400 m)

TIA568A Category 5 24 AWG (twisted pair 
solid or stranded, plenum or non-plenum)

46

58

24/.27 mm

2

168

3000 feet (900 m)

Wire/Cable type (Unshielded)

Maximum Length for Segment(s)

Node-to-Node

FTT Network Bus

Honeywell Cable 1125 (stranded non-plenum)

1640 feet (500 m)

1640 feet (500 m)

Belden 85102 (stranded non-plenum)

1640 feet (500 m)

1640 feet (500 m)

Belden 8471 (stranded non-plenum)

1300 feet (400 m)

Level IV Cable Specifications, 22AWG (solid/stranded twisted pair)

TIA568A Category 5 24 AWG twisted pair (solid or stranded, plenum or 
non-plenum)

820 feet (250 m)

1500 feet (450 m)

Wire/Cable Type (Stranded Unshielded)

Maximum FTT Network Bus Length for Segment(s)

Honeywell Cable 3252 - plenum (one twisted pair)

4600 feet (1400 m)

Honeywell Cable 3253 - plenum (two twisted pair)

Honeywell Cable 1061 - non-plenum (one twisted pair)

Paige AK3797 - plenum (one twisted pair)

Paige AK3799 - plenum (two twisted pair)

Paige AK3798 - non-plenum (one twisted pair)

Wire/Cable Type (Stranded Unshielded)

Maximum Length for Segment(s)

FTT Network Bus

Node-to-Node

Honeywell Cable 3252 - plenum (one twisted pair)

1640 feet (500 m)

1300 feet (400 m)

Honeywell Cable 3253 - plenum (two twisted pair)

Honeywell Cable 1061 - non-plenum (one twisted pair)

Paige AK3797 - plenum (one twisted pair)

Paige AK3799 - plenum (two twisted pair)

Paige AK3798 - non-plenum (one twisted pair)

Содержание 3252

Страница 1: ... topology architecture allows the user to wire the control devices with virtually no topology restrictions Unlike bus wiring designs the FTT system uses a free topology wiring scheme that supports T tap star loop mixed and or daisy chain see Fig 1 This design has many advantages First the installer is free to select the method of wiring that best suits the installation reducing the need for advanc...

Страница 2: ...rk traffic may benefit from the use of a Q7751A router which forwards packets only when necessary Routers are not allowed within loops Fig 2 Repeaters and router in a FTT network Fig 3 Physical layer repeater Q7740A 2 Way or Q7750B 4 Way NETWORK CABLING AND CONNECTIONS This section provides information about cabling and FTT network connections IMPORTANT For network terminal connections twist the w...

Страница 3: ... twisted pair 49 67 22 34 mm2 106 4600 feet 1400 m TIA568A Category 5 24 AWG twisted pair solid or stranded plenum or non plenum 46 58 24 27 mm2 168 3000 feet 900 m Wire Cable type Unshielded Maximum Length for Segment s Node to Node FTT Network Bus Honeywell Cable 1125 stranded non plenum 1640 feet 500 m 1640 feet 500 m Belden 85102 stranded non plenum 1640 feet 500 m 1640 feet 500 m Belden 8471 ...

Страница 4: ...t See Fig 1 and 5 Fig 5 Physical connection of module for a single termination network Daisy Chain Double Termination Network Segment In a daisy chain free topology segment doubly terminated two terminations are required one at each end of the FTT daisy chained network segment See Fig 6 and 7 Fig 6 FTT termination module wiring for double termination network topology Fig 7 Physical connection of m...

Отзывы: