Page 4 of 5
62-86-33-41
Step Action
7
Calibrate the potentiometer.
Connect a multi meter set to ohms (
Ω
) to terminals TB4-35 & TB4-36.
Use a small allen wrench in the hole on the potentiometer actuator sleeve to turn the potentiometer.
Adjust the potentiometer to 500
Ω
+/- 5
Ω
.
Install the set screw.
When the potentiometer is set for 500
Ω
tighten the set screw.
8
Replace the gasket.
9
Re-attach the top cover.