6. Set charge terminating voltage
1. The power supply must have reached operating temper-
ature.
For this purpose it must be operated for at least two hours at
rated load and with closed housing.
2. Connect a
A not completely charged accumulator leads to a miss-
alignment.
3. Adjust the voltage at the accumulator terminals using the
potentiometer PO3 according to the ambient temperature at
the accumulator as per the following table.
Only alter the charge terminating voltage:
1. After measuring the exact temperature and
2. When the voltage deviates >200 mV from the set value as
per following table.
charged accumulator.
Please take note of the type of accumulator.
ATTENTION:
T (°C)
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
All other types of
accumulators
T (°C)
0
+5
+10
+15
+20
+25
+30
+35
+40
+45
+50
Sonnenschein accum.
A500 series
(Condition on delivery)
U (V)
14.50
14.30
14.10
13.95
13.80
13.65
13.50
13.40
13.30
13.25
13.20
L
U (V)
14.10
13.95
13.75
13.60
13.50
13.45
13.40
13.35
13.30
13.25
13.20
L
Functional Description
Collective faults:
Version A:
With
Version B:
Without
Mains
(continued)
The messages are transmitted via the outputs
- "Fault", HIGH active and
- "
", LOW active.
The following fault causes are possible:
Mains fault / accum. defective or missing /
input
resistor R33
Display of mains and accumulator fault
resistor R33
Disply of accumulator fault only.
, output, HIGH active.
This output is active during power on.
(ST1/1), input, LOW active.
For connecting "
" outputs of additional emergency power
supplies (cascading).
Fault
SE
SE
Fault
Information on function of the fault outputs:
5. Technical Data
Rated operating voltage
230 V AC
Operating voltage range
-15 % to +10 %
Frequency
40 Hz to 60 Hz
Power consumption
75 VA
Maximum constant current
2 A
Short-term continuous current drain (5 min.) 2.5 A max.
Maximum charging current
1.1 A
Approved accum. capacity as per VdS
32 Ah max.
No. of connectable accumulators
2 max.
Possible accu. combinations e.g. 2x10/ 2x16/ 1x26 Ah
Current consumption as per VdS
for 60 hours at 32 Ah accum. capacity
approx. 500 mA
Permanent accumulator monitoring
Temperature-guided accum. charging voltage
Operating temperature range
-5 °C to +45 °C
Storage temperature range
-25 °C to +70 °C
Environmental class as per VdS
II
Dimensions - PCB:
97.5 x 250 mm
(with
charged accum.)
6 Mounting and Connection Instruktions Mains/charger unit 12 V DC / 32 Ah