NOTE: Some panels support extended addressing. In order to set the module 
above  address  99  on  compatible  systems,  carefully  remove  the  stop  on  the 
upper rotary switch (see Figure 7). If the panel does not support extended ad-
dressing, do not set the lowest address above 90.

FIgURE 7:

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

4.   A shunt is provided to disable a maximum of two unused modules in 

Class B operation and one unused module in Class A operation. Modules 
are disabled from the highest address and work downward. If two mod-
ules are disabled, the lowest eight addresses will be functional, while the 
highest two will be disabled. For example, in Class B operation, if the 
shunt for Address Disable is placed on “two” and the base switch is set 
to 28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 34 and 35 
while disabling the highest two positions.

5.   A  communications  loss  feature  is  available  on  some  panels.  When  a 

module detects an alarm condition on the Initiating Device Circuit and 
there  is  no  activity  on  the  communication  loop,  the  MMF-300-10  will 
send a periodic signal of its own to alert other receiving devices in the 
system. A single shunt is used to enable (shunt on) or disable (shunt off) 
this feature for all modules on the board.

NOTE: Place unused shunts on single pin to store on board for future use.
NOTE: Power must not be applied to the unit when changing functionality of 
the shunts.

wIRINg NOTES

 Power-limited  circuits  must  employ  type  FPL,  FPLR,  or  FPLP  cable  as 

• 

required by Article 760 of the NEC.

PROgRAMMINg

The MMF-300-10 module operates with the following Fire Alarm Control Panels:

MS-9200

• 

MS-9600

• 

The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual. 

FIgURE 6B. INSTALLATION OF MMF-300-10 MODULE IN FRONT 
CHASSIS POSITION:

2

3

1

Step 1: 

 Insert  the  bottom  edge  of  the  MMF-300-10  module  down  into  a 
front slot of the chassis.

Step 2: 

 Carefully swing the upper edge of the board towards the back of 
the chassis until it touches the 11/4˝ (31.75mm) standoffs installed 
on the rear module.

Step 3: 

 Align two 4-40 screws with the two standoffs and tighten.

Step 4: 

 Address and wire the modules according to the instructions in this 
manual.

wIRINg

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 
regulations.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All  wiring  to  the  MMF-300-10  is  done  via  terminal  blocks.  In  order  to 

properly make electrical connections strip approximately 1/4˝ of insula-
tion  from  the  end  of  wire,  sliding  the  bare  end  of  the  wire  under  the 
clamping plate screw.

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module (between 01 and 150).

 

 In  Class  B  operation,  the  remaining  modules  are  automati-

 

cally  assigned  to  the  next  nine  higher  addresses.  For  exam-

 

ple,  if  the  base  address  switch  is  set  to  28,  the  next  nine 

 

modules will be addressed to 29, 30, 31, 32, 33, 34, 35, 36, and 37.

 

 The  module  is  shipped  in  Class  B  position,  remove  shunt  for  Class 
A.  When  operating  in  Class  A,  alternate  modules  are  paired  to-
gether  (+0/+1,  +2/+3,  +4/+5,  +6/+7,  +8/+9),  result-
ing  in  a  total  of  five  modules.  For  example,  if  the  base  address 
switch  is  set  to  28,  then  30,  32,  34  and  36  will  be  automatically  as-
signed to the modules while 29, 31, 33, 35 and 37 are available to be

 

used for other modules on the SLC. For Class A and B operation, DO NOT 
set the lowest address above 150, as the other modules will be assigned 
to nonexistent addresses.

F300-20-00 

I56-1873-005

This device complies with part 15 of the FCC Rules. Operation is subject to the fol-

lowing two conditions: (1) This device may not causeharmful interference, and (2) 

this device must accept any interference received, including interference that may 

cause undesired operation.

NOTE:

 This equipment has been tested and found to comply with the limits for a Class 

B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to pro-
vide reasonable protection against harmful interference in a residential installation. This 
equipment generates, uses and can radiate radio frequency energy and, if not installed 
and used in accordance with the instructions, may cause harmful interference to radio 
com-munications. However, there is no guarantee that interference will not occur in a 

C0226-00

C0227-00

particular  installation.  If  this  equipment  does  cause  harmful  inter-ference  to  radio  or 
television  reception,  which  can  be  determined  by  turning  the  equipment  off  and  on, 
the user is encouraged to try to correct the interference by one or more of the following 
measures:
 

– Reorient or relocate the receiving antenna.

 

– Increase the separation between the equipment and receiver.

 

–  Connect the equipment into an outlet on a circuit different from that to which 

the receiver is connected.

 

– Consult the dealer or an experienced radio/TV technician for help.