homevent HV PIV LOFT Скачать руководство пользователя страница 2

2.

INTRODUCTION

The HV PIV LOFT is a positive input ventilation unit suitable for installation in a loft. It continuously supplies fresh air through a single, Supply Air 

Valve, situated on the ceiling of the top floor in a central hallway or landing.

The unit is suitable for hanging using the cord provided or roof joist mounting.

WHAT IS IN THE BOX

1. Fan Unit with Pre-wired 3 Pin Plug and Lead 
2. Filter 
3. Flexible Duct
4. Control Box 
5. Control Box Connection Cable and Jack Plug

6. Supply Air Valve
7. Installer Label
8. Dyno-ties
9. Hanging Cord
10. Installation and Maintenance Instructions

PRE-INSTALLATION LOFT CHECK

Prior to installation the loft should be inspected to ensure there is adequate ventilation of the loft. The presence of daylight is a good indication of a loft 

that is suitably ventilated. Advice should be obtained if the loft is tightly sealed.

There should be no leaks from the house into the loft. Extractor fans should not discharge straight into the loft. Loft hatches and holes for ceiling lights 

should be adequately sealed.

The unit must not be installed in a loft space that is open to another property’s loft space e.g. in a terraced home without a barrier between loft spaces.

TECHNICAL SPECIFICATIONS

• 

Acoustically lined, painted metal fan casing incorporating high efficiency mixed flow fan.

• 

Supplied with white painted metal Supply Air Valve.

• 

An ultra-quiet EC motor / fan assembly. 

• 

G4 filter fitted provided as standard with large surface area to provide long filter life and efficient filtration of incoming air.

• 

Supplied with quality flexible duct to connect fan unit and supply air valve.

• 

Single duct connection to supply fresh clean air without the need to create holes in external walls.

• 

Control box (HV-POT-10-TB) and cable supplied as standard.

• 

Power Supply 230V - 50 / 60Hz.

OPERATION

The HV PIV LOFT Unit can be set to operate in a number of different ways using the control box (HV-POT-10-TB) supplied which is connected to the 

Fan Unit using a supplied length of connection cable incorporating a jack plug. Wiring diagrams 2-7 which follow show the various control options 

possible and wiring diagrams for each.

Содержание HV PIV LOFT

Страница 1: ...ontact a qualified technician immediately Use original spare parts only for repairs The electrical system to which the device is connected must comply with applicable regulations Before connecting the product to the power supply or the power outlet ensure that The data plate voltage and frequency correspond to those of the electrical mains The electrical power supply socket is adequate for maximum...

Страница 2: ...Lofthatchesandholesforceilinglights shouldbeadequatelysealed The unitmustnotbeinstalledin a loftspacethatis open toanotherproperty sloftspacee g inaterracedhomewithoutabarrierbetweenloftspaces TECHNICAL SPECIFICATIONS Acoustically lined painted metal fan casing incorporating high efficiency mixed flow fan Supplied with white painted metal Supply Air Valve An ultra quiet EC motor fan assembly G4 fi...

Страница 3: ...ply Air Valve should not be located within 1 metre of a smoke or CO detector or heating thermostat The unit can be suspended using the cord provided or mounted onto the roof joints Please ensure that there is a least 150mm clear all around the unit including the bottom to allow air to enter the unit via the filter Please pay particular attention to make sure mineral wool or other loft insulation m...

Страница 4: ...a suitable 230 volt ac single phase 50 60Hz power supply Note If the unit is required to switch off when the loft temperatures is very high e g during hot summer days this can be achieved by the installer providing a suitable thermostatic switch to interrupt the mains power supply to the unit when the selected trigger temperature is reached with the switch switching power back on to the unit again...

Страница 5: ...5 Wiring Diagram 2 Continuous running at Normal Airflow set via VR2 RED BLACK BLUE VR2 SPEED ADJUSTER VR1 SPEED ADJUSTER HV POT 10 TB CONTROL BOX CABLE CONNECTED TO FAN USING JACK PLUG SUPPLIED LINK ...

Страница 6: ...2 with Boosted Airflow set via VR1 when triggered by suitable user control switch inside the home provided by installer RED BLACK BLUE VR2 SPEED ADJUSTER VR1 SPEED ADJUSTER HV POT 10 TB CONTROL BOX CABLE CONNECTED TO FAN USING JACK PLUG SUPPLIED USER CONTROL SWITCH C ...

Страница 7: ...2 with Reduced Airflow set via VR1 when triggered by suitable user control switch inside the home provided by installer RED BLACK BLUE VR2 SPEED ADJUSTER VR1 SPEED ADJUSTER HV POT 10 TB CONTROL BOX CABLE CONNECTED TO FAN USING JACK PLUG SUPPLIED USER CONTROL SWITCH C ...

Страница 8: ... when triggered by suitable humidistat or other IAQ switch inside the home provided by installer RED BLACK BLUE VR2 SPEED ADJUSTER VR1 SPEED ADJUSTER HV POT 10 TB CONTROL BOX CABLE CONNECTED TO FAN USING JACK PLUG SUPPLIED Suitable humidistat or other IAQ switch inside the home provided by installer C ...

Страница 9: ...rflow set via VR1 when triggered by suitable thermostatic switch in the roof space provided by installer RED BLACK BLUE VR2 SPEED ADJUSTER VR1 SPEED ADJUSTER HV POT 10 TB CONTROL BOX CABLE CONNECTED TO FAN USING JACK PLUG SUPPLIED Suitable thermostatic switch in the roof space provided by installer C ...

Страница 10: ...irflow set via VR1 when triggered by suitable thermostatic switch in the roof space provided by installer RED BLACK BLUE VR2 SPEED ADJUSTER VR1 SPEED ADJUSTER HV POT 10 TB CONTROL BOX CABLE CONNECTED TO FAN USING JACK PLUG SUPPLIED Suitable thermostatic switch in the roof space provided by installer C ...

Страница 11: ...ilation Rate I s Power Consumption W SFP Fully anti clockwise 0 0 0 10 clockwise 0 0 0 20 clockwise 22 2 0 09 30 clockwise 30 5 0 17 40 clockwise 36 10 0 28 50 clockwise 38 15 0 39 60 clockwise 44 18 0 41 70 clockwise 48 23 0 48 80 clockwise 54 32 0 59 90 clockwise 56 36 0 64 100 clockwise 58 40 0 69 To optimise air distribution and limit noise the installer must ensure that the front edge of the ...

Страница 12: ...te Set at VR1 l s Ventilation Rate Set at VR2 l s Method of Operation The Installer or Commissioning Engineer must explain to the home occupants how this unit ventilates their home the method of operation above and how the unit is serviced and maintained as described in the section which follows The Installer or Commissioning Engineer should take a copy of this completed document for their records...

Страница 13: ...urrounding ceiling by light dusting if required 3rd Service Within 1 year of previous service Vacuum clean filter if required and clean supply air valve and surrounding ceiling by light dusting if required 4th Service Within 1 year of previous service Change filter and clean supply air valve and surrounding ceiling by light dusting if required 5th Service Within 1 year of previous service Vacuum c...

Страница 14: ...tes kWh m2 a 21 5 Energy label No d Unit typology NRVU UVU e Type of drive Variable speed drive f Type of Heat Recovery System Absent g Thermal efficiency of heat recovery N A h Maximum flow rate m3 h 208 i Electric power input at maximum flow rate W 40 j Sound power level LWA dBA 24 k Reference flow rate m3 h 108 l Reference pressure difference Pa 199 m Specific power input SPI W m3 h 0 324 n1 Co...

Отзывы: