IM-182
Caution
Field application of Pipe Thread Sealant is
required. Failure to properly apply pipe thread
sealant could cause this unit to leak.
Figure 2
GR1060
2.2.3
Loosen ballast assembly door screw, remove two hinge
screws at the rear of the ballast assembly door on the outside of the
arm to remove ballast assembly door.
2.2.4
Connect the wires from the optical assembly to the wires
from the arm assembly. Connect green wire to green wire, white
wire to white wire, and black wire to black wire.
2.2.5
With ballast assembly door removed, attach and level
luminare to the pole using mounting bolt pattern at the rear of the
arm assembly. On units using a tenon fitter tighten set screws at the
base of the tenon fitter to 10-12 foot pounds. See figure 3.
2.2.6
Connect electrical supply wires to the terminal block inside the
arm assembly. The terminals are marked “L1” (line1). “G” (Ground).
“L2” (line2). If one of the supply wires is electrically neutral, it should
be connected to terminal “L2”.
2.2.7
Open the wire chamber cover by loosening the door screw.
Connect the male wiring harness connector from the optical assy. to
the female wiring harness connector from the ballast assy. close the
ballast compartment door and tighten the screw. See figure 4.
2.2.8
Tighten door screw on ballast assembly door to 10-12 foot
pounds. See figure 4.
2.2.9
Open lamp chamber by loosening the refractor door screw
and swing down refractor. Refer to Figure 1.
3. MAINTENANCE
3.1 Relamping and Cleaning.
3.1.1
Wipe off exterior dirt and debris.
3.1.2
Open lamp chamber by loosening the refractor door
screw and swing down refractor. Refer to Figure 1.
3.1.3
Remove lamp.
3.1.4
Wipe out the refractor interior with a clean dry cloth.
3.1.5
Install new lamp of correct wattage and type. Tighten
the lamp carefully but securely.
3.1.6
Close lamp chamber by swinging up the refractor and
tightening the refractor door screw.
3.1.7
Energize the luminaire. Check for proper operation.
3.2 Replacement Ballast Assembly.
3.2.1
Loosen ballast door screw at optical assembly end of
luminaire. Refer to Figure 4.
Figure 3
GR1101
Figure 4
GR2004
3.2.2
Swing down ballast assembly door with one hand and use
other hand to disconnect the male wiring harness connector.
3.2.3
Remove ballast assembly door refer to section 2.2.3
3.2.4
Unscrew (2) ballast mounting strap screws located to the rear
of the ballast assembly door they are the screws attaching the ballast
strap to the door assembly, remove ballast.
3.2.5
Unpack replacement ballast assembly. Check voltage
leads.
3.2.6
Replace the ballast assembly and reinstall the ballast-
mounting strap.
3.2.7
Reconnect the male wiring harness connector to the female
wiring harness connector, reattach the ballast door assembly and
swing ballast assembly door completely closed
3.2.8
Tighten ballast door screw to 10-12 ft.-lbs.
3.2.9
Energize the luminaire. Check for proper operation.
4. Limited Warranty and Limitation of Liability
The Holophane limited warranty and limitation of liability is published
in the "Terms and Conditions" section of the current Holophane
buyer's guide, and is available from your local Holophane sales
representative.
®