![Hochiki TCH-B200 Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/hochiki/tch-b200/tch-b200_operating-instructions_2143455001.webp)
2-3-0-237/ISS5/SEP15
HOCHIKI TCH-B200
– ESP DEVICE PROGRAMMER
OPERATING INSTRUCTIONS
General Description
The TCH-B200 ESP Programmer is designed for use with the following products:
ALK / ALG-ALN
C
Analogue Photoelectric
Sensors
AIE-E
C
Analogue Ionisation Sensor
ATG-E
C
Analogue Heat Sensor
CHQ-WS2
C
Wall Sounder
ATJ / ACB-E
C
/ ACB-EW
2
Analogue Multi-Heat Sensors
CHQ-WSB/WSB2
C
Wall Sounder Beacons
ACC / ACA-E
C
Analogue Multi-Sensors
YBO-BS
C
Base Sounder
YBO-BSB/BSB2
C
Base Sounder Beacons
HCP Range
3
Analogue Manual Call Points
CHQ-CB/WB/AB
C
Addressable Beacons
CHQ-POM
3
Powered Output Module
CHQ-SIM
3
Single Input Module
CHQ-ARI
C
Addressable Remote Indicator
C = device clips straight onto Programmer, 2 = in conjunction with PL-2 Programming Lead, 3 = in conjunction with PL-3 Programming
Lead
The programmer is used to set the address of the above products for use with Hochiki ESP systems. The unit is
designed to be light, robust and easy to use and operates from a single PP3 size, heavy-duty battery which gives
the capacity for up to 8,000 operations.
Keys
The TCH-B200 has 3 operating keys, a middle blue key and lower left and right grey keys, these keys have the
following functions.
Left
(grey key) key - Power On - automatically reads the address of the fitted sensor - subsequent
operations of this key will advance the programmer address in units of 10.
Right
(grey key) key - Advances the programmer address display in units of 1. Also used as the Power Off
button.
Centre
(Blue key) key -
Stores the displayed address to the Sensor and is used to read the Sensor’s
analogue levels.
Operation - Address Setting
Locate the Device onto the programmer ensuring the 3 locating pips line up with the grooves in the
programmer.
Press the left (grey) key to switch the programmer on, a battery check message will be displayed followed by
the address of the device fitted (previously un-programmed devices will read 127).
Select the required address by incrementing the programmer display (left grey k
ey, 10’s, right grey key,
units). Whilst the display is showing an address different to that stored in the device, 3 dots will also flash.
Once the wanted address is displayed press the centre (blue) key to store the address in the device. Once
the address is correctly stored the 3 dots will cease to flash and the display will show the address set.
To program a CHQ-BS a PL-2 Programming Lead must be used, firstly connect the plug into the remote
(Blue)
www.acornfiresecurity.com