Hochiki SPC-E Скачать руководство пользователя страница 4

SPC-E Mounting Guidelines 

Page 4

 

Hochiki Europe (UK) Ltd 

2-3-0-798/ISS2/MAR08 

 

While synchronization is being established with the emitter and while the reception signal level is automatically 
adjusted, the monitor lamp (green) and fault lamp (yellow) on the receiver blink at intervals of three seconds.  If the 
system shifts successfully to the monitoring state, the monitor lamp (green) alone will blink.  It takes about two minutes 
for fire monitoring to begin after the receiver cover is closed.  In the meantime, take care not to block the beam. Once 
this has completed the cover should be locked in place with the supplied locking screw (please refer to Fig.5). 

 

After the SPC-E has completed its initialisation it should be tested using the filters supplied.  The range 1 filter relates to 
25%, the range 2 filter relates to 50% and the range 3 filter relates to 60%.  Firstly place the no alarm side of the filter in 
front of the SPC-E for at least one minute this should cause no fire or fault signals, if a fault occurs the amber LED will 
flash once every 3 seconds.  Next place the alarm side of the filter in front of the SPC-E for at least one minute.  During 
this time a fire alarm should occur and the red LED should illuminate continuously, if no alarm occurs, then the SPC-E is 
not operating as expected. 

 

Installation Data 

Allowable Misalignment Angle 

Emitter ± 

0.5° 

(max) 

Receiver ± 

1.0° 

(max) 

Guide Settings 

Range Sensitivity 

5 ~10m 

25% (1.25 dB) 

10 ~ 100m 

50% (3.01 dB) 

Approved Settings 

The SPC-E is EN54-12:2002 approved at the 25% and 50% sensitivity settings. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Hochiki Europe (UK) Ltd 

Grosvenor Road, Gillingham Business Park, 

Gillingham, Kent, ME8 0SA, England 

Telephone: +44(0)1634 260133     Facsimile: +44(0)1634 260132 

Email: [email protected] 

Web: www.hochikieurope.com 

 

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been 
made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be 
a complete and up-to-date description.  Please check our web site for the latest version of this document. 