Connect wiring to the bases as shown in the wiring diagrams that
follow. Detectors and bases may be mixed on the same initiating
loop as long as the number of two-wire powered detectors does not
exceed the specifications of the control panel (see Figure 2 below)

SMOKE DETECTOR DATA

BUILT-IN

TEST FEATURE

135°F(SLR-24H only)

30/ZONE 

17.7-30.0 VDC

HD3

FIG. 2

 BREAK WIRE RUN TO PROVIDE SUPERVISION

DO NOT LOOP WIRE UNDER  TERMINALS. 

CONNECT WIRING TO TERMINALS AS SHOWN. 

HSC-BASE

NS4-BASE

NS6-BASE

BASE

PHOTOELECTRIC

5V RIPPLE MAX.

FILTERED DC 

160 A

45   A

150 mA

15-33.0 VDC

NSTT-A100

30/ZONE 

HCP-1008E CONTROL PANEL

HEAT ELEMENT RATING

TYPE OF DETECTOR

SENSITIVITY TEST DEVICES

COMPATIBILITY IDENTIFIER

AVERAGE STANDBY CURRENT

MAX. SURGE CURRENT

MAX. ALARM CURRENT

VOLTAGE WAVEFORM

RATED VOLTAGE (4-WIRE)

WORKING VOLTAGE (2-WIRE)

DETECTORS

NOTE:

HD3

N/A

IONIZATION

200   A

5V RIPPLE MAX.

FILTERED DC 

40   A

150 mA

17.7-30.0 VDC

15-33.0 VDC

SPECIFICATIONS

BUENA PARK, CA 90621-2268

7051 VILLAGE DRIVE SUITE 100

HOCHIKI AMERICA CORPORATION

CAUTION

INSTALLATION INSTRUCTIONS

BUILT-IN

TEST FEATURE

SLR-835/-835W/

PHOTOELECTRIC

8.0~35.0 VDC

8.0~35.0 VDC

*

FILTERED DC 

15% RIPPLE MAX.

150 mA

200   A

55   A @ 24VDC

38   A @ 12 VDC

70   A @ 35VDC

HD5

30/ZONE 

30/ZONE

135/190°F

DCD-135/-135W/-135C

OF RISE HEAT

FIXED TEMP/RATE-

 35   A

HD3

160   A

*

5V RIPPLE MAX.

FILTERED DC 

TTA-1H

150 mA

17.7-30.0VDC

15.0-33.0VDC

DWG. # HA-06-060

*

CAUTION

BOX MOUNTING

NO

YES

NO

3" OCT

YES

YES

NO

4" OCT

YES

NO

YES

4" SQR

FIG. 1

(Pg.1 of 2, 06/16)

PART# 1700-09987

*

DETECTOR MODEL

DFE-190/-190W/DFE-190C

NON-CURRENT

NON-CURRENT

(57mA MAX)

37~45 mA @ 24V

(88.5mA @ 26.5VDC MAX)

(54 mA MAX.)

ALARM CURRENT

67~80 mA @ 24V

35~42 mA @ 24V

 NOTE: BASES/DETECTORS WITH THE "W" SUFFIX ARE WHITE IN COLOR.

HSC-221L/-221LW

NS6-100,100W

NS4-100,100W

BASE MODEL

HSC-220L/-220LW

HSC-224L/-224LW

TEMPERATURE RATING

MAX. ALARM CURRENT

DETECTOR TYPE

Pig Tail Lead

NS6-100

LISTED

DEVICE

END OF LINE 

190°F.

100 mA

FIXED TEMPERATURE

HB-63

FIXED TEMPERATURE

100 mA

135°F.

COMPATIBILITY

IDENTIFIER

HB-64

HB-62

LATCHING

INDICATION

YES

DFE HEAT DETECTORS

BASE STYLES

SPECIFICATIONS

NS6 SERIES

S1

HEAT DETECTOR DATA

(4 INCH BASE)

NS4 SERIES

HSC SERIES

S2 L2 L1

H1

H2

YES

YES

LIMITED

N/A

NO

LIMITED

N/A

NO

COMPATIBLE

CONTROL

PANEL

UL LISTED

SUPPLY

NEGATIVE

PANEL

POWER

HSC-220L

6

SIJ-24/-24C

SLR-24/-24C/-24V/-24VC

OF CONNECTIONS.

-24VN/-24H/-24HC

-190/-190W/-190C

-835C

55   A @ 24VDC

70   A @ 35VDC

38   A @ 12 VDC

200   A

150 mA

15% RIPPLE MAX.

FILTERED DC 

*

8.0~35.0 VDC

8.0~35.0 VDC

PHOTOELECTRIC

SLR-835H/-835HW

HD5

BUILT-IN

TEST FEATURE

30/ZONE 

135°F

N/A

DFE-135/-135W/DFE-135C

15°F./MIN.

TEMPERATURE RATING

MAX. ALARM CURRENT

100 mA

SPECIFICATIONS

DETECTOR TYPE

DETECTOR MODEL

HEAT DETECTOR DATA

DSC-EA HEAT DETECTORS

RATE OF RISE

DSC-EA/DSC-EAW

UL LISTED TEMPERATURE

6

L4

L3

5

6

3

4

1

2

S1

S2

H2

H1

L2 L1

L3 L4

L2

L1

L3

L4

(EXCEPT NS6-100)

NS6-100

(EXCEPT NS4-100)

NS4-100

(4 INCH BASE)

1

2

6

5

3

4

6

NS6 SERIES

(EXCEPT NS6-100)

For testing and cleaning information, refer to Page 2 of these instructions and
to Technical Bulletin HA-97 Conventional.  Also refer to NFPA-72 Chapters 2
and 7 for Automatic Fire Detector installation guidelines, testing, and
maintenance.

Use "3M" Weatherban # 606 non-flammable sealing compound to seal
field wiring conduit openings in the mounting back box.  Compliance with
this request may reduce the occurrence of the "STACK EFFECT".

These instructions apply to all Hochiki America detector bases that utilize an NS detector with LEDs to
indicate power, and alarm.

Install the bases in this instruction in accordance with applicable
NFPA standards, local codes, and the authorities having
jurisdiction.  Failure to follow these instructions may result in
failure of the detector to initiate an alarm condition.  Hochiki
America is not responsible for detectors that have been
improperly installed, tested, or maintained.

* When using a four-wire
   base full wave rectified

   AC can be used.

When mounting detector on

a wall, it must be between 4"
and 12" from the ceiling.

PHOTOELECTRIC

SLV-24V/-24N 

BUILT-IN

TEST FEATURE

30/ZONE 

17.7-30.0 VDC

HD3

5V RIPPLE MAX.

FILTERED DC 

45   A

150 mA

15-33.0 VDC

*

N/A

160   A

-24NW/SLV-24

Note:  The SLR-24V, SLV-24V and SOC-24V are suitable for installation in air velocities up to 4000ft./min.

  0°C ~ 37.8°C

(32°F ~ 100°F)

OPERATING TEMPERATURE

(14°F ~ 122°F)

-10°C ~ 50°C

 NOTE: BASES/DETECTORS WITH THE "C" SUFFIX ARE CANADIAN.

PHOTOELECTRIC

SOC-24V/-24VN 

30/ZONE 

HD3

FILTERED DC 

59   A

150 mA

*

N/A

160   A

8.0~35.0 VDC

8.0~35.0 VDC

15% RIPPLE MAX.

SOC-24VW

5

6

5

1

2

1

2

BUILT-IN

TEST FEATURE