  INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 

                                                                                         

 

Hochiki America Corporation 
7051 Village Drive, Suite 100 
Buena Park, CA 90621-2268 
 

DWG # HA-06-060, Rev 11/21 
PAGE 2 of 2 
PART # 1700-09987 
 

NS6-100

DEVICE

END OF LINE 

LISTED

NS6-220/-221/-224

NS4-220/-221/-224

UL LISTED

CONTROL

PANEL

PANEL

POWER

SUPPLY

NEGATIVE

UL LISTED

2-WIRE OPERATION

2-WIRE RELAY OPERATION

USE ONLY WITH A UL LISTED ACCESSORY

RATED 20MA MAX, 24VDC MIN.

MODELS: RAI-LED

BLU
GRN

GRY

YEL

PUR

ORN

H1 

ORN

YEL

H2 

HSC-220/-221/-224

LISTED 

RELAY

END OF LINE

PAM-4

HSC-4R/-4R12

PUR

CONTROL

PANEL

INITIATING

CIRCUIT

HSC-4R/-4R12

4-WIRE OPERATION

1 2

6 5

4

3

1 2

6 5

4

3

1 2

6 5

4

3

UL

LISTED

POWER

SUPPLY

12VDC

use

HSC-4R12

or

24VDC

use

HSC-4R

HSC-XXXR SERIES

CONTACTS, SHOWN

WITH POWER OFF,

NORMAL OPERATION.

L3 L4

H2

H1

L1

L2

S2

S1

L3 L4

H2

H1

L1

L2

S2

S1

L3 L4

H2

H1

L1

L2

S2

S1

L3 L4

H2

H1

L1

L2

S2

S1

(+)

(-)

(C)

(NC)

HSC-4R/-4R12

CONTACTS, SHOWN

WITH POWER OFF,

NORMAL OPERATION.

2A, 30VDC

1A, 120VAC

2A, 30VDC

1A, 120VAC

(+)

(-)

WIRING TERMINALS

NS4-100 AND NS6-100

ARE IDENTICAL

LISTED

DEVICE

END OF LINE 

LISTED END

OF LINE

DEVICE

 

Go/No-Go testing can be used to confirm a detector is within its sensitivity limits and operating normally 
 
GO/NO-GO TESTING SOC-24V/-24VW 

1.

 

Hold a magnet (2lb pull force min) on the detector as shown. 

2.

 

For go: The detector should alarm and latch red within 10 seconds.  
When using Alarm Verification, may take up to 30 seconds. 
For no-go: The detector will blink red every 3 seconds and 
never alarm or latch red. 

3.

 

Upon reset, the smoke detector LED should blink Green every 
3 seconds. If the detector blinks red, it should be replaced. 

 
GO/NO-GO TESTING SOE-24V/-24V (WHT)/-24H/-24H (WHT) 

1.

 

Place the Hochiki America Test Magnet to align the LED marking as shown. 

2.

 

For go: The detector will blink red every second. Holding the magnet 
in position for at least 13 seconds will cause the detector to alarm  
with the red LED latched on. 
For no-go: After at least 13 seconds, the detector will continue to  
blink red every 3 seconds and never alarm or latch red. 

3.

 

Upon reset, the smoke detector LED should blink Green every 
3 seconds. If the detector blinks red, it should be replaced. 

SOC-24V Magnet Placement

Hold Magnet
      Here

LED

SOE-24V Magnet Placement

L E D