INSTALLATION AND MAINTENANCE INSTRUCTIONS
Hochiki America Corporation
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268
DWG # HA-06-060, Rev 11/21
PAGE 2 of 2
PART # 1700-09987
NS6-100
DEVICE
END OF LINE
LISTED
NS6-220/-221/-224
NS4-220/-221/-224
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
NEGATIVE
UL LISTED
2-WIRE OPERATION
2-WIRE RELAY OPERATION
USE ONLY WITH A UL LISTED ACCESSORY
RATED 20MA MAX, 24VDC MIN.
MODELS: RAI-LED
BLU
GRN
GRY
YEL
PUR
ORN
H1
ORN
YEL
H2
HSC-220/-221/-224
LISTED
RELAY
END OF LINE
PAM-4
HSC-4R/-4R12
PUR
CONTROL
PANEL
INITIATING
CIRCUIT
HSC-4R/-4R12
4-WIRE OPERATION
1 2
6 5
4
3
1 2
6 5
4
3
1 2
6 5
4
3
UL
LISTED
POWER
SUPPLY
12VDC
use
HSC-4R12
or
24VDC
use
HSC-4R
HSC-XXXR SERIES
CONTACTS, SHOWN
WITH POWER OFF,
NORMAL OPERATION.
L3 L4
H2
H1
L1
L2
S2
S1
L3 L4
H2
H1
L1
L2
S2
S1
L3 L4
H2
H1
L1
L2
S2
S1
L3 L4
H2
H1
L1
L2
S2
S1
(+)
(-)
(C)
(NC)
HSC-4R/-4R12
CONTACTS, SHOWN
WITH POWER OFF,
NORMAL OPERATION.
2A, 30VDC
1A, 120VAC
2A, 30VDC
1A, 120VAC
(+)
(-)
WIRING TERMINALS
NS4-100 AND NS6-100
ARE IDENTICAL
LISTED
DEVICE
END OF LINE
LISTED END
OF LINE
DEVICE
Go/No-Go testing can be used to confirm a detector is within its sensitivity limits and operating normally
GO/NO-GO TESTING SOC-24V/-24VW
1.
Hold a magnet (2lb pull force min) on the detector as shown.
2.
For go: The detector should alarm and latch red within 10 seconds.
When using Alarm Verification, may take up to 30 seconds.
For no-go: The detector will blink red every 3 seconds and
never alarm or latch red.
3.
Upon reset, the smoke detector LED should blink Green every
3 seconds. If the detector blinks red, it should be replaced.
GO/NO-GO TESTING SOE-24V/-24V (WHT)/-24H/-24H (WHT)
1.
Place the Hochiki America Test Magnet to align the LED marking as shown.
2.
For go: The detector will blink red every second. Holding the magnet
in position for at least 13 seconds will cause the detector to alarm
with the red LED latched on.
For no-go: After at least 13 seconds, the detector will continue to
blink red every 3 seconds and never alarm or latch red.
3.
Upon reset, the smoke detector LED should blink Green every
3 seconds. If the detector blinks red, it should be replaced.
SOC-24V Magnet Placement
Hold Magnet
Here
LED
SOE-24V Magnet Placement
L E D