Hochiki HF-24 UV Flame Detector – Installation Manual
11
Detector Specifications
Detectable Area
Specification
Ordering code;
HF-24
Operating voltage:
15-30 Vdc (Nominal rating 24Vdc)
Standby current:
200
μ
A at 24Vdc
Detection angle:
120
°
Cone
UV sensitivity range:
185 to 260 nm
Maximum current in alarm state:
250mA(without base)
Operating temperature range:
-10
°
C to +50
°
C
Maximum humidity:
95%RH - Non condensing (at 40
°
C)
Colour and case material:
Ivory ACS
Weight:
150g (210g with base)
©
1995 Hochiki Europe (UK) Ltd DS0204/ISS1/DEC95