Hochiki Europe (UK) Ltd – HE-PSU(1.25) Power Supply Installation Manual 

Page 3 of 4 

2-3-0-995/ISS1/OCT07 

 

Suitable cables should be brought into the cabinet using the knockouts provided, making sure that tails are 
long enough to reach the relevant terminals.  The screen or drain wire should be bonded to earth at one 
location only, it should be continuous throughout the circuit.  Terminals will accept one single or 
stranded conductor up to 2.5 mm

2

2.0 COMMISSIONING 

2.1 Mains Connection 

The mains is connected to the PSU via a fused terminal block marked with live, neutral and earth 
symbols.  It is imperative that the equipment is soundly earthed and this connection should be made 
and checked first. 
 
Following connection of the live and neutral cables and with no other connections made, the unit should be 
powered and the battery output measured at around 28 volts DC. 

2.2 Load Connection  

Terminals are provided for connection to the load and are  and -.  The voltage at these 
terminals under normal conditions (i.e. off load) should be around 28.5 to 29 volts.  With the mains 
power off, connect the load cables. 
 
Double check the load connection for correct polarity before switching on mains.  After switching on 
mains check the voltage at the load for correct polarity. 
 
Do not connect or disconnect the wiring to the load terminals with mains or battery power on. 

2.3 Fault/Healthy Connection 

Switched -VE outputs are available for signalling of power fault and power healthy indication marked PO 
(power on) and PF (power fault).  Under normal circumstances (mains and battery connected and fuses 
intact) the -VE appears at the PO terminal. 
 
Failure of the mains or battery supply will transfer the -VE to the PF terminal. 
 
A volt free changeover contact is also available for fault/healthy signalling which can be used to switch 
other voltages or signals 

2.4 Battery Connection 

An output is provided via flying leads with 0.25 inch spade receptacles for connection to sealed lead acid 
rechargeable batteries.  Normally two 12 volt batteries are connected in series and then to the charger. 
 
Before connecting the batteries measure the output voltage on the leads.  It should be 28 volts ±0.1 
volt.  If the voltage differs from this, adjust it to the correct level using the control on the PCB (this may 
vary from the factory setting due to variations in mains supply voltage). 
 
It is very important that the correct polarity is observed before connecting the batteries as the wrong 
polarity connection will blow the charging fuse and may damage the unit. 
With the batteries connected and the mains on the fault contact should show continuity between the “C” 
and “NC” terminals.  With the battery on mains disconnected the fault contact should show continuity 
between the “C” and “NO” terminals. 
 
With the battery connected switch off the mains and ensure that a supply is present at the load terminals. 

3.0 OPERATION & MAINTENANCE 

Under normal circumstances the power supply requires no attention and will transfer automatically to 
battery supply in the event of a mains failure.  Periodic checks should be made however to ensure 
maximum life of the sealed lead acid battery. 
 
To do this, disconnect the battery and using a calibrated voltmeter ensure that the voltage on the 
battery leads is 28 volts ±0.1 volt.  Adjust this if necessary using the control on the PCB. 