0400-01046
PART NUMBER
E.O.L. DEVICE
U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046
Maximum Distance Between
Module and EOL Device
14 AWG 1500 Ft.
16 AWG 900 Ft.
18 AWG 550 Ft.
PLACE THE FRCME-P
TYPICAL WIRING FOR N/C CONTACTS ONLY
TO A COMPATIBLE LISTED CONTROL PANEL
TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED
FIGURE 2A
DO NOT CONNECT MORE THAN ONE N/C CONTACT TO AN INPUT.
CAUTION!
0400-01046
PART NUMBER
E.O.L. DEVICE
U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046
HA-06-102
(PG 2 OF 3 12/03)
PART# 1700-09959
DWG. #
EXPLODED VIEW OF MOUNTING
OPTION USING FRCME-P
(SINGLE GANG SHOWN)
MODULE INTO ANY BACK BOX
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B (FOR WIRING LENGTH REFER TO TABLE 1)
OUT TO
NEXT
MODULE
MODULE
NEXT
OUT TO
AND INHERENTLY POWER LIMITED.
ALL WIRING SHOWN IS SUPERVISED
ALL WIRING SHOWN IS SUPERVISED
AND INHERENTLY POWER LIMITED.
IN-A
SC (IN)
IN-B
S (OUT)
WHT
SC (OUT)
BLK
S (IN)
RED
SER. NO. XXXXXXXXX
S5694
DCP-FRCME-P
ISSUE NO. AH-9765
SIGNALING DEVICE
S
RED
S (IN)
BLK
SC (OUT)
WHT
S (OUT)
IN-B
SC (IN)
IN-A
SIGNALING DEVICE
ISSUE NO. AH-9765
DCP-FRCME-P
S5694
SER. NO. XXXXXXXXX
S
TYPICAL WIRING FOR N/O CONTACTS ONLY
INITIATING OR SUPERVISORY ON THE SAME MODULE
DEVICES MAY BE USED . DO NOT MIX FIRE ALARM
ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE
COMPATIBLE
U.L. LISTED
SC
PANEL
CONTROL
SC
S
U.L. LISTED
COMPATIBLE
CONTROL
PANEL
S
SC
SC
FIGURE 2
TABLE 1: WIRING LIMITATIONS