Storage Temperature

-30°C (-22°F) ~ 70°C (158°F)

4.2"W X 4.7"H X 1.4"D
Approximately 3.0 ounces

Color and mode -  selected and programmed by Control Panel's software

                  (pulsing, steady, etc.)

bi-color LED    -  Green and Red

Up to 90% RH non-condensing

HOCHIKI AMERICA CORPORATION

7051 VILLAGE DRIVE, SUITE 100

BUENA PARK, CA 90621-2268

Dimensions

Environment
Visual Indicator

(status LED)

Max relative humidity

Weight

(FRCME-4 only)

Indoor use only

(PG 1 OF 3  12/03)

DWG. #

HA-06-102

PART# 1700-09959

Alarm and response: 30mA (in 20 ms.)

U.L.listed EOL device Part No. 0400-01046 (10K OHM 1/4W)

Surge current: 30mA (in 5 ms.)

No Alarm and no response: 660   A

0°C (32°F) ~ 49°C (120°F)

               CAUTION !!!

If this module will be installed in an 
existing operational system, inform the 
operator and local authority that the system 

will be temporarily out of service.  
Disconnect power to the control panel 
before installing the module.

Note:

R

adio 

F

requency 

I

nterference and 

E

lectro-

M

agnetic 

I

nterference are sources 

of noise that can adversely affect the fire alarm systems installation. 

When installing fire alarm system devices, avoid placing devices or 
wiring close to potential noise sources such as:

• 

Transmitters or antennas;

 Ballast lighting;

 Electrical motors;

 Large power transformers;

 Large machines.

Avoid running SLC circuit in the same conduit as power lines. Utilize twisted 
pair and shielded wire in environments where excessive noise is expected.

INSTALLATION INSTRUCTIONS FOR DCP-FRCME-EEPROM FAST RESPOND CONTACT 

MONITORING MODULE

The information contained in this installation instruction is a quick reference guide. For detailed system 

information refer to the panel manufacturers installation manual. This instruction is generic and will not address 

specific programming procedures.

This instruction applies to the DCP EEPROM Fast Response Contact 

Monitoring Module (FRCME) which is to be connected to a DCP 

Signaling Line Circuit (SLC).  Typical applications are manual pull 

stations, water flow devices or any dry contact alarm device, either 

FRCME-P is shown in Fig. 2, the FRCME-4 is shown in Fig. 3.  All 

3) The address must be set on the FRCME-4 before the cover plate is 

Absolute Maximum

Average Current 

Maximum Current

Supply Voltage Nominal

Applied Voltage

Consumption

Consumption

End of Line Device for Input

Operating Temperature Range

CAUTION !!!

TO ENSURE PROPER 

OPERATION  CONNECT THIS 

MODULE TO A COMPATIBLE 

FIRE CONTROL PANEL ONLY.  

REFER TO PANEL 

INSTRUCTIONS FOR PROPER 

CONNECTION AND 

COMPATIBILITY.

attached (see Fig. 1).  

S, SC:  41 VDC

550  A (Typical)

S, SC:  33 VDC

GENERAL DESCRIPTION:

N/O or N/C contacts can be monitored. 

MOUNTING REQUIREMENTS:

The DCP FRCME Module has two mounting options.  The 

the modules will follow Fig. 2A & 3A for wiring connections.

NOTE: All wiring must conform to local codes, ordinances and 

1) Install module wiring in accordance with the job drawings and 

appropriate wiring diagram (see Fig. 2A & 3A).

2) Secure the module to a U.L. listed electrical box (supplied by 

installer) as shown in Fig. 2, 3.

WIRING:

regulations.

FRCME-P PROGRAMMING CONNECTIONS

To program the FRCME-P, 

connect the red alligator clip to 

the S(In) wire and the black 

alligator clip to the SC(In) wire 

(see figure 1A).  For proper 

address setting, polarity must 

be observed.

SER. NO. XXXXXXXXX

S5694

DCP-FRCME-P

ISSUE NO. AH-9765

SIGNALING DEVICE

FIGURE 1A.

IN-B

WHT

IN-A

SC (IN)

S (OUT)

SC (OUT)

BLK

S (IN)

RED

(BLACK)

TO PROGRAMMER

(RED)

CONNECTION AND INDICATOR

STATUS LED

FIGURE 1.

 FRCME-4 PROGRAMMING CONNECTIONS

FRCME-4 MODULE ADDRESS PROGRAMMING

PROGRAMMING PLUG

(NON-POLARIZED)

TO PROGRAMMER