Hochiki CHQ-WS2 Скачать руководство пользователя страница 3

2-3-0-626/ISS6/MAY11

 

CHQ-WS2 Operating Voltage 17 ~ 41 Vd.c

Table 2 

Tone 
Number  

Tone 
Description  

Graphic 
Representation  

Tone 
Number 

Tone 
Description  

Graphic 
Representation  

Sounder Off  

  

19  

800 Hz : 250 ms 
970 Hz : 250 ms  

  

925 Hz : 250 ms 
628 Hz : 250 ms  

 

20  

2850 Hz Continuous  

  

925 Hz Continuous  

 

21  

2400 Hz : 250 ms 
2850 Hz : 250 ms  

  

628 Hz Continuous  

 

22  

800 Hz : 500 ms 
970 Hz : 500 ms  

  

(French)  
554 Hz : 100 ms 
440 Hz : 400 ms  

 

23  

2850 Hz : 500 ms 
Off : 500 ms  

  

(Swedish)  
660 Hz : 150 ms 
Off : 150 ms  

 

24  

925 Hz : 250 ms 
Off : 1000 ms  

  

925 Hz : 150 ms 
Off : 600 ms  

 

25  

970 Hz Continuous  

  

7  

670 Hz : 250 ms 
845 Hz : 370 ms  

 

26  

660 Hz : 1800 ms 
Off: 1800 ms  

  

8  

Whoop  
500 Hz - 1200 Hz 3000 ms 
Off : 500 ms  

 

27  

660 Hz : 6500 ms 
Off : 13000 ms  

  

9  

1200 Hz : 500 ms 
500 Hz : 500 ms  

 

28  

660 Hz Continuous  

  

10  

970 Hz : 500 ms 
Off : 500 ms  

 

29  

554 Hz : 500 ms 
440 Hz : 500 ms  

  

11  

Sweep  
800 Hz - 970 Hz  
over 140 ms  (7 Hz)  

 

30  

660 Hz : 500 ms 
Off : 500 ms  

  

12  

Sweep  
800 Hz - 970 Hz  
over 1000 ms  (1 Hz)  

 

31  

2850 Hz : 150 ms 
Off : 100 ms  

  

13  

Sweep  
800 Hz - 970 Hz  
over 20 ms  (50 Hz)  

 

32  

Sweep  
2400 Hz – 2850 Hz  
over 20 ms (50 Hz)  

  

14  

Sweep  
2400 Hz – 2850 Hz  
over 140 ms  (7 Hz)  

 

33  

Sweep  
800 Hz – 970 Hz  
over 500 ms  (2 Hz)  

  

15  

Sweep  
2400 Hz – 2850 Hz  
over 1000 ms  (1 Hz)  

 

34  

988 Hz : 250 ms 
645 Hz : 250 ms  

  

16  

Sweep  
300 Hz – 1200 Hz  
over 1000 ms  (1 Hz)  

 

35  

510 Hz : 250 ms 
610 Hz : 250 ms  

  

17  

ISO8201 : 970 Hz : 500 ms  

 

36  

Sweep  
800 Hz – 970 Hz  
over 110 ms (9 Hz)  

  

18  

ISO8201 : 2850 Hz : 500 ms  

 

37  

Sweep  
800 Hz – 970 Hz  
over 330 ms (3 Hz)  

 

Содержание CHQ-WS2

Страница 1: ...ether with the amount of current drawn when operated The units are also capable of utilising a number of different EN54 3 Approved tones these are listed in Table 2 page 3 The tone of the sounder and the volume level is selected and controlled by the control panel therefore check with the control panel manufacturer for options and default values available The sounder and beacon elements of the CHQ...

Страница 2: ...d surface using appropriate fixings For correct wiring of the each base type refer to Fig 4 When installing either of these units in exterior locations use the WS2 WPK Weather Proofing Kit The kit consists of a weatherproof back box and two gaskets which must be used in conjunction with either mounting base to maintain the IP rating see Fig 3 For further information refer to the WS2 WPK Weather Pr...

Страница 3: ... Hz 1800 ms Off 1800 ms 8 Whoop 500 Hz 1200 Hz 3000 ms Off 500 ms 27 660 Hz 6500 ms Off 13000 ms 9 1200 Hz 500 ms 500 Hz 500 ms 28 660 Hz Continuous 10 970 Hz 500 ms Off 500 ms 29 554 Hz 500 ms 440 Hz 500 ms 11 Sweep 800 Hz 970 Hz over 140 ms 7 Hz 30 660 Hz 500 ms Off 500 ms 12 Sweep 800 Hz 970 Hz over 1000 ms 1 Hz 31 2850 Hz 150 ms Off 100 ms 13 Sweep 800 Hz 970 Hz over 20 ms 50 Hz 32 Sweep 2400 ...

Страница 4: ...ut notice Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe UK Ltd to be a complete and up to date description Please check our web site for the latest version of this document YBO BSB Setting Corresponding CHQ WSB Level Sound Level dB A Current mA Sound Level dB A Current mA Off Quiesce...