2-3-0-1574/ISS1/JUNE14
*
2
Dependent on the utilisation of the WS2-WPK Weather Proofing Kit.
Setting the Address
The CHQ-CB must have its address set before system operation. Using an installation plan that shows the proper
location for each device, find the address for the CHQ-CB to be installed. Check that the address and location on the
plan match correctly. Address is any number from 1 to 127. For address setting, use the Hochiki TCH-B100 Hand Held
Programmer and write the address number on the beacon after setting. When address changing, renew the number on
the label. See the TCH-B100 instructions (2-3-0-237) for further details of the setting method.
Wiring and Locking Mechanism
The bases used with the beacon should be wired as
shown in Fig 2 below. The CHQ-CB can also be
locked onto the relevant base by removing a plastic
lug on the underside of the beacon, please refer to
Fig 1. The beacon can only then be removed by
using a special Removal Tool (TSC-SRT) which is
available from Hochiki Europe (UK) Ltd.
NOTE: For further details of external power requirements please see application note
AP131
A
: Loop (+)
B
: Loop (-)
C
: Cable Screen
D
: EXT Power+ (if used)
E
: EXT Power- (if used)
CHQ-CB/WL
CHQ-CB(WHT)/WL
CHQ-CB(RED)/WL
CHQ-CB(WHT)/WL-HFP
CHQ-CB(RED)/WL-HFP
0832-CPR-F0560/14
14
EN54-23
CHQ-CB/WL-15
CHQ-CB(WHT)/WL-15
CHQ-CB(RED)/WL-15
CHQ-CB(WHT)/WL-15-HFP
CHQ-CB(RED)/WL-15-HFP
0832-CPR-F0559/14
14
EN54-23
CHQ-CB/RL
CHQ-CB(WHT)/RL
CHQ-CB(RED)/RL
CHQ-CB(WHT)/RL-HFP
CHQ-CB(RED)/RL-HFP
0832-CPR-F0561/14
14
EN54-23
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England
Telephone: +44(0)1634 260133
Facsimile: +44(0)1634 260132
Email: [email protected]
Web: www.hochikieurope.com
Hochiki Europe (UK) Ltd. reserves the right to alter
the specification of its products from time to time
without notice. Although every effort has been
made to ensure the accuracy of the information
contained within this document it is not warranted
or represented by Hochiki Europe (UK) Ltd. to be a
complete and up-to-date description. Please
check our web site for the latest version of this
document.
Fig 1
Remove tab carefully using a
pair of pliers
NOTE:
Loop Voltage range 17
– 41
Vdc
Maximum current for remote
indicator is 10 mA.
Base fixing centres are 48 mm
to 74 mm
Maximum wire thickness is 2.5
mm
2
/terminal
If external power is used it must
be 20-28 Vdc
If external power is used,
remote indicator is not available
Fig. 2