2-3-0-1574/ISS1/JUNE14 

*

Dependent on the utilisation of the WS2-WPK Weather Proofing Kit. 

Setting the Address

 

 
The CHQ-CB must have its address set before system operation.  Using an installation plan that shows the proper 
location for each device, find the address for the CHQ-CB to be installed.  Check that the address and location on the 
plan match correctly.  Address is any number from 1 to 127.  For address setting, use the Hochiki TCH-B100 Hand Held 
Programmer and write the address number on the beacon after setting.  When address changing, renew the number on 
the label.  See the TCH-B100 instructions (2-3-0-237) for further details of the setting method. 

 

Wiring and Locking Mechanism 

The bases used with the beacon should be wired as 
shown in Fig 2 below.  The CHQ-CB can also be 
locked onto the relevant base by removing a plastic 
lug on the underside of the beacon, please refer to 
Fig 1. The beacon can only then be removed by 
using a special Removal Tool (TSC-SRT) which is 
available from Hochiki Europe (UK) Ltd. 

 

 

NOTE: For further details of external power requirements please see application note  
AP131

 

 

A

: Loop (+)  

B

: Loop (-)  

C

: Cable Screen  

D

: EXT Power+ (if used)  

E

: EXT Power- (if used) 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

CHQ-CB/WL 

CHQ-CB(WHT)/WL 

CHQ-CB(RED)/WL 

CHQ-CB(WHT)/WL-HFP 

CHQ-CB(RED)/WL-HFP 

0832-CPR-F0560/14 

14 

EN54-23 

CHQ-CB/WL-15 

CHQ-CB(WHT)/WL-15 

CHQ-CB(RED)/WL-15 

CHQ-CB(WHT)/WL-15-HFP 

CHQ-CB(RED)/WL-15-HFP 

0832-CPR-F0559/14 

14 

EN54-23 

CHQ-CB/RL 

CHQ-CB(WHT)/RL 

CHQ-CB(RED)/RL 

CHQ-CB(WHT)/RL-HFP  

CHQ-CB(RED)/RL-HFP 

0832-CPR-F0561/14 

14 

EN54-23 

 

Hochiki Europe (UK) Ltd 
Grosvenor Road, Gillingham Business Park, 
Gillingham, Kent, ME8 0SA, England 
Telephone: +44(0)1634 260133     
Facsimile: +44(0)1634 260132 
Email: [email protected] 
Web: www.hochikieurope.com

 

Hochiki Europe (UK) Ltd. reserves the right to alter 
the specification of its products from time to time 
without notice. Although every effort has been 
made to ensure the accuracy of the information 
contained within this document it is not warranted 
or represented by Hochiki Europe (UK) Ltd. to be a 
complete and up-to-date description.  Please 
check our web site for the latest version of this 
document. 

 

Fig 1 

Remove tab carefully using a 
pair of pliers 

NOTE: 

 

Loop Voltage range 17 

– 41 

Vdc 

 

Maximum current for remote 
indicator is 10 mA. 

 

Base fixing centres are 48 mm 
to 74 mm 

 

Maximum wire thickness is 2.5 
mm

2

/terminal 

 

If external power is used it must 
be 20-28 Vdc 

 

If external power is used, 
remote indicator is not available 

Fig. 2 