number on the label of the sensor after setting. When address changing, renew the number on the label. See the 
instruction of the appropriate address programmer TCH-B100 about detail of setting method.  Note that to program the 
ACB-EW with the TCH-B100 address programmer, a programming lead (PL-2) must be used (jack plug to croc-clips). 

Wiring and Head Locking Mechanism 

The bases should be wired as shown in figure 1 
below.  Note that the ACB-EW features flying leads 
for connection to the loop and is supplied with its 
own fixing base.  The ESP range of Sensors can 
also be locked onto the relevant bases by removing 
a plastic lug on the underside of the sensor, please 
refer to figure 1. The Sensor can then only be 
removed by using a special removal tool, which is 
available from Hochiki Europe (UK) Ltd.   

 

A

: Loop (+)  

B

: Loop (-)  

C

: Cable Screen 

 

 

 

 

ACA-E 0832-CPD-0114 

05 

EN54-5 Point type heat detectors 
EN54-7 Point type smoke detectors 

ACB-E 

0832-CPD-0122 

05 

EN54-5 Point type heat detectors 

ACB-EW 

0832-CPD-0123 

05 

EN54-5 Point type heat detectors 

AIE-E, AIE-E(NP) 

0832-CPD-0124 

05 

EN54-7 Point type smoke detectors 

ALG-EN 

0832-CPD-0612 

08 

EN54-7 Point type smoke detectors 

 

Protocol specified in TI/006 

ALG-E, ALG-E(NP) 

0832-CPD-0110 

05 

EN54-7 Point type smoke detectors 

Fig.1 

Remove tab carefully 
using a pair of pliers 

NOTE: 

‰

 

Maximum current for remote 
indicator is 10mA. 

‰

 

Base fixing centres are 48mm to 
74mm 

‰

 

Maximum wire thickness is 
2.5mm

2

/terminal 

Fig.2 

NOTE:  
Suitable 
waterproof 
crimps MUST 
be used 
between flying 
leads and loop 
cables.  