Hochiki America FN-400ULX Скачать руководство пользователя страница 3

- 3 - 

 

4.

 

Connect devices to be powered to terminals marked [+ DC –] 

(Fig. 2, pg. 3)

5.

 

Measure output voltage before connecting devices. This helps avoiding potential  damage. 

6.

 

For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the 

loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. 

Connect battery to terminals marked [+ BAT –] 

(Fig. 2, pg. 3)

. Use two (2) 12VDC batteries connected in series for 

24VDC operation (battery leads included). 

7.

 

Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 2a, pg. 3) 

supervisory relay outputs. 

Note: 

When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be 

utilized to visually indicate that AC power is on. To delay report 6 hours cut “AC Delay” jumper 

(Fig. 2b, pg. 3)

8.

 

Please ensure that the door is secured with the provided cam lock. 

Wiring: 

Use 14 AWG or larger for all power connections. 

Note: 

Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery). 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

Output Voltage Test: 

Under normal load conditions, the DC output voltage should be checked for proper voltage level 

(

refer to Power Supply Voltage Output Specifications chart

). 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified voltage both at battery 

terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires. 

Note: 

Maximum charging current under discharge is 0.7 amp. 

Note: 

Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. 

CAUTION: De-energize unit prior to servicing. For continued protection against risk of 

Fig. 2 

electric shock and fire hazard replace fuse with the same type and rating. 

Do not expose to rain or moisture. 

 
 
 
 

 

Fig. 

 
 
 
 
 
 
 

 

Fig. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Keep power-limited wiring separate from non power-limited. 

Use minimum 0.25" spacing. 

2a 

Door 

Green 

Lead 

Wire 

Strap 

(from 

Enclosure 

to Door) 

Do Not Touch 

Exposed Metal Parts 

Bat Fail NC C NO NC C NO Fail 

Battery & AC Supervision 

Circuit 

(power-limited) 

115VAC 

power mains 

non power- 

limited 
Class 1 

Fig. 2c 

2b 

AC Delay 

Opened - 24V 

Closed - 12V 

SW1 

J1 

15 

 
 

 

+  

BAT --- 

DC --- 

Battery connection 

(non power-limited) 

DC Output to devices 

(power-limited) 

Battery 1 

Battery 2 

12VDC Rechargeable Battery 

(optional) 

12VDC Rechargeable Battery 

(optional) 

CAUTION: Optional rechargeable stand-by batteries must match 

the power supply output voltage setting. 

 
 
 
 
 
 
 
 
 
 
 

 

AC 

O

p

en

ed

 - 

24

V

 

C

lo

se

d

 - 

12

V

 

S

W

J1

 

15

A

 2

50

V

 

R

is

o

f F

ire

R

e

pl

ac

F

u

s

es

 

A

M

ar

ke

d

 

A

C

 D

C

 B

at

 

5A

 2

50

V

 

L

 G

 N

 

B

a

t F

ai

l N

C

 C

 N

O

 N

C

 C

 N

O

 A

C

 F

ai

A

C

 D

e

la

Отзывы: