Rev. 101112
FN-300ULX
Power Supply/Charger
Installation Guide
Altronix Corp.
140 58th St. Brooklyn, NY
Страница 1: ...Rev 101112 FN 300ULX Power Supply Charger Installation Guide Altronix Corp 140 58th St Brooklyn NY ...
Страница 2: ...rm 2 5 amp 24VDC 12AH Battery Stand by 200mA Alarm 2 5 amp 24VDC 40AH Battery Stand by 2 5 amp Alarm 2 5 amp Stand by 1 0 amp Alarm 2 5 amp Stand by 300mA Alarm 2 5 amp Installation Instructions The unit should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all applicable Local Codes 1 Mount unit in the desired location Mark and predrill holes in...
Страница 3: ...proper voltage level refer to Power Supply Voltage Output Specifications chart Battery Test Under normal load conditions check that the battery is fully charged check specified voltage both at battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum charging current under discharge is 0 7 amp Note Expected battery life is ...
Страница 4: ...AC or brownout fail is reported within 1 minute of event To delay reporting of up to 6 hrs cut AC delay jumper and reset power to unit Bat Fail NC C NO Indicates low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1 amp 28VDC BAT Stand by battery connections Maximum charge current 0 7 amp Enclosure Dimensions H x W x D 13 5 x 13 x 3 25 ...