- 3 - 

 

Power Supply Output  Specifications: 

Output  Switch Position 

12VDC  SW1 - CLOSED 

(Fig. 1a, pg. 4) 

24VDC  SW1 - OPEN 

(Fig. 1a, pg. 4) 

 

Stand-by Specifications 

(total current shown)

Output 

4 hr. of Stand-by & 

5 Minutes of Alarm 

24 hr. of Stand-by & 

5 Minutes of Alarm 

60 hr. of Stand-by & 

5 Minutes of Alarm 

12VDC / 40AH Battery 

Stand-by = 6.0 amp 

Alarm = 6.0 amp 

Stand-by = 1.0 amp 

Alarm = 6.0 amp 

Stand-by = 300mA 

Alarm = 6.0 amp 

24VDC / 12AH Battery 

-------- 

Stand-by = 200mA 

Alarm = 6.0 amp 

-------- 

24VDC / 40AH Battery 

Stand-by = 6.0 amp 

Alarm = 6.0 amp 

Stand-by = 1.0 amp 

Alarm = 6.0 amp 

Stand-by = 300mA 

Alarm = 6.0 amp 

LED Diagnostics: 

 

Red (DC)  Green (AC)  Red (BAT)  Status 

ON 

ON 

ON 

Normal operating condition. 

ON 

OFF 

ON 

Loss of AC. Stand-by battery supplying power. 

OFF 

ON 

OFF 

No DC output. Battery Trouble 

OFF 

OFF 

OFF 

Loss of AC. Discharged or no stand-by battery. No DC output. 

ON 

ON 

OFF 

Battery missing / Low battery. 

Terminal Identification: 

 

Terminal 

Legend 

Function/Description 

L, G, N 

Connect 115VAC 60 Hz. to these terminals: L to hot, N to Neutral. Do not use the [G] terminal. 

+ DC --- 

12VDC or 24VDC @ 6 amp continuous non power-limited output. 

AC Fail 
NC, C, NO 

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized 
when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 
minute of the event. To delay reporting for up to 6 hrs., cut “AC delay” jumper and reset power to unit. 

 

Bat Fail 
NC, C, NO 

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power 
is present. Contact rating 1 amp @ 28VDC. Low battery conditions will report approximately 21VDC 
(24VDC output setting) or approximately 10.5VDC (12VDC output setting). 
Battery presence detection will report approximately 1 minute after battery remains undetected 
(missing or removed). 

+ BAT --- 

Stand-by battery connections. Maximum charge current 0.7 amp. 

 

Use 14 AWG or larger for all power connections. 

Wiring: 

Note: 

Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery). 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

Output Voltage Test: 

Under normal load conditions the DC output voltage should be checked for proper voltage level 

(Power Supply Voltage Output Specifications Chart, pg. 3). 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified voltage both at the 

battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery 
connection wires. 

Note: 

Maximum charging current under discharges is 0.7 amp. 

Note: 

Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. 