OM-2226 / Operation and Maintenance Manual
60CU20 / Series 500062 / 400 Hz. Generator Set
May 2, 2013
Chapter 2-3
Page 3
b) Operational Test Procedures
(1) Start the engine in accordance with instructions in Section 1-3.
(2) Check operation of engine instruments; ammeter
,
coolant temperature indicator, oil pressure
gage and hour meter.
(3) Check engine idle speed. Should be 1000 +/- 25 RPM.
NOTE:
A stroboscope may be required for this check.
(4) Again check for oil, fuel, and coolant leaks and correct any leaking condition
.
(5) Position switches and controls for automatic voltage regulation and power delivery as follows:
a
Place regulated-diagnostic switch in “
REGULATED
” position.
b
Place EF Bypass switches in “
BYPASS / OFF
” position.
c
If the output voltage coarse adjustment potentiometer on the voltage regulator has been
disturbed, place the knob at mid-range position.
(6) Bring the engine up to rated speed, which also energize the generator, by pressing the “
ENGINE
START
” push button switch a second time. If the engine comes up to rated speed and a 115 V
voltage value appears on the voltmeter, the engine ECM and excitation circuits are functioning.
(7) After generator overhaul or repair, the Regulated/Diagnostic switch must be placed in the
“
DIAGNOSTIC
”
position for 3 to 5 seconds to re-magnetize the exciter. Then return the switch to
the “
REGULATED
” position after voltage has built-up.
(8) Observe frequency meter. If engine speed is properly set, frequency should read 400 Hz.
(9) Observe voltmeter. Use output fine voltage coarse adjustment potentiometer to adjust voltage to
115 V AC.
(10) Check adjustable voltage range.
a
Observe voltmeter and turn output voltage coarse adjustment potentiometer to full clockwise
position. Maximum voltage should be 134 volts or higher.
NOTE:
If voltage should decrease when regulator potentiometer is turned clockwise, it indicates that
internal wiring in the voltage regulator is incorrect. Replace complete voltage regulator assembly.
b
Observe voltmeter and turn regulator potentiometer knob to full counterclockwise position.
The minimum voltage should be 95 volts or lower.
(11) Position load bank switches, etc., to apply a light load to the generator.
Содержание 500062-DLX
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 209: ......
Страница 210: ......
Страница 211: ......
Страница 212: ......
Страница 213: ......
Страница 214: ......
Страница 215: ......
Страница 216: ......
Страница 217: ......
Страница 218: ......
Страница 219: ......
Страница 220: ......
Страница 221: ......
Страница 222: ......
Страница 223: ......
Страница 224: ......
Страница 225: ......
Страница 226: ......
Страница 227: ......
Страница 228: ......
Страница 229: ......
Страница 230: ......
Страница 231: ......
Страница 232: ......
Страница 233: ......
Страница 234: ......
Страница 235: ......
Страница 236: ......
Страница 237: ......
Страница 238: ......
Страница 239: ......
Страница 240: ......
Страница 241: ......
Страница 242: ......