Connections
8
Doc: HMSI-168-92 Rev: 3.10
Netbiter EasyConnect Gateway User Manual
2.2 Netbiter EC220
2.2.1 Terminal Block (12-pin)
Analog Input Configuration Switches
The
function
of
each
analog
input
can
be
selected
with
an
internal
DIP
switch.
The
default
setting
is
PT100
(temperature
sensor).
1.
Unscrew
the
two
top
screws
(A)
using
a
T10
torx
screwdriver.
2.
Loosen
the
two
lower
screws
(B)
but
do
not
remove
them.
3.
Lift
the
cover
carefully.
Take
care
not
to
damage
the
antenna
cable.
4.
Set
the
switch
to
match
the
desired
function
for
the
analog
input.
5.
Replace
the
cover,
again
taking
care
not
to
damage
the
antenna
cable.
6.
Re
‐
tighten
all
4
screws
.
Pin
Function
Note
+Vdc
Power 12–24 VDC
GND
PE ground
AO:OUT
Analog output
0–10 VDC
AO.COM
Analog output common
Internally connected to GND
AI:AI 1
Analog input #1
PT100, current or voltage
(selected with internal switch)
AI:AI 2
Analog input #2
AI:COM
Analog input common
Internally connected to GND
DI:DI1
Digital input #1
Low = 0–1 VDC, High = 9–24 VDC
DI:DI2
Digital input #2
DI:COM
Digital input common
Relay:COM
Relay output common
Relay:NO
Normally open connected
Rated load: 1 A @ 24 VDC
a
a. The relay output must be supplied from an isolating transformer using a secondary
listed fuse rated at maximum 3.3 A and minimum 30 VDC.
Setting
Function
Note
PT100
Temperature sensor
-50 to +150 °C (default)
0–20 mA
Current
Input resistance 270
0–10 VDC
Voltage
Input resistance 280
Содержание Netbiter EasyConnect
Страница 55: ...Technical Specifications 53 Doc HMSI 168 92 Rev 3 10 Netbiter EasyConnect Gateway User Manual Netbiter EC220...
Страница 56: ...Technical Specifications 54 Doc HMSI 168 92 Rev 3 10 Netbiter EasyConnect Gateway User Manual Netbiter EC250...
Страница 57: ...Technical Specifications 55 Doc HMSI 168 92 Rev 3 10 Netbiter EasyConnect Gateway User Manual Netbiter EC310...
Страница 58: ...Technical Specifications 56 Doc HMSI 168 92 Rev 3 10 Netbiter EasyConnect Gateway User Manual Netbiter EC350...