Intesis
TM
KNX
– BACnet Client
User Manual r1.2 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
17 / 26
Figure 5.4
Devices configuration section
Devices can be added in three ways:
•
Manually
: With checkbox ‘Use template’ disabled,
Add
button should be clicked. Number of devices to add
can be adjusted in the text field next to button
Add
.
•
From template
: Same as manual but based on a template file. This will add in Signals table all the signals
specified in the template file for the device to be integrated.
•
From scan
: Gives functionality to scan the BACnet network for existing BACnet server devices and their
objects, enabling to add them in the config. See section ‘BACnet scan functionality’ below for further detail.
Once a device is added, following fields must be filled in for each device:
Figure 5.5
Devices configuration section
1.
Device Name
. Device identifier within MAPS. It will be used to reference the device from the signals table
2.
Recipient Type
. Way in which the device will be identified within the BACnet network. Options are Device
(instance), Address, Address (MSTP). Depending on which option is chosen different parameters will appear
to enter the details of the address.
3.
(Recipient type: Device) Object Instance
: Instance number of device object for the BACnet server device.
4.
(Recipient type: Address) Network
: Destination network, 0..65535. 0 for local network, 65535 for broadcast
(all networks).
5.
(Recipient type: Address) IP / Port
: IP and Port of the BACnet server device.