4.2.5  Hisense configuration 

Set parameters for connection with Hisense’s installation. 
 

 

 

Figure 4.4 

Intesis MAPS Hisense configuration tab 

 
In Units Configuration section you need to enter, for each unit: 
 

 

Active

. If it’s active (checkbox at Unit xx), ranging from 1 to 64 indoor units that will be integrated (maximum 

number of units will depend on Intesis model) 

 

 

IU address

. Address 1..64 of Unit in Hisense H-Link bus.  

 

 

OU address

. Address 1..64 of Outdoor Unit in Hisense H-Link bus. 

 

 

Description

. Descriptive name to easy identification of the unit (for example, ‘living room floor 1 unit’, etc). 

 

Additional to manual entry of each unit, autodiscover of present units in an H-Link installation is possible. To do so, click 
button 

Scan

. Following window will appear: 

 

Содержание Intesis KNX - Hisense VRF

Страница 1: ...Hisense VRF Air Conditioning Gateway for the integration of Hisense VRF systems into KNX home automation systems USER MANUAL Issue date 01 2019 r1 1 ENGLISH ...

Страница 2: ...nd are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables and requirements associated with any particular implementation HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data examples or illustrations included in ...

Страница 3: ...U All rights reserved This information is subject to change without notice URL https www intesis com 3 30 Gateway for the integration of Hisense VRF systems into KNX home automation systems ORDER CODE LEGACY ORDER CODE INKNXHIS016O000 HS AC KNX 16 INKNXHIS064O000 HS AC KNX 64 ...

Страница 4: ...to KNX 10 Connection to the configuration tool 10 4 Set up process and troubleshooting 11 Pre requisites 11 Intesis MAPS Configuration monitoring tool for Intesis KNX series 11 4 2 1 Introduction 11 4 2 2 Connection 11 4 2 3 Configuration tab 12 4 2 4 KNX configuration 12 4 2 5 Hisense configuration 15 4 2 6 Signals 17 4 2 7 Sending the configuration to Intesis 18 4 2 8 Diagnostic 18 4 2 9 Set up ...

Страница 5: ...integration is to monitor and control your Hisense air conditioning system from your KNX TP 1 installation To do it so Intesis performs as a one more KNX device sending and receiving telegrams to group addresses in the KNX network Intesis makes available the Hisense air conditioning system indoor units datapoints through independent KNX objects Up to 64 indoor units supported depending on product ...

Страница 6: ... network for all configured signals and keeps the updated status of all of them in its memory It triggers updates on configured group addresses to KNX network on value change Commands toward the indoor unit communication adaptor are permitted Each indoor unit is offered as a set of KNX objects Element Object supported Outdoor Unit Communication status Status Indoor Unit Status Command Communicatio...

Страница 7: ... Element Max Notes Number of indoor units 64 Number of indoor units that can be controlled through Intesis There are different models of Intesis KNX Hisense VRF each one with different capacity The table above shows the capacity for the top model with maximum capacity Their order codes are INKNXHIS016O000 Model supporting up to 16 indoor units INKNXHIS064O000 Model supporting up to 64 indoor units...

Страница 8: ...ion object See details below Points definition Every group object in configuration has following KNX properties Property Description Description Descriptive information about the communication object or signal Object function Information on range of values for the group object DPT Datapoint type It is the KNX data type used to encode the signal s value It will depend on the type of signal associat...

Страница 9: ...t Connect the cable coming from the IP network to the connector ETH of the gateway Use an Ethernet CAT5 cable If communicating through the LAN of the building contact the network administrator and make sure traffic on the port used is allowed through all the LAN path check the gateway user manual for more information Default IP is 192 168 100 246 DHCP is enabled by default PortA KNX Connect the KN...

Страница 10: ...h The use of AC power supplies only if they are floating and not powering any other device Connect to Hisense installation Use the Port B connector of the Intesis device in order to connect Hisense H Link bus to the Intesis Remember to follow all safety precautions indicated by Hisense Connect the Hisense H Link bus to connectors B1 and B2 of gateway s PortB Bus is not sensitive to polarity Connec...

Страница 11: ...teway Link to download the configuration tool USB Console cable to communicate with Intesis Product documentation Intesis MAPS Configuration monitoring tool for Intesis KNX series 4 2 1 Introduction Intesis MAPS is a Windows compatible software developed specifically to monitor and configure Intesis new generation gateways The installation procedure and main functions are explained in the Intesis ...

Страница 12: ...ration tab Select the Configuration tab to configure the connection parameters Three subsets of information are shown in this window General Gateway general parameters KNX KNX interface configuration and Hisense Hisense interface parameters Figure 4 2 Intesis MAPS configuration tab 4 2 4 KNX configuration Set parameters of KNX interface of Intesis Figure 4 3 Intesis MAPS KNX configuration tab ...

Страница 13: ...objects the corresponding operating mode and ON operation is sent to the indoor unit Whenever both values are 0 indoor unit is set to OFF 2 3 Use of 1 bit Operating Modes 1 bit Control Objects Enables a bit type object for the control of each operating mode 2 4 Use of 1 bit Operating Modes 1 bit Status Objects Enables a bit type object for monitoring each operating mode 3 Temperature Sensor 3 1 Am...

Страница 14: ...t Fan Speed 1 bit Control Objects Enables a bit type object for control of fan speed 4 5 Use of 1 bit Fan Speed 1 bit Status Objects Enables a bit type object for monitoring of each fan speed 5 Vanes Position Settings related to KNX interface for control and feedback of AC unit s vanes position 4 1 Auto Swing Vanes Configures availability of Auto and Swing control monitoring objects 4 2 KNX DPT fo...

Страница 15: ...o enter for each unit Active If it s active checkbox at Unit xx ranging from 1 to 64 indoor units that will be integrated maximum number of units will depend on Intesis model IU address Address 1 64 of Unit in Hisense H Link bus OU address Address 1 64 of Outdoor Unit in Hisense H Link bus Description Descriptive name to easy identification of the unit for example living room floor 1 unit etc Addi...

Страница 16: ...ere is a problem in the connection with H Link bus units not powered bus not connected A progress bar will appear during the scan which will take up to a few minutes After scan is completed detected units will be shown in available units as follows Figure 4 6 Intesis MAPS Scan Hisense Units window with scan results Select with its checkbox units to add or replace in installation according to selec...

Страница 17: ...on is subject to change without notice URL https www intesis com 17 30 Figure 4 7 Intesis MAPS Hisense configuration tab after importing scan results 4 2 6 Signals All available KNX objects its corresponding description and other main parameters are listed in the signals tab Figure 4 8 Intesis MAPS Signals tab ...

Страница 18: ...Send button in the Receive Send section 4 2 8 Diagnostic To help integrators in the commissioning tasks and troubleshooting the Configuration Tool offers some specific tools and viewers In order to start using the diagnostic tools connection with the Gateway is required The Diagnostic section is composed by two main parts Tools and Viewers Tools Use the tools section to check the current hardware ...

Страница 19: ...MS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 19 30 Figure 4 10 Diagnostic More information about the Diagnostic section can be found in the Configuration Tool manual ...

Страница 20: ...ongly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected to earth The use of AC power supplies only if they are floating and not powering any other device 6 If you want to connect using IP connect the Ethernet cable from the laptop PC to the port marked as Ethernet of Intesis More details...

Страница 21: ...crew terminal block 3 poles 9 to 36VDC 10 Max 140mA 24VAC 10 50 60Hz Max 127mA Recommended 24VDC Push Button Button A Check the user manual Button B Check the user manual Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet LED port link and activity Operational Humidity 5 to 95 no condensation Port A 1 x KNX TP 1 Plug in screw terminal block orange 2 poles 2500VDC...

Страница 22: ...eserved This information is subject to change without notice URL https www intesis com 22 30 6 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting with space enough for external connections 100 mm h 100 mm w 130 mm d 56 mm h 88 mm w 90 mm d ...

Страница 23: ...ation is subject to change without notice URL https www intesis com 23 30 7 AC Unit Types compatibility A list of Hisense unit model references compatible with INKNXHIS016O000 INKNXHIS064O000 and their available features can be found in https www intesis com docs compatibilities inxxxhis001r000_compatibility ...

Страница 24: ...r OFF 04 Abnormality between lnverter PCB and Outdoor PCB lnverter PCB Outdoor PCB Transmission Failure Loose Connector Wire Breaking Blowout of Fuse 04 Abnormality between Fan Controller and Outdoor PCB Fan Controller Outdoor PCB Transmission Failure Loose Connector Wire Breaking Blowout of Fuse 05 Supply Phase Abnormality Power Source Phases lncorrect Power Source Connection to Reversed Phase Op...

Страница 25: ... Designed for R22 38 Abnormality of Picking up Circuit for Protection in Outdoor Unit Failure of Protection Detecting Device lncorrect Wiring of Outdoor PCB 39 Compressor Abnormality Running Current at Constant Speed Compressor Overcurrent Blowout Fuse Current Sensor Failure instantaneous Power Failure Voltage Drop Abnormal Power Supply 3A Outdoor Unit Abnormality of Outdoor Unit Capacity Outdoor ...

Страница 26: ...Heat Exchanger Clogging Fan Motor Failure 5b Activation of Overcurrent Protection Fan Motor Failure 5C Abnormality of Fan Controller Sensor Failure of Current Sensor lnstantaneous Overcurrent lncrease of Fin Temperature Low Voltage Earth Fault Step Out EE Compressor Compressor Protection Alarm lt is cannot be reset from remote Controller This alarm code appears when the following alarms occurs thr...

Страница 27: ...arm 1 005 R T 0 No error 1 Error TEMPERATURES Status_Outdoor Air Temperature ºC 2 byte DPT_Value_Temp 9 001 R T 50 99 ºC Status_Compresor Top Temperature ºC 2 byte DPT_Value_Temp 9 001 R T 0 200 ºC COMPRESOR Status_Total Real Compresor Freq 4 byte DPT_Value_Frequency 14 033 R T 0 255 Hz Status_Total Compresor Current 4 byte DPT_Value_Electric_Current 14 019 R T 0 255 A VALVE Status_Out Exp Valve 1...

Страница 28: ...enumerated 1 byte Non standarized 5 x R T 1 Low 2 Mid 3 High 4 High Control _Fan speed scaling 1 byte DPT_Scaling 5 001 W Thersholds 0 37 38 62 63 87 88 100 Status _Fan speed scaling 1 byte DPT_Scaling 5 001 R T Thersholds 25 50 75 100 Control_ Fan speed low 1 bit DPT_Switch 1 001 W 1 Set fan speed low Status_Fan speed low 1 bit DPT_Switch 1 001 R T 1 Speed low active 0 Speed low not active Contro...

Страница 29: ...tion 4 not active Control_Vane position position 5 1 bit DPT_Switch 1 001 R T 1 Set position 5 vane Status_Vane position position 5 1 bit DPT_Switch 1 001 W 1 Vane position 5 active 0 Vane position 5 not active Control_Vane position position 6 1 bit DPT_Switch 1 001 R T 1 Set position 6 vane Status_Vane position position 6 1 bit DPT_Switch 1 001 W 1 Vane position 6 active 0 Vane position 6 not act...

Страница 30: ...1 002 R T 0 No disabled 1 Disabled Control_Fan Remote controll disablement 1 bit DPT_Bool 1 002 W 0 No disabled 1 Disabled Status_Fan Remote controll disablement 1 bit DPT_Bool 1 002 R T 0 No disabled 1 Disabled SYSTEM INFO Status_Unit type 1 byte DPT_Value_1_Ucount 5 010 R T 1 SS 2 FC 3 VRF 4 IU 5 ES 13 Not Defined Status_Unit adress 1 byte DPT_Value_1_Ucount 5 010 R T 1 64 Status_System adress 1...