Intesis
TM
KNX
– Mitsubishi Electric
User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
26 / 32
VANE
POS
x
Vane position (all the groups)
1 byte
DPT_Value_1_Ucount
5.010
W
1
– Horizontal; 2 – Position-2; 3 –
Position-3; 4
– Position-4; 5 –
Vertical
x
Vane position AUTO (all the groups)
1 bit
DPT_Switch
1.001
W
0
– Stop auto vane; 1 – Set auto
vane
x
Vane position Swing (all the groups)
1 bit
DPT_Switch
1.001
W
0
– Stop swing vane; 1 – Set
swing vane;
SETP
TEMP
x
x
x
x
x Individual Temperature Setpoint (ºC)
2 byte
DPT_Value_Temp
9.001
W
5..90 ºC
GROUP
SIGNALS
ON / OFF
x
x
x
x
x
x Control_On/Off
1 bit
DPT_Switch
1.001
W
0
– Off; 1 – On
x
x
x
x
x
x Status_On/Off
1 bit
DPT_Switch
1.001
R
T
0
– Off; 1 – On
OP MODE
IC
x
x
Control_Operation mode IC
1 byte
DPT_HVACContrMode
20.105
W
0
– Auto; 1 – Heat; 3 – Cool; 9 –
Fan; 14
– Dry
x
x
Status_Operation mode IC
1 byte
DPT_HVACContrMode
20.105
R
T
0
– Auto; 1 – Heat; 3 – Cool; 9 –
Fan; 14
– Dry
x
x
Control_Operation mode IC
1 byte
Non-standarized
5.x
W
0
– Auto; 1 – Heat; 2 – Dry; 3 –
Fan; 4
– Cool; 5 – Setback
x
x
Status_Operation mode IC
1 byte
Non-standarized
5.x
R
T
0
– Auto; 1 – Heat; 2 – Dry; 3 –
Fan; 4
– Cool; 5 – Setback
x
x
Control_Mode Cool/Heat IC
1 bit
DPT_Heat/Cool
1.100
W
0
– Cool; 1 – Heat
x
x
Status_Mode Cool/Heat IC
1 bit
DPT_Heat/Cool
1.100
R
T
0
– Cool; 1 – Heat
x
x
Control_Heat mode&ON IC
1 byte
DPT_Scaling
5.001
W
0%
– Off, 0.1%-100% – On+Heat
x
x
Control_Cool mode&ON IC
1 byte
DPT_Scaling
5.001
R
T
0%
– Off, 0.1%-100% – On+Cool
x
x
Control_Auto mode IC
1 bit
DPT_Switch
1.001
W
1
– Set Auto mode
x
x
Status_Auto mode IC
1 bit
DPT_Switch
1.001
R
T
0
– Auto mode not active; 1 –
Auto mode active
x
x
Control_Heat mode IC
1 bit
DPT_Switch
1.001
W
1
– Set Heat mode
x
x
Status_Heat mode IC
1 bit
DPT_Switch
1.001
R
T
0
– Heat mode not active; 1 –
Heat mode active
x
x
Control_Cool mode IC
1 bit
DPT_Switch
1.001
W
1
– Set Cool mode
x
x
Status_Cool mode IC
1 bit
DPT_Switch
1.001
R
T
0
– Cool mode not active; 1 –
Cool mode active